RAV-SM561AT-E, RAV-SM801AT-E, RAV-SM1101AT-E, RAV-SM1401AT-E
OUTDOOR UNIT
SPLIT TYPE
R410A
OUTDOOR
CONTENTS
INDOOR
4-Way Air Discharge Cassette Type
RAV-SM561AT-E, RAV-SM801AT-E
OUTDOOR
RAV-SM1101AT-E, RAV-SM1401AT-E
INSTALLATION MANUAL
New Refrigerant Air Conditioner Installation
1 PRECAUTIONS FOR SAFETY
To Disconnect the Appliance from Main Power Supply
Connect the connecting cable correctly
Accessory and Installation Parts
2 ACCESSORY AND REFRIGERANT
Required tools for installation work
Refrigerant Piping
Before installation
3 SELECTION OF INSTALLATION
Example
Length of refrigerant pipe SM56
Necessary Space for Installation
Installation Place
Obstacle at rear side Upper side is free
Obstacle at front side Upper side is free
Standard installation
Installation of Outdoor Unit
Serial installation at front and rear sides
Standard installation
NO GOOD
4 REFRIGERANT PIPING
Optional Installation Parts Local Procure
Refrigerant Piping Connection
NO GOOD
Tightening of Connecting Part
REQUIREMENT
Do not apply refrigerating machine oil to the flared surface
Air Purge
5 EVACUATING
Vacuum pump
RAV-SM561AT-E, RAV-SM801AT-E
Valve handling precautions
5 EVACUATING
RAV-SM561AT-E, RAV-SM801AT-E
How to remove the valve cover
6 ELECTRICAL WORK
How to wire
Tripping length power cord and connecting cable
Installation/Servicing Tools
7 FINAL INSTALLATION CHECKS
Check and Test Operation
Changes in the product and components
DANGER
8 APPLICABLE CONTROL OF OUTDOOR UNIT
Recovery method of refrigerant
Work procedure
New Refrigerant Air Conditioner Installation
1 PRECAUTIONS FOR SAFETY
To Disconnect the Appliance from Main Power Supply
Connect the connecting cable correctly
Required tools for installation work
Perform the specified installation work to guard against an earthquake
Be sure to provide grounding
R410A Special requirement
3 SELECTION OF INSTALLATION
2 ACCESSORY AND REFRIGERANT
Accessory and Installation Parts
Before installation
Necessary Space for Installation
Installation Place
Obstacle at rear side Upper side is free
Obstacle at front side Upper side is free
Standard installation
Installation of Outdoor Unit
Serial installation at front and rear sides
Standard installation
Knockout procedure
Optional Installation Parts Local Procure
Refrigerant Piping Connection
For Reference
4 REFRIGERANT PIPING
How to remove the front panel
NO GOOD
Pipe Forming/End Positioning
NO GOOD
Tightening of Connecting Part
REQUIREMENT
Do not apply refrigerating machine oil to the flared surface
Air Purge
5 EVACUATING
Vacuum pump
RAV-SM1101AT-E, RAV-SM1401AT-E
Valve handling precautions
How to open the valve
Charge hose For R410A only Service port Valve core Setting pin
Handle position
How to wire
Stripping length power cord and connecting cable
Single phase 50 Hz
Connecting cable
Check and Test Operation
7 FINAL INSTALLATION CHECKS
Useful Functions
Self-Diagnosis by LED Indication
Installation/Servicing Tools
Recovery method of refrigerant
Work procedure
DANGER
Demand control
8 APPLICABLE CONTROL OF OUTDOOR UNIT
Night operation control Sound reduction
Compressor operation output
INDOOR
CONTENTS
OWNER’S MANUAL
4-Way Air Discharge Cassette Type
PRECAUTIONS FOR SAFETY
ACCESSORIES SOLD SEPARATELY
WARNINGS ABOUT INSTALLATION
Remote controller
CAUTIONS ABOUT OPERATION
CAUTIONS ABOUT INSTALLATION
RAV-SP1100UT-E
RAV-SM560UT-E, RAV-SM800UT-E, RAV-SM1100UT-E, RAV-SM1400UT-E
Remote controller
PARTS NAME
Pipes and electric wires
Indoor unit
4 Timer time display
PARTS NAME OF REMOTE CONTROLLER
5 Timer SETIN setup display
10 Set up temperature display
2 Timer set button
1 Air volume select button
5 Filter reset button
10 Set up temperature button
Turn on the main power switch and/or the leakage breaker
CORRECT USAGE
3 Select air volume with “FAN ” button
Preparation
Temperature button
AUTOMATIC OPERATION Auto Changeover
When restarting the operation after stop
Start
How to set up the wind direction
ADJUSTMENT OF WIND DIRECTIONd
How to start swinging
How to stop swinging
Timer operation
TIMER OPERATION
Cancel of timer operation
1 Push TIMER SET button
Never open doors and windows more often than necessary
Maintain room temperature at comfortable level Clean air filters
Window curtains
Get uniform circulation of room air
Cleaning of remote controller
MAINTENANCE
power supply to the air conditioner
If you do not plan to use the unit for more than 1 month
Power failure
AIR CONDITIONER OPERATIONS AND PERFORMANCE
Heating characteristics Preheating operation
3 minutes protection function
TROUBLES AND CAUSES
RE-INSTALLATION
Do not install the air conditioner in the following places
DANGER
Does not cool well or heat well
Inoperative
Indoor unit or outdoor unit makes a strange noise
The room air is smelly or a bad odor comes from the air conditioner
PRECAUTIONS FOR SAFETY
ACCESSORIES SOLD SEPARATELY
Remote controller
WARNINGS ABOUT INSTALLATION
CAUTIONS ABOUT INSTALLATION
CAUTIONS ABOUT OPERATION
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
REMOTE CONTROLLER
Connecting duct
PARTS NAME
Indoor unit
4 Timer time display
PARTS NAME OF REMOTE CONTROLLER
11 Set up temperature display
12 Remote controller sensor display
5 Filter reset button
Timer set button
10 Set up temperature button
Remote controller sensor
3 Select air volume with “FAN ” button
Turn on the main power switch and/or the leakage breaker
CORRECT USAGE
Preparation
When restarting the operation after stop
Temperature button
AUTOMATIC OPERATION Auto Changeover
Start
Timer operation
TIMER OPERATION
Clear of timer operation
1 Push TIMER SET button
Do not open doors and windows more often than necessary
Maintain room temperature at comfortable level Clean air filters
Window curtains
Get uniform circulation of room air
Cleaning of remote controller
MAINTENANCE
If you do not plan to use the unit for more than 1 month
Checks before operation
Heating characteristics Preheating operation
Power failure
AIR CONDITIONER OPERATIONS AND PERFORMANCE
3 minutes protection function
Do not install the air conditioner in the following places
RE-INSTALLATION
TROUBLES AND CAUSES
DANGER
Does not cool well or heat well
Inoperative
Indoor unit or outdoor unit makes a strange noise
The room air is smelly or a bad odor comes from the air conditioner
AUTO
TROUBLES AND CAUSES Concerning Remote Controller
Setting Change is Impossible
Symptoms
PRECAUTIONS FOR SAFETY
ACCESSORIES SOLD SEPARATELY
Remote controller
WARNINGS ABOUT INSTALLATION
CAUTIONS ABOUT INSTALLATION
CAUTIONS ABOUT OPERATION
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
Pipes and electric wires
Remote controller
PARTS NAME
Indoor unit
4 Timer time display
PARTS NAME OF REMOTE CONTROLLER
5 Timer SETIN setup display
10 Set up temperature display
2 Timer set button
1 Air volume select button
5 Filter reset button
10 Set up temperature button
3 Select air volume with “FAN ” button
Turn on the main power switch and/or the leakage breaker
CORRECT USAGE
Preparation
When restarting the operation after stop
Temperature button
AUTOMATIC OPERATION Auto Changeover
Start
How to set up the wind direction
ADJUSTMENT OF WIND DIRECTION
How to start swinging
How to stop swinging
Timer operation
TIMER OPERATION
Cancel of timer operation
1 Push TIMER SET button
Never open doors and windows more often than necessary
Maintain room temperature at comfortable level Clean air filters
Window curtains
Get uniform circulation of room air
Cleaning of remote controller
MAINTENANCE
If you do not plan to use the unit for more than 1 month
Checks before operation
Heating characteristics Preheating operation
Power failure
AIR CONDITIONER OPERATIONS AND PERFORMANCE
3 minutes protection function
Do not install the air conditioner in the following places
RE-INSTALLATION
TROUBLES AND CAUSES
DANGER
Does not cool well or heat well
Inoperative
Indoor unit or outdoor unit makes a strange noise
The room air is smelly or a bad odor comes from the air conditioner
CONTENTS
INSTALLATION MANUAL
INDOOR
4-Way Air Discharge Cassette Type
H Accessory parts
Accessory parts and Parts to be procured locally
H Parts to be procured locally
Separate sold parts
1 PRECAUTIONS FOR SAFETY
WARNINGS
New Refrigerant Air Conditioner Installation
To Disconnect the Appliance from Main Power Supply
1 PRECAUTIONS FOR SAFETY
RAV-SP1100UT-E
RAV-SM560UT-E, RAV-SM800UT-E, RAV-SM1100UT-E, RAV-SM1400UT-E
Installation space
2 SELECTION OF INSTALLATION PLACE
Install the air conditioner at a height 2.5m or more from the floor
Avoid installing in the following places
Advice
Selection of installation place
Height list of ceiling possible to be installed
Discharge direction
REQUIREMENT
External view
RAV-SP1100UT-E
RAV-SM560UT-E, RAV-SM800UT-E, RAV-SM1100UT-E, RAV-SM1400UT-E
Installation of hanging bolt
Opening a ceiling and installation of hanging bolts
Installation of ceiling opening and hanging bolt
Treatment of ceiling
Installation of remote controller Sold separately
Installation of ceiling panel Sold separately
REQUIREMENT
REQUIREMENT
Piping/Heat insulating material
3 DRAIN PIPING WORK
REQUIREMENT
Flexible hose
Drain up
Connection procedure
Check the draining
Perform heat insulating
Refrigerant Piping
4 REFRIGERANT PIPING AND EVACUATING
Permissible Piping Length and Heat
Flaring diam. meter size A Unit mm
REQUIREMENT
Air purge
REQUIREMENT
REQUIREMENT
CAUTIONS
5 ELECTRICAL WORK
2. Be sure to connect earth wire. Grounding work
Remote controller wiring
Cable connection
Thermal insulation to cabling connecting port
REQUIREMENT
Cabling on the ceiling panel
Cabling diagram
Remote Controller Cabling
Wiring diagram
Cabling
How to execute a test run
6 TEST RUN
In case of wired remote controller
Before test run
Confirmation of error history
7 TROUBLESHOOTING
Confirmation and check
RAV-SP1100UT-E
Before maintenance, be sure to turn off the leakage breaker
8 MAINTENANCE
Cleaning of panel and air filter
Clean the panel and air filter with water
r Parts to be procured locally
r Accessory parts
Accessory parts and Parts to be procured locally
Separate sold parts
New Refrigerant Air Conditioner Installation
1 PRECAUTIONS FOR SAFETY
To Disconnect the Appliance from Main Power Supply
Connect the connecting cable correctly
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
1 PRECAUTIONS FOR SAFETY
Installation space
2 SELECTION OF INSTALLATION PLACE
Selection of installation place
Advice
3 INSTALLATION OF INDOOR UNIT
Installation procedure
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
External view
Dimension
REQUIREMENT
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
1. Hanging down of indoor unit
Mounting of clamp Accessory
Clamp mounting
Removal of air filter
1. Installation clearance
Restriction to installation
Concealed duct type
Ledge ceiling concealed duct type
Static pressure characteristics of each model
4 AIR DUCTING WORK
Fig. 1 RAV-SM561BT Round duct
Fig. 3 RAV-SM801BT Round duct
Fig. 7 RAV-SM1401BT Round duct
Fig. 5 RAV-SM1101BT Round duct
Fig. 6 RAV-SM1101BT Square duct
Fig. 8 RAV-SM1401BT Square duct
Installation reference Example for RAV-SM801BT model
Connecting method of the duct
Round duct
Square duct Reference for square duct
Points at installation work
Connecting method of the duct
1. Supply air side Round duct
Square duct
Hanging of indoor unit
Mounting of remote controller
Mounting of filter and canvas for suction port
For reference
Piping material
5 DRAIN PIPING WORK
Piping and cautions
Thermal-insulating process
Connection of the drain hose
Drain-up
Check of water drain
After electric piping work
Refrigerant piping
6 REFRIGERANT PIPING AND EVACUATING
Permissible piping length and heat
Flaring dia meter size A Unit mm
REQUIREMENT
Air purge
REQUIREMENT
REQUIREMENT
How to wire
7 ELECTRICAL WORK
CAUTIONS
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
Cabling diagram
Remote controller cabling
7 ELECTRICAL WORK
Cabling
How to execute a test run
8 TEST RUN
In case of wired remote controller
Before test run
Confirmation of error history
9 TROUBLESHOOTING
Confirmation and check
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
NOTIFICATION
10 APPLICABLE CONTROLS
Exchange of applicable control setup
Basic operation procedure for setup exchange
Setup of external static pressure
1 → 2 → 3 → 4 → 5 →
Exchange by wired remote controller
To incorporate a filter sold separately
1 → 2 → 3 → 4 → 5 →
1 → 2 → 3 → 4 → 5 →
Change of lighting time of filter sign
To secure better effect of heating
12 MAINTENANCE
11 INSTALLATION/SERVICING TOOLS
Cleaning of Return grille
Clean the Return grilles with water
r Accessory parts
Accessory parts and Parts to be procured locally
r Parts to be procured locally
Separate sold parts
New Refrigerant Air Conditioner Installation
1 PRECAUTIONS FOR SAFETY
To Disconnect the Appliance from Main Power Supply
Connect the connecting cable correctly
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
Installation space
2 SELECTION OF INSTALLATION PLACE
Perform a specified installation work to guard against an earth quake
Install the air conditioner at a height 2.5m or more from the floor
Before installation
In case of wireless type
List of installable ceiling height
Height of ceiling
Installation pattern
How to use attached installation pattern
External view
REQUIREMENT
Knockout hole of power cable take-in port
Installation of hanging bolts
Pipe knockout hole
Draw-out direction of pipe/cable
Installation of remote controller Sold separately
Installation of indoor unit
REQUIREMENT
Preparation before holding down main unit
Piping/Heat insulating material
3 DRAIN PIPING WORK
REQUIREMENT
Drain up
Thermal insulating process
Connection of drain hose
REQUIREMENT
Connection of drain pipe
Refrigerant Piping
4 REFRIGERANT PIPING AND EVACUATING
Permissible Piping Length and Heat
Flaring diam. meter size A Unit mm
REQUIREMENT
Air purge
REQUIREMENT
REQUIREMENT
Remote controller wiring
2. Be sure to connect earth wire. Grounding work
How to wire
5 ELECTRICAL WORK
Cable connection
5 ELECTRICAL WORK
REQUIREMENT
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
Cabling diagram
Remote Controller Cabling
Wiring diagram
Cabling
In case of wired remote controller
How to execute a test run
6 TEST RUN
Before test run
Confirmation of error history
7 TROUBLESHOOTING
Confirmation and check
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
Exchange of applicable control setup
8 APPLICABLE CONTROLS
Basic operation procedure for setup exchange
When power will be turned on after finish of automatic addressing
When using wireless remote controller
In case of installation to high ceiling
Exchange by wired remote controller
1 → 2 → 3 → 4 → 5 →
1 → 2 → 3 → 4 → 5 →
1 → 2 → 3 → 4 → 5 →
Change of lighting time of filter sign
To secure better effect of heating
10 MAINTENANCE
9 INSTALLATION/SERVICING TOOLS
Cleaning of Return grille
Clean the Return grilles with water
3 Soak up dust with a cleaner or clean with wash
Cleaning of air filter
1 Open the suction grille
4 Mount the air filter 5 Close the suction grille