RAV-SM561BT-E, RAV-SM801BT-E, RAV-SM1101BT-E, RAV-SM1401BT-E

Change of lighting time of filter sign

According to the installation condition, the lighting time of the filter sign (Notification of filter cleaning) can be changed.

Follow to the basic operation procedure

(1 2 3 4 5 6 ).

For the item code in Procedure 3, specify [01].

For the set data in Procedure 4, select the setup data of lighting time of filter sign to be changed from the table below.

Set data

Filter sign lighting time

 

 

0000

None

 

 

 

0001

150H

 

 

 

 

0002

2500H

(At shipment)

 

 

 

0003

5000H

 

 

 

 

0004

10000H

 

 

 

 

To secure better effect of heating

When it is difficult to obtain satisfactory heating due to installation place of the indoor unit or structure of the room, the detection temperature of heating can be raised. Also use a circulator, etc. to circulate heat air near the ceiling.

Follow to the basic operation procedure

(1 2 3 4 5 6 ).

For the item code in Procedure 3, specify [06].

For the set data in Procedure 4, select the setup data of shift value of detection temperature to be set up from the table below.

Set data

Shift value of detection temp.

 

 

0000

No shift

 

 

0001

+1°C

 

 

0002

+2°C (At shipment)

 

 

0003

+3°C

 

 

0004

+4°C

 

 

0005

+5°C

 

 

0006

+6°C

 

 

Check and test operation

Be sure to test the pipe connections for gas leak.

Check the flare nut connections, valve stem cap connections and service port cap connections for gas leak with a leak detector or some soap water.