RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E

10 APPLICABLE CONTROLS

Setup of external static pressure

Select with shifting of the short plug on the indoor unit microcomputer P.C. board.

Matching with the resistance (External static pressure) of the duct to be connected, be sure to set up the tap exchange according to the basic operation procedure

(1 2 3 4 5 6 ).

For the item code in Procedure 3, specify [5d].

For the set data in Procedure 4, select the setup data of static pressure outside of the machine to be set up from the table below.

(Exchange by wired remote controller)

Set data

 

 

External static pressure

 

 

 

 

 

0000

40Pa

 

 

Standard (At shipment)

 

 

 

 

 

0001

70Pa

*1

 

High static pressure 1

 

 

 

 

 

0003

100Pa

*2

 

High static pressure 2

 

 

 

 

 

0006

20Pa

 

 

Low static pressure

 

 

 

 

 

*1: For SM1401BT, set 65Pa.

*2: For SM1401BT, set 90Pa.

To incorporate a filter sold separately

Short plug position

External static

pressure

40Pa

Standard

(At shipment)

70Pa

High static-

pressure 1

100Pa

High static-

pressure 2

20Pa

Low static-

pressure

Filter sold separately

Standard filter (At shipment)

Optical regeneration deodorizing filter

*1

High-performance filter 65 High-performance filter 90 Deodorant filter Ammonia deodorizing filter

——

——

When mounting a filter sold separately, be sure to set up the tap exchange according to the type of filter.

In this case, also follow to the basic operation procedure (1 2 3 4 5 6 ).

For the item code in Procedure 3, specify [5d].

For the set data in Procedure 4, select the setup data of filter to be incorporated from the table below.

Set data

Filter sold separately

 

 

0000

Standard filter (At shipment)

 

 

 

Optical regeneration deodorizing filter

 

 

0001

High-performance filter 65, 90

 

 

 

Deodorant filter Ammonia deodorizing filter

 

 

*1 Resistance of high-performance filter 65 and 90, deodorant filter, or ammonia deodorizing filter is equivalent to 30Pa. Therefore, set the resistance (external static pressure) of a duct to be connected to 40Pa.

Short plug position

(CN112, CN111, CN110 from the left)

– 114 –

Page 114
Image 114
Toshiba RAV-SM801AT-E, RAV-SM1101AT-E Setup of external static pressure, To incorporate a filter sold separately