3 INSTALLATION OF INDOOR UNIT

1. Hanging down of indoor unit

Refer to installation figures of hanging material and hanging bolt.

Adjustment of hanging bolt length and nut position

Adjust hanging bolt length and nut position as shown in the figure before hanging down the indoor unit.

Using the level vial, etc., set the horizontal level of the main unit within 5mm.

Hanging bolt

1)

M10 flat washer

(W3/8 or M10)

(Accessory)

Nut

2)

(W3/8 or M10)

 

M10 flat washer

Nut

(Accessory)

(W3/8 or M10)

 

1)Required those other than M10 flat washer at site.

2)To prevent falling-off of bolt (safety), be sure to set it just under the hanging bracket as shown in the figure.

Considering pipe/wire connecting work inside the ceiling after the indoor unit has been hanged, select an installation place and determine piping direction.

If the ceiling has been already set, prepare refrigerant pipe, drain pipe, connecting wire, switch panel cord, etc. at the place where pipe and wire are connected before hanging the main unit.

Mounting of clamp (Accessory)

In order to avoid falling of the air filter, be sure to mount the attached clamps with stepped screws.

(561BT : 2, 801BT to 1401BT : 4)

• Clamp mounting

• Removal of air filter

Clamp

Stepped screw

Pull out filter downward while holding the frames.