3 DRAIN PIPING WORK

Connection of drain hose

Thermal insulating process

Insert the attached drain hose into the drain pipe connecting port on the drain pan up to the end.

Fit the attached hose band to the end of the pipe connecting port, and then tighten it securely.

REQUIREMENT

Be sure to fix the drain hose with the attached

 

hose band, and set the tightening position

 

upward.

As the draining is the natural water draining,

 

arrange the pipe outside of the unit on the down

Using the attached drain hose thermal insulator, lap the connecting section and the drain hose without clearance, and then tighten with two handing band so that thermal insulator does not open.

Covering the attached drain hose thermal insulator, lap the thermal insulator (procured locally) to the drain pipe without clearance.

Lap covering connecting section

between drain pan and drain hose. Thermal insulator (procured locally)

slope.

• If piping is performed as shown in the figure,

drain cannot be discharged.

Refrigerant pipe

Drain pipe

Drain pipe

Drain hose

Drain

pan

Hose band Banding band Hose band

Attached thermal insulator

*Tighten the banding band so that attached thermal insulator is not pushed excessively.

Lap the attached thermal insulation so that the one end is put on the other end at the upper side.

Fit the attached hose band to the end of the hose, lay down the knob, and then tighten hose band.

Drain pan

Attached drain hose

Confirm that soft hose is pushed in up to the end of the drain pan.

Connection of drain pipe

Connect the hard vinyl chloride pipe (procured locally) to the mounted drain hose which was attached.

In case of taking pipe from the left side

In case of taking pipe from the left side, exchange the plug from left to right. Push in the plug of which end is not sharp up to the end.

Drain pan

Pulg

– 126 –