3 SELECTION OF INSTALLATION

CAUTION

When using an air conditioner under low outside temperature condition (Outside temp.:–5°C or lower) with COOL mode, prepare a duct or wind shield so that it is not affected by the wind.

<Example>

Suction hood (Side) Discharge hood

Suction hood (Rear side)

Discharge

 

Fin

 

Fin

Suction

Suction

Before installation

Be careful to the following items before installation.

Length of refrigerant pipe

<SM56>

Length of refrigerant

 

pipe connected to

Item

indoor/outdoor unit

 

 

 

20 m or shorter

Addition of refrigerant is

unnecessary at the local site.

 

 

 

21 m to 30 m

<Addition of refrigerant>

Add 20 g of refrigerant for every

 

1 m of pipe which exceeds 20 m.

 

 

Caution at addition of refrigerant

When the total length of refrigerant pipe exceeds 20 m, add 20 g/m of refrigerant and the maximum total length of pipe is 30 m.

(Max. amount of additional refrigerant is 200 g.)

Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor.

Air purge

For air purge, use a vacuum pump.

Do not use refrigerant charged in the outdoor unit for air purge. (The refrigerant for air purge is not contained in the outdoor unit.)

Electrical cabling

Be sure to fix the power cables and indoor/outdoor connecting cables with clamps so that they do not contact with the cabinet, etc.

<SM80>

Length of refrigerant

 

pipe connected to

Item

indoor/outdoor unit

 

 

 

20 m or shorter

Addition of refrigerant is

unnecessary at the local site.

 

 

 

21 m to 30 m

<Addition of refrigerant>

Add 40 g of refrigerant for every

 

1 m of pipe which exceeds 20 m.

 

 

Caution at addition of refrigerant

When the total length of refrigerant pipe exceeds 20 m, add 40 g/m of refrigerant and the maximum total length of pipe is 30 m.

(Max. amount of additional refrigerant is 400 g.)

Charge the refrigerant accurately. Overcharge may cause a serious trouble of compressor.