R410A
OUTDOOR UNIT
RAV-SM561AT-E, RAV-SM801AT-E, RAV-SM1101AT-E, RAV-SM1401AT-E
SPLIT TYPE
4-Way Air Discharge Cassette Type
CONTENTS
OUTDOOR
INDOOR
INSTALLATION MANUAL
OUTDOOR
RAV-SM561AT-E, RAV-SM801AT-E
RAV-SM1101AT-E, RAV-SM1401AT-E
Connect the connecting cable correctly
1 PRECAUTIONS FOR SAFETY
New Refrigerant Air Conditioner Installation
To Disconnect the Appliance from Main Power Supply
Refrigerant Piping
2 ACCESSORY AND REFRIGERANT
Accessory and Installation Parts
Required tools for installation work
Length of refrigerant pipe SM56
3 SELECTION OF INSTALLATION
Before installation
Example
Obstacle at front side Upper side is free
Installation Place
Necessary Space for Installation
Obstacle at rear side Upper side is free
Standard installation
Installation of Outdoor Unit
Standard installation
Serial installation at front and rear sides
Refrigerant Piping Connection
4 REFRIGERANT PIPING
NO GOOD
Optional Installation Parts Local Procure
Do not apply refrigerating machine oil to the flared surface
Tightening of Connecting Part
NO GOOD
REQUIREMENT
RAV-SM561AT-E, RAV-SM801AT-E
5 EVACUATING
Air Purge
Vacuum pump
Valve handling precautions
5 EVACUATING
RAV-SM561AT-E, RAV-SM801AT-E
Tripping length power cord and connecting cable
6 ELECTRICAL WORK
How to remove the valve cover
How to wire
Changes in the product and components
7 FINAL INSTALLATION CHECKS
Installation/Servicing Tools
Check and Test Operation
Work procedure
8 APPLICABLE CONTROL OF OUTDOOR UNIT
DANGER
Recovery method of refrigerant
Connect the connecting cable correctly
1 PRECAUTIONS FOR SAFETY
New Refrigerant Air Conditioner Installation
To Disconnect the Appliance from Main Power Supply
R410A Special requirement
Perform the specified installation work to guard against an earthquake
Required tools for installation work
Be sure to provide grounding
Before installation
2 ACCESSORY AND REFRIGERANT
3 SELECTION OF INSTALLATION
Accessory and Installation Parts
Obstacle at front side Upper side is free
Installation Place
Necessary Space for Installation
Obstacle at rear side Upper side is free
Standard installation
Installation of Outdoor Unit
Standard installation
Serial installation at front and rear sides
For Reference
Optional Installation Parts Local Procure
Knockout procedure
Refrigerant Piping Connection
Pipe Forming/End Positioning
How to remove the front panel
4 REFRIGERANT PIPING
NO GOOD
Do not apply refrigerating machine oil to the flared surface
Tightening of Connecting Part
NO GOOD
REQUIREMENT
RAV-SM1101AT-E, RAV-SM1401AT-E
5 EVACUATING
Air Purge
Vacuum pump
Handle position
How to open the valve
Valve handling precautions
Charge hose For R410A only Service port Valve core Setting pin
Connecting cable
Stripping length power cord and connecting cable
How to wire
Single phase 50 Hz
Self-Diagnosis by LED Indication
7 FINAL INSTALLATION CHECKS
Check and Test Operation
Useful Functions
DANGER
Recovery method of refrigerant
Installation/Servicing Tools
Work procedure
Compressor operation output
8 APPLICABLE CONTROL OF OUTDOOR UNIT
Demand control
Night operation control Sound reduction
4-Way Air Discharge Cassette Type
CONTENTS
INDOOR
OWNER’S MANUAL
Remote controller
ACCESSORIES SOLD SEPARATELY
PRECAUTIONS FOR SAFETY
WARNINGS ABOUT INSTALLATION
RAV-SM560UT-E, RAV-SM800UT-E, RAV-SM1100UT-E, RAV-SM1400UT-E
CAUTIONS ABOUT INSTALLATION
CAUTIONS ABOUT OPERATION
RAV-SP1100UT-E
Indoor unit
PARTS NAME
Remote controller
Pipes and electric wires
10 Set up temperature display
PARTS NAME OF REMOTE CONTROLLER
4 Timer time display
5 Timer SETIN setup display
10 Set up temperature button
1 Air volume select button
2 Timer set button
5 Filter reset button
Preparation
CORRECT USAGE
Turn on the main power switch and/or the leakage breaker
3 Select air volume with “FAN ” button
Start
AUTOMATIC OPERATION Auto Changeover
Temperature button
When restarting the operation after stop
How to stop swinging
ADJUSTMENT OF WIND DIRECTIONd
How to set up the wind direction
How to start swinging
1 Push TIMER SET button
TIMER OPERATION
Timer operation
Cancel of timer operation
Get uniform circulation of room air
Maintain room temperature at comfortable level Clean air filters
Never open doors and windows more often than necessary
Window curtains
If you do not plan to use the unit for more than 1 month
MAINTENANCE
Cleaning of remote controller
power supply to the air conditioner
3 minutes protection function
AIR CONDITIONER OPERATIONS AND PERFORMANCE
Power failure
Heating characteristics Preheating operation
DANGER
RE-INSTALLATION
TROUBLES AND CAUSES
Do not install the air conditioner in the following places
The room air is smelly or a bad odor comes from the air conditioner
Inoperative
Does not cool well or heat well
Indoor unit or outdoor unit makes a strange noise
WARNINGS ABOUT INSTALLATION
ACCESSORIES SOLD SEPARATELY
PRECAUTIONS FOR SAFETY
Remote controller
CAUTIONS ABOUT INSTALLATION
CAUTIONS ABOUT OPERATION
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
Indoor unit
Connecting duct
REMOTE CONTROLLER
PARTS NAME
12 Remote controller sensor display
PARTS NAME OF REMOTE CONTROLLER
4 Timer time display
11 Set up temperature display
Remote controller sensor
Timer set button
5 Filter reset button
10 Set up temperature button
Preparation
Turn on the main power switch and/or the leakage breaker
3 Select air volume with “FAN ” button
CORRECT USAGE
Start
Temperature button
When restarting the operation after stop
AUTOMATIC OPERATION Auto Changeover
1 Push TIMER SET button
TIMER OPERATION
Timer operation
Clear of timer operation
Get uniform circulation of room air
Maintain room temperature at comfortable level Clean air filters
Do not open doors and windows more often than necessary
Window curtains
Checks before operation
MAINTENANCE
Cleaning of remote controller
If you do not plan to use the unit for more than 1 month
3 minutes protection function
Power failure
Heating characteristics Preheating operation
AIR CONDITIONER OPERATIONS AND PERFORMANCE
DANGER
RE-INSTALLATION
Do not install the air conditioner in the following places
TROUBLES AND CAUSES
The room air is smelly or a bad odor comes from the air conditioner
Inoperative
Does not cool well or heat well
Indoor unit or outdoor unit makes a strange noise
Symptoms
TROUBLES AND CAUSES Concerning Remote Controller
AUTO
Setting Change is Impossible
WARNINGS ABOUT INSTALLATION
ACCESSORIES SOLD SEPARATELY
PRECAUTIONS FOR SAFETY
Remote controller
CAUTIONS ABOUT INSTALLATION
CAUTIONS ABOUT OPERATION
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
Indoor unit
Remote controller
Pipes and electric wires
PARTS NAME
10 Set up temperature display
PARTS NAME OF REMOTE CONTROLLER
4 Timer time display
5 Timer SETIN setup display
10 Set up temperature button
1 Air volume select button
2 Timer set button
5 Filter reset button
Preparation
Turn on the main power switch and/or the leakage breaker
3 Select air volume with “FAN ” button
CORRECT USAGE
Start
Temperature button
When restarting the operation after stop
AUTOMATIC OPERATION Auto Changeover
How to stop swinging
ADJUSTMENT OF WIND DIRECTION
How to set up the wind direction
How to start swinging
1 Push TIMER SET button
TIMER OPERATION
Timer operation
Cancel of timer operation
Get uniform circulation of room air
Maintain room temperature at comfortable level Clean air filters
Never open doors and windows more often than necessary
Window curtains
Checks before operation
MAINTENANCE
Cleaning of remote controller
If you do not plan to use the unit for more than 1 month
3 minutes protection function
Power failure
Heating characteristics Preheating operation
AIR CONDITIONER OPERATIONS AND PERFORMANCE
DANGER
RE-INSTALLATION
Do not install the air conditioner in the following places
TROUBLES AND CAUSES
The room air is smelly or a bad odor comes from the air conditioner
Inoperative
Does not cool well or heat well
Indoor unit or outdoor unit makes a strange noise
4-Way Air Discharge Cassette Type
INSTALLATION MANUAL
CONTENTS
INDOOR
Separate sold parts
Accessory parts and Parts to be procured locally
H Accessory parts
H Parts to be procured locally
To Disconnect the Appliance from Main Power Supply
WARNINGS
1 PRECAUTIONS FOR SAFETY
New Refrigerant Air Conditioner Installation
1 PRECAUTIONS FOR SAFETY
RAV-SP1100UT-E
RAV-SM560UT-E, RAV-SM800UT-E, RAV-SM1100UT-E, RAV-SM1400UT-E
Avoid installing in the following places
2 SELECTION OF INSTALLATION PLACE
Installation space
Install the air conditioner at a height 2.5m or more from the floor
Discharge direction
Selection of installation place
Advice
Height list of ceiling possible to be installed
RAV-SM560UT-E, RAV-SM800UT-E, RAV-SM1100UT-E, RAV-SM1400UT-E
External view
REQUIREMENT
RAV-SP1100UT-E
Treatment of ceiling
Opening a ceiling and installation of hanging bolts
Installation of hanging bolt
Installation of ceiling opening and hanging bolt
REQUIREMENT
Installation of ceiling panel Sold separately
Installation of remote controller Sold separately
REQUIREMENT
Flexible hose
3 DRAIN PIPING WORK
Piping/Heat insulating material
REQUIREMENT
Perform heat insulating
Connection procedure
Drain up
Check the draining
Flaring diam. meter size A Unit mm
4 REFRIGERANT PIPING AND EVACUATING
Refrigerant Piping
Permissible Piping Length and Heat
REQUIREMENT
Air purge
REQUIREMENT
REQUIREMENT
Remote controller wiring
5 ELECTRICAL WORK
CAUTIONS
2. Be sure to connect earth wire. Grounding work
Cabling on the ceiling panel
Thermal insulation to cabling connecting port
Cable connection
REQUIREMENT
Cabling
Remote Controller Cabling
Cabling diagram
Wiring diagram
Before test run
6 TEST RUN
How to execute a test run
In case of wired remote controller
RAV-SP1100UT-E
7 TROUBLESHOOTING
Confirmation of error history
Confirmation and check
Clean the panel and air filter with water
8 MAINTENANCE
Before maintenance, be sure to turn off the leakage breaker
Cleaning of panel and air filter
Separate sold parts
r Accessory parts
r Parts to be procured locally
Accessory parts and Parts to be procured locally
Connect the connecting cable correctly
1 PRECAUTIONS FOR SAFETY
New Refrigerant Air Conditioner Installation
To Disconnect the Appliance from Main Power Supply
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
1 PRECAUTIONS FOR SAFETY
Advice
2 SELECTION OF INSTALLATION PLACE
Installation space
Selection of installation place
3 INSTALLATION OF INDOOR UNIT
Installation procedure
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
Dimension
External view
REQUIREMENT
Removal of air filter
Mounting of clamp Accessory
1. Hanging down of indoor unit
Clamp mounting
Ledge ceiling concealed duct type
Restriction to installation
1. Installation clearance
Concealed duct type
Fig. 3 RAV-SM801BT Round duct
4 AIR DUCTING WORK
Static pressure characteristics of each model
Fig. 1 RAV-SM561BT Round duct
Fig. 8 RAV-SM1401BT Square duct
Fig. 5 RAV-SM1101BT Round duct
Fig. 7 RAV-SM1401BT Round duct
Fig. 6 RAV-SM1101BT Square duct
Square duct Reference for square duct
Connecting method of the duct
Installation reference Example for RAV-SM801BT model
Round duct
Square duct
Connecting method of the duct
Points at installation work
1. Supply air side Round duct
For reference
Mounting of remote controller
Hanging of indoor unit
Mounting of filter and canvas for suction port
Thermal-insulating process
5 DRAIN PIPING WORK
Piping material
Piping and cautions
After electric piping work
Drain-up
Connection of the drain hose
Check of water drain
Flaring dia meter size A Unit mm
6 REFRIGERANT PIPING AND EVACUATING
Refrigerant piping
Permissible piping length and heat
REQUIREMENT
Air purge
REQUIREMENT
REQUIREMENT
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
7 ELECTRICAL WORK
How to wire
CAUTIONS
Cabling
Remote controller cabling
Cabling diagram
7 ELECTRICAL WORK
Before test run
8 TEST RUN
How to execute a test run
In case of wired remote controller
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
9 TROUBLESHOOTING
Confirmation of error history
Confirmation and check
Basic operation procedure for setup exchange
10 APPLICABLE CONTROLS
NOTIFICATION
Exchange of applicable control setup
To incorporate a filter sold separately
1 → 2 → 3 → 4 → 5 →
Setup of external static pressure
Exchange by wired remote controller
To secure better effect of heating
1 → 2 → 3 → 4 → 5 →
1 → 2 → 3 → 4 → 5 →
Change of lighting time of filter sign
Clean the Return grilles with water
11 INSTALLATION/SERVICING TOOLS
12 MAINTENANCE
Cleaning of Return grille
Separate sold parts
Accessory parts and Parts to be procured locally
r Accessory parts
r Parts to be procured locally
Connect the connecting cable correctly
1 PRECAUTIONS FOR SAFETY
New Refrigerant Air Conditioner Installation
To Disconnect the Appliance from Main Power Supply
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
Install the air conditioner at a height 2.5m or more from the floor
2 SELECTION OF INSTALLATION PLACE
Installation space
Perform a specified installation work to guard against an earth quake
Height of ceiling
In case of wireless type
Before installation
List of installable ceiling height
REQUIREMENT
How to use attached installation pattern
Installation pattern
External view
Draw-out direction of pipe/cable
Installation of hanging bolts
Knockout hole of power cable take-in port
Pipe knockout hole
Preparation before holding down main unit
Installation of indoor unit
Installation of remote controller Sold separately
REQUIREMENT
Drain up
3 DRAIN PIPING WORK
Piping/Heat insulating material
REQUIREMENT
Connection of drain pipe
Connection of drain hose
Thermal insulating process
REQUIREMENT
Flaring diam. meter size A Unit mm
4 REFRIGERANT PIPING AND EVACUATING
Refrigerant Piping
Permissible Piping Length and Heat
REQUIREMENT
Air purge
REQUIREMENT
REQUIREMENT
5 ELECTRICAL WORK
2. Be sure to connect earth wire. Grounding work
Remote controller wiring
How to wire
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
5 ELECTRICAL WORK
Cable connection
REQUIREMENT
Cabling
Remote Controller Cabling
Cabling diagram
Wiring diagram
Before test run
How to execute a test run
In case of wired remote controller
6 TEST RUN
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
7 TROUBLESHOOTING
Confirmation of error history
Confirmation and check
When power will be turned on after finish of automatic addressing
8 APPLICABLE CONTROLS
Exchange of applicable control setup
Basic operation procedure for setup exchange
1 → 2 → 3 → 4 → 5 →
In case of installation to high ceiling
When using wireless remote controller
Exchange by wired remote controller
To secure better effect of heating
1 → 2 → 3 → 4 → 5 →
1 → 2 → 3 → 4 → 5 →
Change of lighting time of filter sign
Clean the Return grilles with water
9 INSTALLATION/SERVICING TOOLS
10 MAINTENANCE
Cleaning of Return grille
4 Mount the air filter 5 Close the suction grille
Cleaning of air filter
3 Soak up dust with a cleaner or clean with wash
1 Open the suction grille