Desa V36EN-A, VV36ENB, V36EP-A, VV36EPB installation manual Checking GAS Connections

Page 20

20

FIREPLACE INSTALLATION

Checking Gas Connections

FIREPLACE INSTALLATION

Continued

CHECKING GAS CONNECTIONS

WARNING: Test all gas piping and connections, internal and external to unit, for leaks after installing or servicing. Correct all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG (3.5 kPa)

1.Disconnect fireplace and its individual equipment shutoff valve from gas supply piping system. Pressures in excess of 1/2 psig (3.5 kPa) will damage fireplace gas regulator.

2.Cap off open end of gas pipe where equipment shutoff valve was connected.

3.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air.

4.Check all joints of gas supply piping system. Apply noncorro- sive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5.Reconnect fireplace and equipment shutoff valve to gas sup- ply. Check reconnected fittings for leaks.

Test Pressures Equal To or Less Than 1/2 PSIG (3.5 kPa)

1.Close equipment shutoff valve (see Figure 33).

2.Pressurize supply piping system by either opening propane/LP supply tank valve for propane/LP gas fireplace or opening main gas valve located on or near gas meter for natural gas fire- place, or using compressed air.

3.Check all joints from propane/LP supply tank or gas meter to equipment shutoff valve (see Figure 34 for propane/LP or Figure 35 for natural gas). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Fireplace Gas Connections

1.Open equipment shutoff valve (see Figure 33).

2.Open propane/LP supply tank valve for propane/LP fireplace or main gas valve located on or near gas meter for natural gas fireplace.

3.Make sure control knob of fireplace is in the OFF position.

4.Check all joints from equipment shutoff valve to gas valve (see Figure 34 for propane/LP or Figure 35 for natural gas). Apply noncorrosive leak detection fluid to all joints. Bubbles forming show a leak. Correct all leaks at once.

5.Light fireplace (see Operating Fireplace, page 25). Check all other internal joints for leaks.

6.Turn off fireplace (see To Turn Off Gas to Appliance, page 25).

Equipment

Open

Shutoff

 

Valve

 

 

Closed

Figure 33 - Equipment Shutoff Valve

 

Equipment

Propane/LP

Shutoff

Valve

Supply Tank

 

 

Gas Valve

Figure 34 - Checking Gas Joints for Propane/LP Gas Fireplace

Equipment

Shutoff

Valve

Gas

Meter

Gas Valve

Figure 35 - Checking Gas Joints for Natural Gas Fireplace

For..com

111253-01D

Image 20
Contents For Your Safety What to do if YOU Smell GAS OWNER’S Operation Installation ManualFor Your Safety Table of Contents Safety InformationProduct Identification Local CodesLocation and Space Requirements Product FeaturesPRE-INSTALLATION Preparation Clearances Framing and FinishingLocation of Termination CAP Balcony with Perpendicular Side WallVenting Installation Instructions Installation PrecautionsInstallation Planning Horizontal Termination InstallationInstalling Siding Standoff Combustible Exterior Horizontal Termination Configurations Ground Floor InstallationCorner Installation Venting with Two 90 Elbows Installation for Vertical Termination Flat Ceiling InstallationVertical Termination Configurations Desa 5/8 Pipe & Vent Kits High Altitude InstallationParts Lists for Venting Kits and Components Fireplace Installation Installing Optional Blower AccessoryModel BK Installation Check GAS TypeModel BKT Installation Attaching Speed Control to FireboxInstallation Items Needed Installing GAS Piping to Fireplace LocationBlower Wiring Diagram Connecting Fireplace to GAS Supply Gas ConnectionChecking GAS Connections Pressure Testing Gas Supply Piping SystemPressure Testing Fireplace Gas Connections Cleaning Glass Door REMOVING/REPLACING Glass DoorRemoving Louver Panels Removing Glass DoorInstalling LOGS, Lava Rock and Glowing Embers Installing Rear Brick PanelInstalling Log No Installing Log No Optional Remote Control Wiring DiagramWall Switch Installation For Your Safety Read Before Lighting Operating FireplaceLighting Instructions To Turn OFF GAS To ApplianceOperating Optional Blower Accessory Pilot AssemblyInspecting Burners Burner Flame PatternCleaning Maintenance Glass DoorPilot and Burners LogsTroubleshooting Observed Problem Possible Cause RemedyGas leak. See Warning statement at Illustrated Parts Breakdown ModelsParts List VV36EPSB1 VV36EPHB1 Description QTYBurner Assembly for Models KEY Part Number Description QTY Replacement Parts Service Hints Technical ServiceSpecifications Parts Under WarrantyOwners Registration Form Postage Required Accessories Warranty Information