6 ELECTRICAL WORK

For the air conditioner that has no power cable, connect a power cable as mentioned below.

Model

RAV-SM56, RAV-SM80

 

 

 

Power supply

220 – 240 V

 

Single phase 50 Hz

 

 

 

 

 

 

Maximum running current

15 A

 

 

 

 

Installation fuse rating

25 A (D type

)

 

 

Power cable

H07 RN-F or 245 IEC 66

(2.5 mm2 or more)

 

 

 

 

CAUTION

Wrong wiring may cause a burnout to some electrical parts.

Be sure to use the cord clamps attached to the product.

Do not damage or scratch the conductive core and inner insulator of power and inter-connect- ing cables when peeling them.

Be sure to comply with local regulations of the cable from outdoor unit to indoor unit.

(wire size and cabling method etc.)

Use the power and Inter-connecting cables with specified thickness, specified type and protec- tive devices required.

How to remove the valve cover

1.Remove screws of the valve cover.

2.Pull the valve cover downward to remove it.

Valve cover

Piping cover

Indoor/outdoor connecting cables

Power cable

How to wire

1.Connect the connecting cable to the terminal as identified with their respective numbers on the terminal block of indoor and outdoor unit.

H07 RN-F or 245 IEC 66 (1.0 mm2 or more)

2.When connecting the connecting cable to the outdoor unit terminal, prevent water coming in the outdoor unit.

3.Insulate the unsheathed cords (conductors) with electrical insulation tape. Process them so that they do not touch any electrical or metal parts.

4.For inter connecting cable, do not use a wire jointed to another on the way.

Use wires long enough to cover the entire length.

Terminal block

1 2 3 L N

Screw

Connecting Power cable cable

Tripping length power cord and connecting cable

L N

10

10

1 2 3

10

 

 

10

40

40

30

30

Earth line

Earth line

(mm)

 

 

Power cable

Connecting

 

 

cable

 

CAUTION

The installation fuse (25A D type ) must be used for the power supply line of this air conditioner.

Incorrect/incomplete wiring might cause an electrical fire or smoke.

Prepare the exclusive power supply for the air conditioner.

This product can be connected to the mains. Connection to the fixed wiring :

A switch which disconnects all poles and has a contact separation of at least 3 mm must be incorporated in the fixed wiring.

– 13 –