Regency L676E-NG, L676E-LP installation manual Unit Installation with Horizontal Termination

Page 23

INSTALLATION

UNIT INSTALLATION WITH HORIZONTAL TERMINATION

(Rigid Vent Systems)

Note: A top clearance of 3"(76mm) and side & bottom clearance of 2"(51mm) must be maintained; except when passing through a wall, ceiling, or at the termination where the use of a firestop or wall thimble reduces the required clearance to 1-1/2" (38mm). Werecommendframinga11"(279mm) x 11"(279mm) (inside dimensions) hole to give structural rigidity for mounting the termination.

Install the vent system according to the manufacturer's instructions included with the components.

1)Set the unit in its desired location. Check to determine if wall studs or roof rafters are in the way when the venting system is attached. If this is the case, you may want to adjust the location of the unit. Rough in the gas preferably on the right side of the unit and the electrical (junction block is on the left side) on the left.

2)Direct Vent pipe and fittings are designed with special twist-lock connections to connect the venting system to the appliance fl ue outlet. A twist-lock appliance adaptor is required.

3)In conjunction with the Simpson Dura-Vent Direct Vent GS system. Install the adaptor after the unit is set in its desired location. Put a bead of high temperature silicone inside the outer section of the adapter and a bead of Mill Pack on the inner collar. Slip the adapter over the existing inner and outer fl ue collar. Fasten to the outer collar only with the 3 supplied screws (drilling pilot holes will make this easier).

4)Level the fireplace and fasten it to the framing using nails or screws through the top and side nailing strips.

5)Assemble the desired combination of pipe and elbows to the appliance adaptor and twist-lock for a solid connection.

Note: For best results and optimum perfor- mance with each approved venting system, it is highly recommended to apply “Mill-Pac” sealant (supplied) to every inner pipe connec- tion. Failure to do so may result in drafting or performance issues not covered under warranty. Silicone (red RTV) is optional.

Horizontal runs of vent must be supported every 3 feet (0.9meter). Wall straps are available for this purpose.

6)Mark the wall for a 11" x 11" (279mm x 279mm) square hole. The center of the square hole should line up with the center- line of the horizontal pipe. Cut and frame the 11 inch (279mm) square hole in the exterior wall where the vent will be terminated. See diagram 2 for center line requirements.

If the wall being penetrated is constructed of non-combustible material, i.e. masonry block or concrete, an 8" (203mm) diameter hole is acceptable.

Diagram 2

Note:

a)The horizontal run of vent must be level, or have a 1/4 inch rise for every 1 foot of run towards the termination. Never allow the vent to run downward. This could cause high temperatures and may present the possibility of a fi re.

b)The location of the horizontal vent termination on an exterior wall must meet all local and national building codes, and must not be blocked or obstructed. See "Exterior Vent Termination Locations" section for more details.

7)Ensure that the pipe clearances to combustible materials are maintained (Diagram 5). Install the termination cap.

Note: If installing termination on a vinyl siding covered wall, a vinyl siding standofforfurring stripsmustbeused to ensure that the termination is not recessed into the siding.

Diagram 5

The four wood screws provided should be re- placed with appropriate fasteners for stucco, brick, concrete, or other types of sidings.

8)Before connecting the horizontal run of vent pipe to the vent termination, slide the Wall Thimble over the vent pipe. The wall thimble is required for all horizontal terminations.

9)Slide the appliance and vent assembly towards the wall carefully inserting the vent pipe into the vent cap assembly. It is important that the vent pipe extends into the vent cap sufficientdistancesoastoresultinaminimum pipe overlap of 1-1/4 inches (32mm). Secure the connection between the vent pipe and the vent cap.

10)Install wall thimble in the center of the 11" (279mm)squareandattachwithwoodscrews (Diagram 7).

Diagram 7

INSTALLATION

NOTE: A Vent Guard is required when the AstroCap is installed above grade at 7 feet or lower.

Diagram 1

Regency® L676E Direct Vent Gas Fireplace

23

Image 23
Contents Libertytm L676E Gas Fireplace Information for MOBILE/MANUFACTURED Homes After First Sale Manufactured Mobile Home RequirementsTable of Contents Copy of Safety Decal Safety LabelMA Code CO Detector RequirementsUnit Dimensions Important Message Save These Instructions InstallationGeneral Safety Information Installation ChecklistHeat Release KIT Manufactured Mobile Home Additional RequirementsLocating Your GAS Fireplace Heatwave Duct KITClearances Mantel LEG Clearances Mantel ClearancesImportant Header must be metal stud Framing & FinishingPrior to Installation Unit AssemblyFactory set for LP units Venting IntroductionVent Restrictor Position Factory set for NG units= Clearance to permanently closed window *min /30cm Exterior Vent Termination RequirementsHorizontal Termination Flex Venting ArrangementsBasic Horizontal & Vertical Terminations Rigid Pipe Venting Systems58DVA-16AB 8 Rigid Pipe Cross Reference ChartL676 & L900 Direct Vent Fireplace Allowable Horizontal Terminations Vent Restrictor SettingHorizontal Venting with Two 2 90o Elbows Vertical Venting with Two 2 90o Elbows Rigid Pipe Allowable Vertical TerminationsUnit Installation with Horizontal Termination Minimum Vent Unit Installation With Vertical TerminationThis allows for small adjustments DiagramAstrocap XL Unit InstallationAdjustment Pilot AdjustmentTesting Aeration GAS Line InstallationHeat Shield BACK-UP Battery InstallationBattery Wires Handle with care. do not Force Into Position Brick Panel InstallationExterior Brick Panel Installation 03-25 LOG SET InstallationComplete Log Set Installation Do not cut the ground terminal off under any circumstances Wiring DiagramOperating Instructions Operating InstructionsGAS Control Valve Matching Remote Handset & Control BOX ID CodeBackup Battery Lighting ProcedureShutdown Procedure Operation During Power OutageCopy of Lighting Plate Instructions For Your Safety Read Before LightingMaintenance Backup Battery Latch Location Control BOX ReplacementD E Back-up Battery Power ReceptacleRemove the exterior brick panels Valve Tray ReplacementBottom Brick Panel Wire Harness Connectors Wire Harness DisconnectedBack-up Battery shown HarnessValve Tray Description Parts ListMain Assembly Burner & LOG Assembly Regency L676E Direct Vent Gas Fireplace Regency L676E Direct Vent Gas Fireplace Regency L676E Direct Vent Gas Fireplace Warranty Limited Lifetime WarrantyInstaller Please complete the following information

L676E-LP, L676E-NG specifications

Regency L676E-LP and L676E-NG are two remarkable gas fireplaces designed to elevate any living space with their blend of efficiency, aesthetics, and innovative technology. These models stand out with their versatile design, suitable for both new and existing homes, while offering homeowners an exceptional heating experience.

Both the L676E-LP (liquid propane) and L676E-NG (natural gas) fireplaces showcase a stylish contemporary design that fits seamlessly into modern and traditional decors alike. With a sleek and elegant appearance, these fireplaces serve as a stunning focal point in any room, creating a cozy ambiance while efficiently warming the space.

One of the key features of the L676E series is its high-efficiency rating. These gas fireplaces are engineered to produce substantial heat while minimizing energy consumption. Equipped with advanced energy-efficient technology, they provide a significant reduction in utility costs compared to traditional heating methods. The L676E models also come with an impressive heat output, making them suitable for larger areas, effectively maintaining a comfortable environment during colder months.

The L676E fireplaces are built with a powerful burner system that ensures even heat distribution throughout the room. The innovative technology allows for adjustable flame heights, enabling users to customize the intensity of the fire to suit their mood. The clean-burning design also contributes to an environmentally-friendly experience, producing minimal emissions and reducing the carbon footprint.

Another standout characteristic is the ease of use and convenience offered by both models. Featuring an intuitive remote control system, users can adjust settings effortlessly. The option for thermostat control further enhances comfort, allowing the fireplace to maintain a consistent temperature automatically.

Safety is paramount in the design of the L676E-LP and L676E-NG fireplaces. They are equipped with advanced safety features, including an automatic shutdown system and a protective glass front to prevent accidental burns. Additionally, their durable construction ensures long-lasting performance and reliability.

In summary, the Regency L676E-LP and L676E-NG gas fireplaces merge cutting-edge technology with elegant design. Their high efficiency, impressive heating output, and safety features make them a valuable addition to any home, providing both comfort and style. Whether for new construction or retrofitting an existing space, these models represent an ideal choice for homeowners seeking a blend of functionality and sophistication.