Stove Installation (for qualified installers only) | 9 |
Stove Placement Requirements
Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or other means approved by local building or fire officials.
•Stove must be placed so that no combustibles are within, or can swing within (e.g. drapes, doors), 36" of the front of the stove
•If the stove is placed in a location where the ceiling height is less than 7', it must follow the requirements in the section "Alcove Installation Requirements"
•Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):
Clearances
Corner Installations
Straight Installations
d
e | f |
a
b
c
NOTE:
Measure clearances to the stove top.
Minimum | Clearance | Singlewall | Reduced | |
(See | the | illustration below) | Connector | Clearance* |
A | Sidewall to stove | 18" | 13" | |
B | Backwall to stove | 16 1/2" | 9" | |
C | Cornerwall to stove | 10" | 7 1/2" | |
D | Connector to sidewall | 27" | 21 1/2" | |
E | Connector to backwall | 19 1/2" | 11 1/2" | |
F | Connector to cornerwall | 19 1/2" | 16 1/2" |
*Reduced clearance installations require one of | the chimneys and connectors listed below: |
• DURAVENT model DVL with DURATEC chimney | • GSW Double Wall Chimney Connector with Super Chimney |
• DURAVENT model DVL with | • SELKIRK METALBESTOS model DS connector with model SSII chimney |
• | • I.C.C. Excel |
• SECURITY model DL with SECURITY model ASHT or S2100 chimney | • Standard Masonry Chimney with any one of the above listed connectors |
• |
|
NOTE: Standard residential installations with reduced clearance connector may use the clearance determined by the manufacturer of the connector for the connector to wall clearance or the clearance listed in this manual. Offsets must be used to maintain the stove to wall clearance.
NOTE: Reduced clearance connectors may not connect to the flue collar – order an appliance adapter for the connector being used.
Travis Industries | 93508131 | 4 020327 |