Desa FMH26TN Ventilation Air From Inside Building, Ventilation Air From Outdoors, Continued

Page 7
VENTILATION AIR

OWNER’S MANUAL

AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 5). You can also remove door into adjoining room (see op- tion 3, Figure 5). Follow the National Fuel

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code, ANSI Z223.1/NFPA 54, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

12"

Figure 5 - Ventilation Air from Inside Building Shown with Optional Mantel

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 6 - Ventilation Air from Outdoors Shown with Optional Mantel

107105

7

Image 7
Contents OWNER’S OPERATION AND INSTALLATION MANUAL VENT-FREENATURAL GAS FIREPLACE SYSTEMWHAT TO DO IF YOU SMELL GAS Do not try to light any applianceNATURAL GAS VENT-FREEFIREPLACE SYSTEM SAFETY INFORMATIONWARNINGS UNPACKING PRODUCT FEATURESSAFETY PILOT LOCAL CODESblower now. Follow installation in ASSEMBLYInstalling Log cessories, page 26. Install optionalConfined and Unconfined Space AIR FOR COMBUSTION AND VENTILATIONPROVIDING ADEQUATE VENTILATION Unusually Tight ConstructionContinued DETERMINING FRESH-AIRFLOW FOR FIREPLACE LOCATIONNATURAL GAS VENT-FREEFIREPLACE SYSTEM AIR FOR COMBUSTION AND VENTILATIONAIR FOR COMBUSTION AND VENTILATION VENTILATION AIRVentilation Air From Inside Building Ventilation Air From OutdoorsLOCATING FIREPLACE INSTALLATIONINSTALLATION ITEMS CHECK GAS TYPEINSTALLATION BUILT-INFIREPLACE INSTALLATIONContinued NATURAL GAS VENT-FREEFIREPLACE SYSTEM OPTIONAL MANTEL INSTALLATIONMantel Clearances for Built-InInstallation INSTALLATIONRemoving Valve Cover Shield INSTALLING BLOWER ACCESSORY GA3450TRemoving Upper Louver Assembly Installing Blower AssemblyContinued INSTALLATION9. Install the switch plate on the valve NATURAL GAS VENT-FREEFIREPLACE SYSTEMINSTALLATION For Built-InInstallationContinued INSTALLATION CONNECTING TO GAS SUPPLYExtension Cord Attaching Wood Base to Solid FloorINSTALLATION Installation Items NeededContinued INSTALLATION Pressure Testing Gas Supply Piping SystemPressure Testing Fireplace Gas Connections CHECKING GAS CONNECTIONSOPERATING FIREPLACE FOR YOUR SAFETY READ BEFORE LIGHTINGLIGHTING INSTRUCTIONS THERMOSTAT CONTROL OPERATION MANUAL LIGHTING PROCEDUREINSPECTING BURNER TO TURN OFF GAS TO APPLIANCEAir Passageways CLEANING AND MAINTENANCEBURNER FLAME PATTERN CABINETREMEDY TROUBLESHOOTINGOBSERVED PROBLEM POSSIBLE CAUSEContinued Maintenance, pageTROUBLESHOOTING OBSERVED PROBLEMOBSERVED PROBLEM ing Gas Connections, page1. Refer to Air for Combustion and Venti TROUBLESHOOTINGTECHNICAL SERVICE SPECIFICATIONSREPLACEMENT PARTS SERVICE HINTSFMH26TN ILLUSTRATED PARTS BREAKDOWNNATURAL GAS VENT-FREEFIREPLACE SYSTEM PARTS AVAILABLE - NOT SHOWN PARTS LISTFMH26TN DESCRIPTIONBRASS TRIM KIT - GA6094 ACCESSORIESCLEANING KIT - GCK EQUIPMENT SHUTOFF VALVE - GA5010Page Model Serial No Date Purchased WARRANTY INFORMATIONLIMITED WARRANTY NOT A UPC