Toshiba RAV-SM1401AT-E Refrigerant Piping, No Good, Optional Installation Parts Local Procure

Models: RAV-SM561AT-E RAV-SM801AT-E RAV-SM1401AT-E RAV-SM1101AT-E

1 139
Download 139 pages 60.62 Kb
Page 9
Image 9

RAV-SM561AT-E, RAV-SM801AT-E

Optional Installation Parts (Local Procure)

 

Parts name

Q’ty

 

 

 

A

Refrigerant piping

Each one

Liquid side : Ø6.4 mm or Ø9.5 mm

 

Gas side : Ø12.7 mm or Ø15.9 mm

 

 

 

 

B

Pipe insulating material (polyethylene

1

foam, 6 mm thick)

 

 

 

 

 

 

C

Putty, PVC tapes

Each one

 

 

 

Refrigerant Piping Connection

<Piping connection>

Capacity

Liquid side

Gas side

rank

 

 

 

 

Outer

Thickness

Outer

Thickness

 

RAV-

diameter

diameter

 

 

 

 

 

SM56

Ø6.4

0.8

Ø12.7

0.8

 

 

 

 

 

SM80

Ø9.5

0.8

Ø15.9

1.0

 

 

 

 

 

CAUTION

TAKE NOTICE THESE IMPORTANT 4 POINTS BELOW FOR PIPING WORK

1.Keep dust and moisture away from inside the connecting pipes.

2.Tightly connect the connection between pipes and the unit.

3.Evacuate the air in the connecting pipes using VACUUM PUMP.

4.Check gas leak at connected points.

4 REFRIGERANT PIPING

Flaring

1. Cut the pipe with a pipe cutter.

OK

NO GOOD

90˚

Obliquity Roughness Warp

2.Insert a flare nut into the pipe, and flare the pipe.

As the flaring sizes of R410A differ from those of refrigerant R22, the flare tools newly manufactured for R410A are recommended.

However, the conventional tools can be used by adjusting projection margin of the copper pipe.

• Flaring size : A (Unit : mm)

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

+0

Outer diam. of copper pipe

- 0.4

 

 

 

R410A

 

R22

 

 

 

 

 

 

6.4

9.1

 

9.0

 

 

 

 

9.5

13.2

 

13.0

 

 

 

 

12.7

16.6

 

16.2

 

 

 

 

15.9

19.7

 

19.4

 

 

 

 

*In case of flaring for R410A with the conventional flare tool, pull it out approx. 0.5 mm more than that of R22 to adjust to the specified flare size.

The copper pipe gauge is useful for adjusting projection margin size.

Projection margin in flaring : B (Unit : mm)

B

Rigid (Clutch type)

Outer diam.

R410A tool used

Conventional tool used

of copper

 

 

 

 

 

 

R410A

R22

R410A

R22

pipe

 

 

 

 

 

 

6.4

 

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

 

9.5

 

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

 

12.7

 

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

 

15.9

 

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

 

Imperial (Wing nut type)

Outer diam. of copper pipe

R410A

R22

 

 

 

6.4

1.5 to 2.0

1.0 to 1.5

 

 

 

9.5

1.5 to 2.0

1.0 to 1.5

 

 

 

12.7

2.0 to 2.5

1.5 to 2.0

 

 

 

15.9

2.0 to 2.5

1.5 to 2.0

 

 

 

– 9 –