Toshiba RAV-SM1101AT-E Installation of Outdoor Unit, For Reference, Standard installation

Models: RAV-SM561AT-E RAV-SM801AT-E RAV-SM1401AT-E RAV-SM1101AT-E

1 139
Download 139 pages 60.62 Kb
Page 8
Image 8

3 SELECTION OF INSTALLATION

<Obstacle also at the upper side>

1000

1000 moreor

or more

 

Obstacles at both front and rear sides

Open the upper side and both right and left sides. The height of obstacle at both front and rear side, should be lower than the height of the outdoor unit.

<Standard installation>

RAV-SM561AT-E, RAV-SM801AT-E

Installation of Outdoor Unit

Before installation, check strength and horizontality of the base so that abnormal sound does not generate.

According to the following base diagram, fix the base firmly with the anchor bolts.

(Anchor bolt, nut: M10 x 4 pairs)

 

90

600

90

 

 

108

 

330

306

60

 

 

 

Ø28 Drain hole

 

1. Single unit installation

Set the out margin of the anchor bolt to 15 mm or less.

15 or less

1000150 or more or more

2. Serial installation of two or more units

 

 

200 or more

300

300

1000 moreor

or more

or more

 

Serial installation at front and rear sides

Open the upper side and both right and left sides. The height of obstacle at both front and rear sides should be lower than the height of the outdoor unit.

<Standard installation>

1000

300

1500

2000

200

or more

or more

or more

or more

or more

In case of draining through the drain hose, attach the following drain nipple and the waterproof rubber cap, and use the drain hose (Inner diam.: 16 mm) sold on the market. And also seal the screws securely with silicone material, etc. so that water does not drop down. Some conditions may cause dewing or dripping of water.

Drain nipple

Waterproof rubber cap

Waterproof rubber cap

Base plate

Drain nipple

For Reference

If a heating operation would be continuously per- formed for a long time under the condition that the outdoor temperature is 0°C or lower, draining of defrosted water may be difficult due to freezing of the bottom plate, resulting in a trouble of the cabinet or fan.

It is recommended to procure an anti-freeze heater locally for a safety installation of the air conditioner.

For details, contact the dealer.

– 8 –

Page 8
Image 8
Toshiba RAV-SM1101AT-E Installation of Outdoor Unit, For Reference, Obstacle also at the upper side, Standard installation