Weil-McLain EG manual Check pilot burner flames, Check main burner flames, Inspect venting system

Page 21

9

EG, PEG, EGH GAS-FIRED BOILERS SERIES 4 — BOILER MANUAL

 

Service(continued)

Check pilot burner flames

1.Proper pilot flame

a)Blue flame.

b)Inner cone engulfing pilot flame sensor.

c)Pilot flame sensor glows cherry red.

functioning properly. If flame blows out or flickers drastically, vent system must be checked for obstructions or other causes of improper venting.

2.Inspect all parts of venting systems for deterioration from corrosion, physical damage, sagging, etc. Correct all conditions found.

3.Verify damper is open when burner ignites. For additional information,see Control Supplement.

Figure 24 Typical pilot burner flame

2.Improper pilot flame.

a)Overfired - flames large and lifting or blowing past pilot flame sensor.

b)Underfired - flame small; pilot flame sensor not engulfed by inner cone.

c)Lack of primary air - flame tip yellow.

d)Pilot flame sensor not heated properly.

Figure 25 Typical main burner flame

Check main burner flames

1.Proper burner flame - Yellow-orange streaks may appear - caused by dust.

2.Improper flame:

a)Overfired - Flames large.

b)Underfired - Flames small.

c)Lack of primary air - Yellow tipping on flames; sooting will occur.

Inspect venting system

1.Check venting system at least once a month during heating season. With boiler firing, hold candle or match below lower edge of draft hood “skirt”. If flame does not blow out, but burns undisturbed, vent system is

Clean boiler heating surfaces

The boiler contains ceramic fiber and fiberglass materials. Use care when handling these materials per instructions on page 19 of this manual. Failure to comply could result in severe personal injury.

1.Follow shut-down procedure

2.Disconnect breeching and remove damper (if used) and draft hood.

3.Removeupperrearjacketpanel.Turn backjacketinsulationtoexposecollector hood.

4.Remove collector hood. Clean excess boiler cement from collector hood and cast iron sections.

5.Remove burners from base of boiler. Follow “Cleaning main burners” to thoroughly clean burners. Place newspaper in base of boiler to collect soot that will fall.

6.With a wire flue brush, clean between the sections.

7.Remove paper and soot. Vacuum or brush base and surrounding area.

8.Replace collector hood. Seal with boiler cement.

9.Replace draft hood, damper (if used) and breeching.

10.Replace insulation and jacket panel.

11.Replace main burners.

When replacing, burner tubes must be seated in slots in back burner support with openings face up. Gas orifices must inject down center of burner.Failure to properly seat burners will result in severe personal injury, death or substantial property damage.

12. Follow“To Place in Operation”procedure.

NOTE: Excessive sooting indicates improper gas combustion. Call a qualified service agency or your local gas utility to check for proper combustion and make any necessary adjustments.

Cleaning main burners

1. Vacuum or brush burners to remove dust and lint.

When replacing, burner tubes must be seated in slots in the back with openings face up. Gas orifices must inject down center of burner. Failure to properly seat burners will result in severe personal injury, death or substantial property damage.

Annual shut-down procedure

1.Follow correct lighting/operating instructions on boiler.

2.Do not drain system unless exposure to freezing temperatures will occur. If antifreeze is used with system, do not drain.

3.If complete boiler and piping system must be drained to avoid freezing, provide method to drain water from both ends of boiler at or below return tapping level.

Part Number 550-110-639/0703

21

Image 21
Contents EG, PEG, EGH Contents Codes InstallationCombustion air and ventilation openings Other size ducting must comply with local codesWhen removing boiler from common venting system Chimney or vent requirementsSelect the boiler location Residential garage installation Installation clearancesInstallation of optional indirect water heater Boiler foundationInstallation of flue collector hood Installation of front and back base panelsHydrostatic pressure test Front and back base panels Damper installation Spill switch installationDraft hood installation Breeching erectionForced hot water boilers and gravity hot water boilers Piping connectionsTo protect Refer to tables and Figures 11a and 11bBypass piping Use with refrigeration systemsMultiple Zoning Condensate receiver capacity Steam boilersWater boiler Install boiler controlsSteam boiler Low water cut off for water boilersOptional heaters For correct operation, install as shown in water boilers orConnecting gas supply piping Gas pipingFor propane gas Install room thermostat WiringFreeze protection when used Final adjustmentsWater treatment Filling water systemsInspect base insulation Skimming steam boilersTo place in operation For propane boilers onlyInstallation and Service Certificate Check-out procedureCheck-out procedure Each zone water boilers only?Service Handling fiberglass and ceramic fiber materials Eye Irrigate immediately Breathing Fresh airNiosh stated First Aid Daily during heating season Beginning of each heating seasonMonthly during heating season End of each heating seasonCleaning main burners Clean boiler heating surfacesAnnual shut-down procedure Check pilot burner flamesReplacement parts EG Replacement parts EG Replacement parts EGH Replacement parts EGH Data Dimensions EG Dimensions P-EG Dimensions EGHDOE RatingsEG boilers add Standard equipmentFor EG water boilers For EG steam boilers

EG specifications

The Weil-McLain EG Series is a notable line of cast iron, steam, and hot water boilers designed primarily for commercial and residential heating applications. Known for its robustness and efficiency, the EG boiler series has become a preferred choice for many heating professionals.

One of the main features of the Weil-McLain EG series is its durable cast iron construction. This material not only contributes to the longevity of the boiler but also ensures excellent heat retention and uniform heating. The boiler's heat exchanger is optimized to maximize thermal efficiency, delivering reliable and effective heating performance across various applications.

Another key aspect of the EG series is its heating capacity. Available in a range of sizes and outputs, the EG boiler provides flexibility, making it suitable for different heating needs. Whether it’s a small residential installation or a larger commercial system, the EG series offers models that can be tailored to meet specific load requirements.

Advanced technology is integrated into the Weil-McLain EG series to enhance efficiency and ease of use. One notable feature is its ability to operate with both gas and oil fuel types, enabling users to choose the most economical and accessible option for their needs. Additionally, the EG boilers come equipped with a reliable and intuitive control system that simplifies operation and maintenance tasks, allowing users to monitor performance easily.

The EG series also incorporates safety features, such as pressure relief valves and advanced combustion controls, which ensure safe and efficient operation. This attention to safety is essential in protecting both the system and the inhabitants of the building it serves.

Maintenance of the EG boiler is designed to be straightforward, with serviceability being a prominent focus in its design. The boiler's modular components can be accessed easily, significantly reducing downtime for repairs and maintenance.

In conclusion, the Weil-McLain EG series stands out for its reliable performance, efficiency, versatility, and robust construction. Its combination of advanced technology and user-friendly features makes it a leading choice for those seeking a dependable heating solution. Whether for residential or commercial applications, the EG series is engineered to deliver consistent heating while maximizing comfort and minimizing operating costs.