CHECKING GAS

NATURAL GAS VENT-FREE FIREPLACE SYSTEM

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

Pressure Testing Gas Supply Piping System WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

Pressure Testing Fireplace Gas Connections WARNING: Never use an open flame to check for a leak. Apply a noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Fig- ure 26).

2.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

3.Check all joints from gas meter to equip- ment shutoff valve (see Figure 27). Apply a noncorrosive leak detection fluid to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Equipment

Open

Shutoff

 

Valve

 

 

O

 

Closed

 

PO

Figure 26 - Equipment Shutoff Valve

Pressure Testing Fireplace Gas Connections

1.Open equipment shutoff valve (see Fig- ure 26).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of fireplace is in the OFF position.

4.Check all joints from equipment shutoff valve to thermostat gas valve (see Fig- ure 27). Apply a noncorrosive leak de- tection fluid to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Light fireplace (see Operating Fire- place, pages 17 and 18). Check all other internal joints for leaks.

7.Turn off fireplace (see To Turn Off Gas to Appliance, page 18).

8.Replace front panel.

1.Disconnect appliance with its appliance main gas valve (control valve) and equip- ment shutoff valve from gas supply pip- ing system. Pressures in excess of 1/2 psig will damage fireplace regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either using compressed air or opening main gas valve located on or near gas meter.

4.Check all joints of gas supply piping system. Apply a noncorrosive leak de- tection fluid to gas joints. Bubbles forming show a leak.

5.Correct all leaks at once.

6.Reconnect heater and equipment shutoff valve to gas supply. Check re- connected fittings for leaks.

Equipment

Shutoff

Valve

Gas Meter

Figure 27 - Checking Gas Joints

16

107105

Image 16
Contents VENT-FREENATURAL GAS FIREPLACE SYSTEM WHAT TO DO IF YOU SMELL GASDo not try to light any appliance OWNER’S OPERATION AND INSTALLATION MANUALNATURAL GAS VENT-FREEFIREPLACE SYSTEM SAFETY INFORMATIONWARNINGS PRODUCT FEATURES SAFETY PILOTLOCAL CODES UNPACKINGASSEMBLY Installing Logcessories, page 26. Install optional blower now. Follow installation inAIR FOR COMBUSTION AND VENTILATION PROVIDING ADEQUATE VENTILATIONUnusually Tight Construction Confined and Unconfined SpaceDETERMINING FRESH-AIRFLOW FOR FIREPLACE LOCATION NATURAL GAS VENT-FREEFIREPLACE SYSTEMAIR FOR COMBUSTION AND VENTILATION ContinuedVENTILATION AIR Ventilation Air From Inside BuildingVentilation Air From Outdoors AIR FOR COMBUSTION AND VENTILATIONINSTALLATION INSTALLATION ITEMSCHECK GAS TYPE LOCATING FIREPLACEINSTALLATION BUILT-INFIREPLACE INSTALLATIONContinued OPTIONAL MANTEL INSTALLATION Mantel Clearances for Built-InInstallationINSTALLATION NATURAL GAS VENT-FREEFIREPLACE SYSTEMINSTALLING BLOWER ACCESSORY GA3450T Removing Upper Louver AssemblyInstalling Blower Assembly Removing Valve Cover ShieldINSTALLATION 9. Install the switch plate on the valveNATURAL GAS VENT-FREEFIREPLACE SYSTEM ContinuedINSTALLATION For Built-InInstallationContinued CONNECTING TO GAS SUPPLY Extension CordAttaching Wood Base to Solid Floor INSTALLATIONINSTALLATION Installation Items NeededContinued Pressure Testing Gas Supply Piping System Pressure Testing Fireplace Gas ConnectionsCHECKING GAS CONNECTIONS INSTALLATIONOPERATING FIREPLACE FOR YOUR SAFETY READ BEFORE LIGHTINGLIGHTING INSTRUCTIONS MANUAL LIGHTING PROCEDURE INSPECTING BURNERTO TURN OFF GAS TO APPLIANCE THERMOSTAT CONTROL OPERATIONCLEANING AND MAINTENANCE BURNER FLAME PATTERNCABINET Air PassagewaysTROUBLESHOOTING OBSERVED PROBLEMPOSSIBLE CAUSE REMEDYMaintenance, page TROUBLESHOOTINGOBSERVED PROBLEM Continueding Gas Connections, page 1. Refer to Air for Combustion and VentiTROUBLESHOOTING OBSERVED PROBLEMSPECIFICATIONS REPLACEMENT PARTSSERVICE HINTS TECHNICAL SERVICEFMH26TN ILLUSTRATED PARTS BREAKDOWNNATURAL GAS VENT-FREEFIREPLACE SYSTEM PARTS LIST FMH26TNDESCRIPTION PARTS AVAILABLE - NOT SHOWNACCESSORIES CLEANING KIT - GCKEQUIPMENT SHUTOFF VALVE - GA5010 BRASS TRIM KIT - GA6094Page WARRANTY INFORMATION LIMITED WARRANTYNOT A UPC Model Serial No Date Purchased