EG, PEG, EGH GAS-FIRED BOILERS SERIES 4 — BOILER MANUAL

 

Check-out procedure

Check-out procedure

Check-off steps as completed.

System properly filled with water?

Automatic air vent, if used,open one turn (water boilers only)?

Air purged from system (water boilers only)?

Steam boilers properly skimmed?

Air purged from gas piping?. Piping checked for leaks?

Are proper orifices installed? Check page 7 for proper size.

Proper orifices must be used. Failure to do so will cause severe personal injury, death or substantial property damage.

Follow operating instruction label on boiler for proper start- up.Also refer to“To Place in Operation,”page 17.

Proper burner flame? Refer to “Check Main Burner Flames” and“Check Pilot Burner Flame,”page 21.

Testlimitcontrol:Whileburnersareoperating,movelimitcontrol indicator below actual boiler water temperature or pressure. Burners should go off. Circulator should continue to operate (water boilers only). Raise indicator above boiler water temperature or pressure and burners should reignite.

Test any additional field-installed controls: If boiler has low water cut-off, additional high limit or other controls, test for operation as outlined by manufacturer. Burners should be operating and should go off when controls are tested. When controls are restored, burners should reignite.

EG only - button on spill switch pushed in?

To test ignition system shut-off device:

a.For boilers with electronic ignition systems: Connect manometer to outlet side of gas valve. Start boiler, allowing for normal start-up cycle to occur and main burners to ignite. With main burners on, manually shut off gas supply at manual main shutoff gas valve. Burners should go off. Open manual main shut-off gas valve. Manometer should confirm there is no gas flow. Pilot will relight, flame sensing element will sense pilot flame and main burners reignite.

b.For standing pilot - Turn gas cock knob to PILOT position and extinguish pilot flame. Pilot gas flow should stop in less than 3 minutes. Put system back into operation (see page 17).

Limitcontrolsettodesigntemperatureorpressurerequirements of system? Maximum limit setting - 240°F (water boilers) - 15# (steam boilers).

For multiple zones, flow adjusted so it is about the same in

 

each zone (water boilers only)?

Thermostat heat anticipator set properly? Refer to “Room Thermostat,”page 15 and correct wiring diagram.

Boiler cycled with the thermostat? Raise to highest setting. Boiler should go through normal start-up cycle. Lower to lowest setting. Boiler should go off.

Measure gas input (natural gas only):

a.Operate boiler 10 minutes.

b.Turn off other appliances.

c.At the natural gas meter, measure time (in seconds) required to use one cubic foot of gas.

d.Calculate gas input:

3600 x 1000

= Btuh

 

number of seconds from step c

e.Btuh calculated should approximate input rating on rating label.

Check manifold gas pressure by connecting a manometer to the downstream test tapping on main gas valve.

MANIFOLD GAS PRESSURE NAT. = 3.5" W.C.

L.P. = 10.0" WC.

Several operating cycles observed for proper operation? If damper is provided, see Control Supplement for check- out procedure.

Room thermostat set to desired temperature?

Installation and Service Certificate on this page completed?

All instructions shipped with this boiler reviewed with owner or maintenance person, returned to envelope and given to owner or displayed near boiler?

Installation and Service Certificate

Boiler Model

Series

 

CP Number

 

 

Date Installed

 

 

 

 

 

 

 

 

 

 

 

BTU Input

 

Installation instructions have been followed.

 

 

 

 

 

 

 

Check-out sequence has been performed.

 

 

 

 

 

 

 

Above information is certified to be correct.

 

 

 

 

 

 

 

Information received and left with owner/maintenance person.

Installer

 

 

 

 

 

 

 

 

 

(Company)

(Address)

(Phone)

(Installer's Signature)

18

Part Number 550-110-639/0703

Image 18
Contents EG, PEG, EGH Contents Combustion air and ventilation openings InstallationCodes Other size ducting must comply with local codesWhen removing boiler from common venting system Chimney or vent requirementsSelect the boiler location Installation of optional indirect water heater Installation clearancesResidential garage installation Boiler foundationInstallation of flue collector hood Installation of front and back base panelsHydrostatic pressure test Front and back base panels Draft hood installation Spill switch installationDamper installation Breeching erectionTo protect Piping connectionsForced hot water boilers and gravity hot water boilers Refer to tables and Figures 11a and 11bBypass piping Use with refrigeration systemsMultiple Zoning Steam boilers Condensate receiver capacitySteam boiler Install boiler controlsWater boiler Low water cut off for water boilersFor correct operation, install as shown in water boilers or Optional heatersConnecting gas supply piping Gas pipingFor propane gas Wiring Install room thermostatWater treatment Final adjustmentsFreeze protection when used Filling water systemsTo place in operation Skimming steam boilersInspect base insulation For propane boilers onlyCheck-out procedure Check-out procedureInstallation and Service Certificate Each zone water boilers only?Service Handling fiberglass and ceramic fiber materials Eye Irrigate immediately Breathing Fresh airNiosh stated First Aid Monthly during heating season Beginning of each heating seasonDaily during heating season End of each heating seasonAnnual shut-down procedure Clean boiler heating surfacesCleaning main burners Check pilot burner flamesReplacement parts EG Replacement parts EG Replacement parts EGH Replacement parts EGH Dimensions EG Dimensions P-EG Dimensions EGH DataRatings DOEFor EG water boilers Standard equipmentEG boilers add For EG steam boilers

EG specifications

The Weil-McLain EG Series is a notable line of cast iron, steam, and hot water boilers designed primarily for commercial and residential heating applications. Known for its robustness and efficiency, the EG boiler series has become a preferred choice for many heating professionals.

One of the main features of the Weil-McLain EG series is its durable cast iron construction. This material not only contributes to the longevity of the boiler but also ensures excellent heat retention and uniform heating. The boiler's heat exchanger is optimized to maximize thermal efficiency, delivering reliable and effective heating performance across various applications.

Another key aspect of the EG series is its heating capacity. Available in a range of sizes and outputs, the EG boiler provides flexibility, making it suitable for different heating needs. Whether it’s a small residential installation or a larger commercial system, the EG series offers models that can be tailored to meet specific load requirements.

Advanced technology is integrated into the Weil-McLain EG series to enhance efficiency and ease of use. One notable feature is its ability to operate with both gas and oil fuel types, enabling users to choose the most economical and accessible option for their needs. Additionally, the EG boilers come equipped with a reliable and intuitive control system that simplifies operation and maintenance tasks, allowing users to monitor performance easily.

The EG series also incorporates safety features, such as pressure relief valves and advanced combustion controls, which ensure safe and efficient operation. This attention to safety is essential in protecting both the system and the inhabitants of the building it serves.

Maintenance of the EG boiler is designed to be straightforward, with serviceability being a prominent focus in its design. The boiler's modular components can be accessed easily, significantly reducing downtime for repairs and maintenance.

In conclusion, the Weil-McLain EG series stands out for its reliable performance, efficiency, versatility, and robust construction. Its combination of advanced technology and user-friendly features makes it a leading choice for those seeking a dependable heating solution. Whether for residential or commercial applications, the EG series is engineered to deliver consistent heating while maximizing comfort and minimizing operating costs.