Finalizing the Installation

Steps for Finalizing the Installation

1.Remove the glass (see page 20).

NOTE: If using propane (LP) convert the appliance prior to installing the logs.

2.We recommend you purge the gas line at this time (with the glass removed). This allows gas to be detected once it enters the firebox, ensuring gas does not build up.

3.Turn on gas to the heater. Leak test all gas joints prior to starting the appliance. Start the pilot. Start the main burner. Leak test all gas joints again.

4.Check the pilot flame following the directions below.

Pilot Flame Inspection

The pilot flame should look like the illustration below. Adjust the pilot flame if necessary.

To adjust the pilot flame, turn this screw. Clockwise

The pilot flame must contact the thermocouple and

 

lowers the flame while counter-clockwise raises it.

thermopile (see the illustration below). Adjust the pilot up or

 

Standard

down as necessary.

Screwdriver

 

5.Install the logs (see page 22).

6.Replace the glass.

7.Check the air shutter following the directions below.

Air Shutter Adjustment

Let the heater burn for fifteen minutes (make sure the logs and glass are in place. The flames should look like the illustration below. Adjust the air shutter, if necessary, to achieve the correct looking flame.

There are two air shutters on this fireplace - adjust both air shutters to obtain the correct flame.

Move the controls left or right until the flame

Front Air Shutter

Rear Air

looks correct. The rear air shutter affects the rear portion of the burner, the front air shutter the front portion of the burner.

Pushing to the right gives the flame more air, making it more blue. Pushing to the left gives the flame less air, making it more orange.

NOTE: If the air control is all the way open, yet the flames remain sooty, shut off gas to the fireplace and contact a qualified gas service technician.

Control

Shutter Control

NOTE: The logs must be installed correctly to monitor the flame while adjusting the air shutter.

Correct

Not Enough Air

Too Much Air

Flames should be blue at the base, yellow-orange on the top.

If the flames are over 14" tall or sooty on the ends, open the air shutter.

If the flames are all blue and short, close the air shutter.

© Travis Industries

4060111

100-01174

Image 24
Contents DVL Insert EF Travis Industries, Inc2Introduction Introduction Important InformationSave Your Bill of Sale 4060111Table of Contents Safety Precautions If YOU Smell GASDo not place anything inside Features Installation Options Heating SpecificationsDimensions Natural Gas PropaneInstallation for qualified installers only Top Convection Deflector Fireplace RequirementsHearth Requirements Leveling BoltsFactory-Built Metal Wood-Burning Fireplace Requirements Clearances Mantel ClearancesFace Sizing Face Height WidthGas Line Requirements Gas Line LocationGas Inlet Pressure Vent Requirements Altitude ConsiderationsVent Installation Vent RestrictorVent Configurations Inlet & Exhaust Re-Line Vent LocationVent Connector Removal and Installation Vent Connector Removal Installation Without Surround Panels Surround Panel InstallationInstallation of the On/Off Switch and Rheostat Electrical ConnectionFinalizing the Installation Glass Frame Removal and InstallationFinalizing the Installation Log Set Installation Install the logsInstall the twigs, ember chunk, kibbles, and rock wool Installing the Rock WoolSteps for Finalizing the Installation Air Shutter AdjustmentPilot Flame Inspection Fine Tuning the EMBER-FYRE Burner 26Operation Before You BeginLocation of Controls Operation Starting The Pilot FlameAdjusting the Flame Height 28OperationStarting the Heater for the First Time Turning the Heater On and OffAdjusting the Blower Speed Operation29Normal Operating Sounds Normal Operating Odors30Maintenance Yearly Service ProcedureMaintaining Your Heaters Appearance Maintenance Troubleshooting Table32Maintenance How this Heater WorksWhat Turns the Main Burners On and Off What Prevents Gas BuildupMaintenance33 Wiring DiagramReplacement Parts List Safety Label Safety LabelLimited 7 Year Warranty Years 1 & 2 Coverage Parts & LaborYears 3 Through 5 Coverage Parts & Labor Years 6 & 7 Coverage Parts onlyBurner Replacement LP Conversion InstructionsOptional Equipment for qualified installers only Follow the directions below to replace the orificesTo adjust the pilot flame, turn this screw Note if totally Firebacks Optional Equipment for qualified installers only Important Installation Note for Models Using the Firebacks Accent LightAccent Light Operation Lower Surround Panel Index

DVL Insert EF II specifications

The Lopi DVL Insert EF II is a remarkable heating solution that combines advanced technology with elegant design. As a part of Lopi’s prestigious line of gas inserts, the DVL Insert EF II is specifically engineered to provide efficient and reliable heating for homeowners. With an array of features, it stands out as an optimal choice for those looking to enhance their living space while maintaining energy efficiency.

One of the main features of the DVL Insert EF II is its exceptional heating efficiency. This insert is designed to provide a high heat output while minimizing energy consumption. With an impressive thermal efficiency rating, it significantly reduces heating costs and ensures that your home remains warm and inviting during the colder months. The insert is capable of heating areas up to 1,800 square feet, making it ideal for both large and small rooms.

The DVL Insert EF II boasts an advanced direct vent technology, which allows for efficient combustion while maintaining indoor air quality. This technology facilitates the intake of external air for combustion, ensuring that exhaust gases are safely vented outside, hence creating a clean and safe environment indoors. Additionally, this direct vent system enables flexible installation options, making it adaptable to various home layouts.

Another significant characteristic of the DVL Insert EF II is its impressive design. The insert features a contemporary aesthetic with clean lines and large viewing glass, allowing for an unobstructed view of the flame. The realistic flame effects and ember bed create a warm ambiance, making it a focal point in any room. Homeowners can also choose from various finishes and decorative options, ensuring that the insert complements their home decor.

Equipped with user-friendly controls, the DVL Insert EF II allows for easy adjustment of flame height and heat output. The intuitive remote control provides added convenience, enabling users to manage their comfort with just the touch of a button. Additionally, the insert is designed for easy maintenance, featuring removable components that simplify cleaning and upkeep.

In summary, the Lopi DVL Insert EF II exemplifies efficiency, elegance, and innovation. With its high thermal efficiency, direct vent technology, and stylish design, this gas insert is an excellent investment for any home. It not only provides warmth and comfort but also enhances the aesthetic appeal of your living space while promoting energy efficiency. Experience the warmth of the Lopi DVL Insert EF II and transform your home into a cozy retreat.