Desa YGF33PRB, FPVF33NRA installation manual Ventilation AIR, Ventilation Air From Inside Building

Page 6

6

AIR FOR COMBUSTION AND VENTILATION

Determining Fresh-Air Flow for Heater Location (Cont.) Ventilation Air

AIR FOR COMBUSTION AND VENTILATION

Continued

The space in the example on page 5 is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the

extra space provides an unconfined space, remove door to adjoining

Ventilation

Grills

Into Adjoining

12"

Ventilation Grills Into Adjoining Room,

room or add ventilation grills between rooms. See Ventilation Air From

Room,

Or

Option 2

Inside Building.

Option 1

Remove

B.

Vent room directly to the outdoors. See Ventilation Air From Outdoors.

C.

Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an uncon- fined space or if the building is of unusually tight construction, provide adequate combustion and ven- tilation air by one of the methods described in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 Sec- tion 5.3 or applicable local codes.

Door into Adjoining Room, Option 3

12"

Figure 3 - Ventilation Air from Inside Building (FPVF33PRA Shown)

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 2). You can also remove door into adjoining room (see option 3, Figure 2). Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 4 - Ventilation Air from Outdoors (FPVF33PRA Shown)

For..com

110148-01B

Image 6
Contents Qqqq ¢¢¢¢ What to do if YOU Smell GASTable of Contents Safety InformationProduct Identification Other gasesUnpacking Product FeaturesLocal Codes AIR for Combustion and VentilationUnusually Tight Construction Providing Adequate VentilationDetermining FRESH-AIR Flow for Heater Location Confined and Unconfined SpaceVentilation AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors Check GAS Type InstallationInstalling Hood Electrical HookupInstallation Clearances Included with Mantel AccessoryAssembling and Attaching Optional Brass Trim Conventional Fireplace Installation Placing Hearth Base Accessory Against WallActual Framing Height Front Width 34 5 35 1 Depth 16 11 17 3 Support Bracket Firebox Wrapper Shield Power Screws Cord Installing GAS Piping to Fireplace Location Mantel Clearances for Built-In InstallationInstallation Items Needed Connecting Fireplace to GAS Supply Gas ConnectionPressure Testing gas Supply Piping system Checking GAS ConnectionsInstalling Logs Pressure Testing Fireplace Gas ConnectionsFPVF33PRA Installing Remote Receiver Unit Optional Wireless HAND-HELD RemoteInstalling 9-VOLT Batteries Installing 9-Volt Battery in ReceiverFor Your Safety Read Before Lighting Operating FireplaceLighting Instructions Manual Lighting Procedure To Turn OFF GAS To ApplianceOptional Remote Operation Pilot Flame Pattern Inspecting BurnersOptional Blower Operation Ghrc Series OperationBurner Primary AIR Holes Cleaning MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole Main BurnerWiring Diagram SpecificationsLogs Troubleshooting Observed Problem Possible Cause RemedyRefer to Air for Combustion and Venti Gas leak. See Warning statement Illustrated Parts Breakdown VYGF33PRBParts List KEY Part Number VYGF33PRB VYGF33NRB Description QTYFirebox VYGF33PRB VYGF33NRB Firebox VYGF33PRB & VYGF33NRB KEY Part Number Description QTYFPVF33PRA KEY Part Number FPVF33PRA FPVF33NRA Description QTY Firebox FPVF33PRA FPVF33NRA Firebox FPVF33PRA & FPVF33NRA Accessories WALL-MOUNT ON/OFF Switch GWMS2 Receiver and HAND-HELD Remote Control KIT Ghrc SeriesWALL-MOUNT Thermostat Switch GWMT1 Firebox Perimeter Brass Trim Accessory GA6090Service Hints Replacement PartsTechnical Service Parts Under WarrantyOwners Registration Form Postage Required 110148-01B Warranty Information