Empire Comfort Systems VFP36FP, VFP32FP Checking Manifold Pressure, Mantel Clearances Figure

Page 10

GAS SUPPLY (continued)

Checking Manifold Pressure

VFP(32,36)FP(30,31)LN (Natural gas) will have a manifold pressure of approximately 3.5" w.c. (.871kPa) for maximum input or 1.7" w.c. (.423kPa) for minimum input at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 4.5" w.c. (1.120kPa) for the purpose of input adjustment to a maximum of 10.5" w.c. (2.614kPa). VFP(32,36)FP(20,21)LN (Natural gas) will have a manifold pressure of approximately 6.0" w.c. (1.49kPa) at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 7.0" w.c. (1.74kPa) for the purpose of input adjustment to a maximum of 10.5" w.c. (2.615kPa). VFP(32,36)FP(30,31)LP (Propane gas) will have a manifold pressure approximately 10.0"w.c. (2.49kPa) for maximum input or 4.9"w.c. (1.220kPa) for minimum input at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0"w.c. (3.237kPa).

VFP(32,36)FP(20,21)LP (Propane gas) will have a manifold pressure approximately 10.0"w.c. (2.49kPa) at the pressure regulator outlet with the inlet pressure to the pressure regulator from a minimum of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a maximum of 13.0"w.c. (3.237kPa).

A test gage connection is located downstream of the gas appliance pressure regulator for measuring gas pressure. The connection is a 1/8 inch (3mm) N.P.T. plugged tapping.

VFP(32,36)FP(30,31) Millivolt Control

The valve regulator controls the burner pressure which should be checked at the pressure test point. Turn captured screw counter clockwise 2 or 3 turns and then place tubing to pressure gauge over test point (Use test point “A” closest to control knob). After taking pressure reading, be sure and turn captured screw clockwise firmly to re-seal. Do not over torque. Check for gas leaks.

CLEARANCES

Minimum Wall and Ceiling Clearances (Figure 4)

Sidewall Clearances: The clearance from the inside of the fireplace to any combustible wall should not be less than 2".

Fireplace Side and Back Clearances: The fireplace outer casing sides and back have zero clearance to combustibles.

Ceiling Clearances: The ceiling height should not be less than 36" from the top of the hood.

Mantel Clearances: Vent free fireplace models must use the hood supplied with the fireplace. If a combustible mantel is installed, it must meet the clearance requirements detailed above.

36”

2”

Mantel Clearances (Figure 5)

12” 10”

MANTEL

COMBUSTIBLES

ALLOWED 8”

6”

18”4”

15 1/4”

12 ½”

2”

 

9 3/4”

7”

4 1/4”

HOOD

Figure 5

Figure 4

Page 10

20101-0-0306

Image 10
Contents Installation Instructions Table of Contents Important Safety Information Safety Information for Users of LP-GAS LP-GAS Warning OdorIntroduction Model SpecificationsMinimum Firebox Opening Unusually Tight Construction Unusually tight construction is defined as construction whereVentilation Air Ventilation Air From Inside Building Figure Ventilation Air From Inside BuildingOutdoors Ventilation Air From Outdoors FigureInstalling a New Main Gas Cock GAS SupplyVFP32,36FP30,31 Millivolt Control ClearancesChecking Manifold Pressure Minimum Wall and Ceiling Clearances FigureCombustible Materials Fireplace Dimensions Planning Installation Installing Hood and Trim KITFinishing Fireplace Framing and Installation Placement of Glowing Embers and Lava Rock Placing Lava Rock in Front of Burner on Fireplace FloorOperation INSTRUCTIONS/FLAME Appearance For Your Safety Read Before Lighting VFP32,36FP30,31 Lighting InstructionsFor Your Safety Read Before Lighting VFP32,36FP20,21 Lighting InstructionsPilot Flame Characteristics Check 750 Millivolt System Operation WiringMaintenance Remote ReceiverAppliance produces unwanted odors Gas odor even when control knob is in OFF positionHeater produces a whistling noise when main burner is lit Appliance shuts off during use. Pilot stays onParts List Wire AssemblyHOW to Order Repair Parts Parts ViewOptional Variable Speed Blower Installation Instructions FBB4 Blower InstallationBlower Motor WiringBlower Wheels Junction BOX Wiring Installation Instructions Optional Brick Liner Installation InstructionsService Notes

VFP32FP, VFP36FP, P)-1, 31)L(N, 21)L(N specifications

Empire Comfort Systems is a well-recognized name in the heating and appliance industry, known for its quality products and innovative technologies. Among their impressive offerings are the VFP32FP, VFP36FP, and VFP21)L(N,31)L(N,P)-1 series gas fireplaces, designed to provide warmth, ambiance, and efficiency for modern homes.

The VFP32FP is a versatile unit that seamlessly blends into various room designs. With a 32-inch viewing area, it showcases a beautiful flame while offering an impressive heat output. This model features a heat exchanger that ensures maximum warmth reaches the living space without excessive energy use. The VFP32FP also comes equipped with a millivolt system that allows for easy operation, even during power outages.

The VFP36FP is ideal for those seeking a larger fireplace experience. With a 36-inch viewing area, it not only enhances the aesthetic of any space but also produces substantial heat to combat chilly nights. What sets the VFP36FP apart is its high-efficiency design, ensuring lower emissions and reduced gas consumption. The unit's adjustable flame and thermostat controls allow homeowners to customize their heating needs easily.

Empire's VFP21)L(N,31)L(N,P)-1 offers a compact yet powerful heating solution. This fireplace is perfect for smaller spaces without sacrificing performance. It comes with a robust design and various decorative options to match any interior style. The advanced technology utilized in this model ensures efficient heat distribution, making it a practical choice for cozy living areas.

All models boast a range of features that enhance usability and comfort. They come with convenient remote control options, allowing for easy operation from anywhere in the room. The emphasis on safety is evident through the inclusion of glass safety screens and built-in safety shut-off systems.

Empire Comfort Systems has committed to sustainability, and these fireplaces exemplify that dedication. Each model is engineered to provide eco-friendly heating solutions, contributing to reduced carbon footprints while delivering exceptional performance.

In summary, the Empire Comfort Systems VFP series, including the VFP32FP, VFP36FP, and VFP21)L(N,31)L(N,P)-1, represents the perfect blend of innovation, efficiency, and beauty. With robust features and cutting-edge technology, these gas fireplaces fulfill the heating needs of contemporary homes while enhancing their visual appeal. Homeowners can enjoy warmth, style, and peace of mind knowing they have chosen a reliable and efficient product from Empire Comfort Systems.