OUTDOOR UNIT
RAV-SM561AT-E, RAV-SM801AT-E, RAV-SM1101AT-E, RAV-SM1401AT-E
SPLIT TYPE
R410A
CONTENTS
OUTDOOR
INDOOR
4-Way Air Discharge Cassette Type
OUTDOOR
RAV-SM561AT-E, RAV-SM801AT-E
RAV-SM1101AT-E, RAV-SM1401AT-E
INSTALLATION MANUAL
1 PRECAUTIONS FOR SAFETY
New Refrigerant Air Conditioner Installation
To Disconnect the Appliance from Main Power Supply
Connect the connecting cable correctly
2 ACCESSORY AND REFRIGERANT
Accessory and Installation Parts
Required tools for installation work
Refrigerant Piping
3 SELECTION OF INSTALLATION
Before installation
Example
Length of refrigerant pipe SM56
Installation Place
Necessary Space for Installation
Obstacle at rear side Upper side is free
Obstacle at front side Upper side is free
Installation of Outdoor Unit
Standard installation
Serial installation at front and rear sides
Standard installation
4 REFRIGERANT PIPING
NO GOOD
Optional Installation Parts Local Procure
Refrigerant Piping Connection
Tightening of Connecting Part
NO GOOD
REQUIREMENT
Do not apply refrigerating machine oil to the flared surface
5 EVACUATING
Air Purge
Vacuum pump
RAV-SM561AT-E, RAV-SM801AT-E
5 EVACUATING
Valve handling precautions
RAV-SM561AT-E, RAV-SM801AT-E
6 ELECTRICAL WORK
How to remove the valve cover
How to wire
Tripping length power cord and connecting cable
7 FINAL INSTALLATION CHECKS
Installation/Servicing Tools
Check and Test Operation
Changes in the product and components
8 APPLICABLE CONTROL OF OUTDOOR UNIT
DANGER
Recovery method of refrigerant
Work procedure
1 PRECAUTIONS FOR SAFETY
New Refrigerant Air Conditioner Installation
To Disconnect the Appliance from Main Power Supply
Connect the connecting cable correctly
Perform the specified installation work to guard against an earthquake
Required tools for installation work
Be sure to provide grounding
R410A Special requirement
2 ACCESSORY AND REFRIGERANT
3 SELECTION OF INSTALLATION
Accessory and Installation Parts
Before installation
Installation Place
Necessary Space for Installation
Obstacle at rear side Upper side is free
Obstacle at front side Upper side is free
Installation of Outdoor Unit
Standard installation
Serial installation at front and rear sides
Standard installation
Optional Installation Parts Local Procure
Knockout procedure
Refrigerant Piping Connection
For Reference
How to remove the front panel
4 REFRIGERANT PIPING
NO GOOD
Pipe Forming/End Positioning
Tightening of Connecting Part
NO GOOD
REQUIREMENT
Do not apply refrigerating machine oil to the flared surface
5 EVACUATING
Air Purge
Vacuum pump
RAV-SM1101AT-E, RAV-SM1401AT-E
How to open the valve
Valve handling precautions
Charge hose For R410A only Service port Valve core Setting pin
Handle position
Stripping length power cord and connecting cable
How to wire
Single phase 50 Hz
Connecting cable
7 FINAL INSTALLATION CHECKS
Check and Test Operation
Useful Functions
Self-Diagnosis by LED Indication
Recovery method of refrigerant
Installation/Servicing Tools
Work procedure
DANGER
8 APPLICABLE CONTROL OF OUTDOOR UNIT
Demand control
Night operation control Sound reduction
Compressor operation output
CONTENTS
INDOOR
OWNER’S MANUAL
4-Way Air Discharge Cassette Type
ACCESSORIES SOLD SEPARATELY
PRECAUTIONS FOR SAFETY
WARNINGS ABOUT INSTALLATION
Remote controller
CAUTIONS ABOUT INSTALLATION
CAUTIONS ABOUT OPERATION
RAV-SP1100UT-E
RAV-SM560UT-E, RAV-SM800UT-E, RAV-SM1100UT-E, RAV-SM1400UT-E
PARTS NAME
Remote controller
Pipes and electric wires
Indoor unit
PARTS NAME OF REMOTE CONTROLLER
4 Timer time display
5 Timer SETIN setup display
10 Set up temperature display
1 Air volume select button
2 Timer set button
5 Filter reset button
10 Set up temperature button
CORRECT USAGE
Turn on the main power switch and/or the leakage breaker
3 Select air volume with “FAN ” button
Preparation
AUTOMATIC OPERATION Auto Changeover
Temperature button
When restarting the operation after stop
Start
ADJUSTMENT OF WIND DIRECTIONd
How to set up the wind direction
How to start swinging
How to stop swinging
TIMER OPERATION
Timer operation
Cancel of timer operation
1 Push TIMER SET button
Maintain room temperature at comfortable level Clean air filters
Never open doors and windows more often than necessary
Window curtains
Get uniform circulation of room air
MAINTENANCE
Cleaning of remote controller
power supply to the air conditioner
If you do not plan to use the unit for more than 1 month
AIR CONDITIONER OPERATIONS AND PERFORMANCE
Power failure
Heating characteristics Preheating operation
3 minutes protection function
RE-INSTALLATION
TROUBLES AND CAUSES
Do not install the air conditioner in the following places
DANGER
Inoperative
Does not cool well or heat well
Indoor unit or outdoor unit makes a strange noise
The room air is smelly or a bad odor comes from the air conditioner
ACCESSORIES SOLD SEPARATELY
PRECAUTIONS FOR SAFETY
Remote controller
WARNINGS ABOUT INSTALLATION
CAUTIONS ABOUT OPERATION
CAUTIONS ABOUT INSTALLATION
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
Connecting duct
REMOTE CONTROLLER
PARTS NAME
Indoor unit
PARTS NAME OF REMOTE CONTROLLER
4 Timer time display
11 Set up temperature display
12 Remote controller sensor display
Timer set button
5 Filter reset button
10 Set up temperature button
Remote controller sensor
Turn on the main power switch and/or the leakage breaker
3 Select air volume with “FAN ” button
CORRECT USAGE
Preparation
Temperature button
When restarting the operation after stop
AUTOMATIC OPERATION Auto Changeover
Start
TIMER OPERATION
Timer operation
Clear of timer operation
1 Push TIMER SET button
Maintain room temperature at comfortable level Clean air filters
Do not open doors and windows more often than necessary
Window curtains
Get uniform circulation of room air
MAINTENANCE
Cleaning of remote controller
If you do not plan to use the unit for more than 1 month
Checks before operation
Power failure
Heating characteristics Preheating operation
AIR CONDITIONER OPERATIONS AND PERFORMANCE
3 minutes protection function
RE-INSTALLATION
Do not install the air conditioner in the following places
TROUBLES AND CAUSES
DANGER
Inoperative
Does not cool well or heat well
Indoor unit or outdoor unit makes a strange noise
The room air is smelly or a bad odor comes from the air conditioner
TROUBLES AND CAUSES Concerning Remote Controller
AUTO
Setting Change is Impossible
Symptoms
ACCESSORIES SOLD SEPARATELY
PRECAUTIONS FOR SAFETY
Remote controller
WARNINGS ABOUT INSTALLATION
CAUTIONS ABOUT OPERATION
CAUTIONS ABOUT INSTALLATION
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
Remote controller
Pipes and electric wires
PARTS NAME
Indoor unit
PARTS NAME OF REMOTE CONTROLLER
4 Timer time display
5 Timer SETIN setup display
10 Set up temperature display
1 Air volume select button
2 Timer set button
5 Filter reset button
10 Set up temperature button
Turn on the main power switch and/or the leakage breaker
3 Select air volume with “FAN ” button
CORRECT USAGE
Preparation
Temperature button
When restarting the operation after stop
AUTOMATIC OPERATION Auto Changeover
Start
ADJUSTMENT OF WIND DIRECTION
How to set up the wind direction
How to start swinging
How to stop swinging
TIMER OPERATION
Timer operation
Cancel of timer operation
1 Push TIMER SET button
Maintain room temperature at comfortable level Clean air filters
Never open doors and windows more often than necessary
Window curtains
Get uniform circulation of room air
MAINTENANCE
Cleaning of remote controller
If you do not plan to use the unit for more than 1 month
Checks before operation
Power failure
Heating characteristics Preheating operation
AIR CONDITIONER OPERATIONS AND PERFORMANCE
3 minutes protection function
RE-INSTALLATION
Do not install the air conditioner in the following places
TROUBLES AND CAUSES
DANGER
Inoperative
Does not cool well or heat well
Indoor unit or outdoor unit makes a strange noise
The room air is smelly or a bad odor comes from the air conditioner
INSTALLATION MANUAL
CONTENTS
INDOOR
4-Way Air Discharge Cassette Type
Accessory parts and Parts to be procured locally
H Accessory parts
H Parts to be procured locally
Separate sold parts
WARNINGS
1 PRECAUTIONS FOR SAFETY
New Refrigerant Air Conditioner Installation
To Disconnect the Appliance from Main Power Supply
RAV-SP1100UT-E
1 PRECAUTIONS FOR SAFETY
RAV-SM560UT-E, RAV-SM800UT-E, RAV-SM1100UT-E, RAV-SM1400UT-E
2 SELECTION OF INSTALLATION PLACE
Installation space
Install the air conditioner at a height 2.5m or more from the floor
Avoid installing in the following places
Selection of installation place
Advice
Height list of ceiling possible to be installed
Discharge direction
External view
REQUIREMENT
RAV-SP1100UT-E
RAV-SM560UT-E, RAV-SM800UT-E, RAV-SM1100UT-E, RAV-SM1400UT-E
Opening a ceiling and installation of hanging bolts
Installation of hanging bolt
Installation of ceiling opening and hanging bolt
Treatment of ceiling
Installation of ceiling panel Sold separately
Installation of remote controller Sold separately
REQUIREMENT
REQUIREMENT
3 DRAIN PIPING WORK
Piping/Heat insulating material
REQUIREMENT
Flexible hose
Connection procedure
Drain up
Check the draining
Perform heat insulating
4 REFRIGERANT PIPING AND EVACUATING
Refrigerant Piping
Permissible Piping Length and Heat
Flaring diam. meter size A Unit mm
Air purge
REQUIREMENT
REQUIREMENT
REQUIREMENT
5 ELECTRICAL WORK
CAUTIONS
2. Be sure to connect earth wire. Grounding work
Remote controller wiring
Thermal insulation to cabling connecting port
Cable connection
REQUIREMENT
Cabling on the ceiling panel
Remote Controller Cabling
Cabling diagram
Wiring diagram
Cabling
6 TEST RUN
How to execute a test run
In case of wired remote controller
Before test run
7 TROUBLESHOOTING
Confirmation of error history
Confirmation and check
RAV-SP1100UT-E
8 MAINTENANCE
Before maintenance, be sure to turn off the leakage breaker
Cleaning of panel and air filter
Clean the panel and air filter with water
r Accessory parts
r Parts to be procured locally
Accessory parts and Parts to be procured locally
Separate sold parts
1 PRECAUTIONS FOR SAFETY
New Refrigerant Air Conditioner Installation
To Disconnect the Appliance from Main Power Supply
Connect the connecting cable correctly
1 PRECAUTIONS FOR SAFETY
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
2 SELECTION OF INSTALLATION PLACE
Installation space
Selection of installation place
Advice
Installation procedure
3 INSTALLATION OF INDOOR UNIT
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
Dimension
External view
REQUIREMENT
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
Mounting of clamp Accessory
1. Hanging down of indoor unit
Clamp mounting
Removal of air filter
Restriction to installation
1. Installation clearance
Concealed duct type
Ledge ceiling concealed duct type
4 AIR DUCTING WORK
Static pressure characteristics of each model
Fig. 1 RAV-SM561BT Round duct
Fig. 3 RAV-SM801BT Round duct
Fig. 5 RAV-SM1101BT Round duct
Fig. 7 RAV-SM1401BT Round duct
Fig. 6 RAV-SM1101BT Square duct
Fig. 8 RAV-SM1401BT Square duct
Connecting method of the duct
Installation reference Example for RAV-SM801BT model
Round duct
Square duct Reference for square duct
Connecting method of the duct
Points at installation work
1. Supply air side Round duct
Square duct
Mounting of remote controller
Hanging of indoor unit
Mounting of filter and canvas for suction port
For reference
5 DRAIN PIPING WORK
Piping material
Piping and cautions
Thermal-insulating process
Drain-up
Connection of the drain hose
Check of water drain
After electric piping work
6 REFRIGERANT PIPING AND EVACUATING
Refrigerant piping
Permissible piping length and heat
Flaring dia meter size A Unit mm
Air purge
REQUIREMENT
REQUIREMENT
REQUIREMENT
7 ELECTRICAL WORK
How to wire
CAUTIONS
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
Remote controller cabling
Cabling diagram
7 ELECTRICAL WORK
Cabling
8 TEST RUN
How to execute a test run
In case of wired remote controller
Before test run
9 TROUBLESHOOTING
Confirmation of error history
Confirmation and check
RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E
10 APPLICABLE CONTROLS
NOTIFICATION
Exchange of applicable control setup
Basic operation procedure for setup exchange
1 → 2 → 3 → 4 → 5 →
Setup of external static pressure
Exchange by wired remote controller
To incorporate a filter sold separately
1 → 2 → 3 → 4 → 5 →
1 → 2 → 3 → 4 → 5 →
Change of lighting time of filter sign
To secure better effect of heating
11 INSTALLATION/SERVICING TOOLS
12 MAINTENANCE
Cleaning of Return grille
Clean the Return grilles with water
Accessory parts and Parts to be procured locally
r Accessory parts
r Parts to be procured locally
Separate sold parts
1 PRECAUTIONS FOR SAFETY
New Refrigerant Air Conditioner Installation
To Disconnect the Appliance from Main Power Supply
Connect the connecting cable correctly
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
2 SELECTION OF INSTALLATION PLACE
Installation space
Perform a specified installation work to guard against an earth quake
Install the air conditioner at a height 2.5m or more from the floor
In case of wireless type
Before installation
List of installable ceiling height
Height of ceiling
How to use attached installation pattern
Installation pattern
External view
REQUIREMENT
Installation of hanging bolts
Knockout hole of power cable take-in port
Pipe knockout hole
Draw-out direction of pipe/cable
Installation of indoor unit
Installation of remote controller Sold separately
REQUIREMENT
Preparation before holding down main unit
3 DRAIN PIPING WORK
Piping/Heat insulating material
REQUIREMENT
Drain up
Connection of drain hose
Thermal insulating process
REQUIREMENT
Connection of drain pipe
4 REFRIGERANT PIPING AND EVACUATING
Refrigerant Piping
Permissible Piping Length and Heat
Flaring diam. meter size A Unit mm
Air purge
REQUIREMENT
REQUIREMENT
REQUIREMENT
2. Be sure to connect earth wire. Grounding work
Remote controller wiring
How to wire
5 ELECTRICAL WORK
5 ELECTRICAL WORK
Cable connection
REQUIREMENT
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
Remote Controller Cabling
Cabling diagram
Wiring diagram
Cabling
How to execute a test run
In case of wired remote controller
6 TEST RUN
Before test run
7 TROUBLESHOOTING
Confirmation of error history
Confirmation and check
RAV-SM561CT-E, RAV-SM801CT-E, RAV-SM1101CT-E, RAV-SM1401CT-E
8 APPLICABLE CONTROLS
Exchange of applicable control setup
Basic operation procedure for setup exchange
When power will be turned on after finish of automatic addressing
In case of installation to high ceiling
When using wireless remote controller
Exchange by wired remote controller
1 → 2 → 3 → 4 → 5 →
1 → 2 → 3 → 4 → 5 →
1 → 2 → 3 → 4 → 5 →
Change of lighting time of filter sign
To secure better effect of heating
9 INSTALLATION/SERVICING TOOLS
10 MAINTENANCE
Cleaning of Return grille
Clean the Return grilles with water
Cleaning of air filter
3 Soak up dust with a cleaner or clean with wash
1 Open the suction grille
4 Mount the air filter 5 Close the suction grille