5 ELECTRICAL WORK

Cable connection

REQUIREMENT

Be sure to connect the cables matching the terminal numbers. Incorrect connection causes a trouble.

Be sure to pass the cables through the bushing of cabling connection port of the indoor unit.

Keep a margin (Approx. 100mm) on a cable to hang down the electric parts box at servicing, etc.

The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)

Loosen the cover mounting screws (2 positions) of the electric parts box, and then remove the cover.

Slit the film of bushing attached to the power take-in port and remote controller cable take-in port, and then pass through cables.

Connect the indoor/outdoor connecting cables and the remote controller cable to the terminal block of the electric parts box.

Tighten screws of the terminal block securely, and fix the cables with code clamp attached to the electric parts box. (Do not apply tension to the connecting section of the terminal block.)

Mount the cover of the electric parts box so that it does not pinch the cables.

Electric parts box

Two screws

Terminal block

 

P.C. board

– 130 –