Weil-McLain CGa manual UserísInformationManual, STOP!! Read before proceeding

Page 3

UserísInformationManual

STOP!! — Read before proceeding

Failure to adhere to the guidelines on this page can result in severe personal injury, death or substantial property damage.

Air contamination

To prevent potential of severe personal injury or death, check for products or areas listed in table at right before installing boiler. If any of these contaminants are found:

• remove contaminants permanently.

— OR —

isolate boiler and provide outside combustion air. See national,

provincial or local codes for further information.

— OR —

for CGs boilers only — combustion air may be ducted from out- side to the boiler air intake.

Service and maintenance

To avoid electric shock, disconnect electrical supply before performing maintenance.

To avoid severe burns, allow boiler to cool before performing maintenance.

You must maintain the boiler as outlined in the manual and have the boiler started up and serviced at least annually by a qualified service technician to ensure boiler/system reliability.

Boiler operation

Do not block flow of combustion or ventilation air to boiler. This boiler is equipped with a control which will automatically shut down the boiler should air or vent be blocked. If vent or air blockage is easily accessible and removable, remove it. The boiler should attempt to restart within an hour. If blockage is not obvious or cannot be removed, have the boiler and system checked by a qualified service technician.

Should overheating occur or gas supply fail to shut off, do not turn off or disconnect electrical supply to pump. Instead, shut off the gas supply at a location external to the appliance.

Do not use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control, which has been under water.

Have the building monitored when it is vacant for an extended period. Safety controls can shut down the boiler at any time. The loss of heat can result in significant damage due to freezing.

Boiler water

DO NOT use petroleum-basedcleaning or sealing compounds in boiler system. Water seal deterioration will occur, causing leakage between sections and damage to heating system components. This can result in substantial property damage.

DO NOT use "homemade cures" or "boiler patent medicines". Serious damage to boiler, personnel and/or property may result.

Continual fresh makeup water will reduce boiler life. Mineral buildup in sections reduces heat transfer, overheats cast iron, and causes section failure. Addition of oxygen and other gases can cause internal corrosion. Leaks in boiler or piping must be repaired at once to prevent makeup water.

Do not add cold water to hot boiler. Thermal shock can cause sections to crack.

Products to avoid

Spray cans containing chloro/fluorocar- bons

Permanent wave solutions

Chlorinated waxes/cleaners

Chlorine-based swimming pool chemicals

Calcium chloride used for thawing

Sodium chloride used for water softening

Refrigerant leaks

Paint or varnish removers

Hydrochloric acid/muriatic acid

Cements and glues

Antistatic fabric softeners used in clothes dryers

Chlorine-type bleaches, detergents, and cleaning solvents found in household laundry rooms

Adhesives used to fasten building products and other similar products

Areas likely to have contaminants

Dry cleaning/laundry areas and establish- ments

Swimming pools

Metal fabrication plants

Beauty shops

Refrigeration repair shops

Photo processing plants

Auto body shops

Plastic manufacturing plants

Furniture refinishing areas and establish- ments

New building construction

Remodeling areas

Garages with workshops

Part Number 550-110-592/1099

3

Image 3
Contents CGa, CGi, CGs, EG, EGH, LGB, PEG, PFG Please read this page first CGa,CGi,CGs,EG,EGH,LGB,PEG,PFGBoilersSTOP!! Read before proceeding UserísInformationManualBoiler components CGiLGB Tankless water heater EG and EGH only Maintain boiler using schedule belowUser maintenance procedures Check dailyBoiler area Check monthly Check condensate drain system Clean vent termination & air intake screensAutomatic air vents if used Main burner flame Pilot burner flameFloat type See Figure Service periodicallyService every 6 months Clean gauge glassOperate boiler relief valve Propane gas odorant Follow boiler shutdown procedureLighting instructions End-of-season shutdownLighting Instructions Foryour Safety Read Before LightingCGa, EG-30 to EG-65 PEG-30 to PEG-55CGa-25 to CGa-6, EG-30 to EG-50, PEG-30 to PEG-50 Position Selector Indicator ArmEG-75, EGH-85, EGH-95 PFG-6, PFG-7Operating Instructions Foryour Safety Read Before Operating Operating instructionsCGa, EG-30 to EG-75, PEG-30 to PEG-55, PFG-5 Spark-ignited pilot Gas valve White-Rodgers 36E CGa-7, CGa-8, EG-55 to EG-75, PEG-55, PFG-5 Spark-ignited pilot Gas valve Robertshaw PFG-6 to PFG-8 EGH-85 to EGH-125For Your Safety Read Before Operating CGi, CGsTo Turn OFF GAS to the Appliance To Place in Operation Annual Shutdown ProcedureSymptom Common Causes Possible Corrections Common problems and solutionsWeil-McLain Blaine Street Michigan City,

CGa specifications

The Weil-McLain CGa is a highly efficient and reliable gas-fired boiler that has established itself as a favorite among homeowners and HVAC professionals alike. Known for its impressive performance and durability, the CGa series is designed to deliver comfort while optimizing energy consumption.

One of the main features of the Weil-McLain CGa is its efficiency. With an AFUE (Annual Fuel Utilization Efficiency) rating of up to 84%, this boiler efficiently converts gas into heat, ensuring minimal energy waste. This efficiency not only translates to cost savings on energy bills but also supports environmental sustainability through reduced emissions.

The CGa boilers are designed for versatility, capable of being used in various applications, including residential heating systems and light commercial settings. With a range of models available, the CGa can meet different heating demands, ensuring consistent comfort regardless of the building size or layout.

The boiler's built-in heating capabilities include the option for either hot water or steam heating, adding to its versatility. Weil-McLain offers multiple BTU outputs across the CGa series, allowing for a customized solution based on specific heating requirements.

State-of-the-art technologies are evident in the CGa's design. The integrated hot surface ignition system enhances start-up reliability, minimizing the risk of combustion issues and ensuring safe operation. Additionally, the unit features a standard draft diverter for efficient venting, allowing for optimal exhaust management within the heating system.

Durability is another key characteristic of the Weil-McLain CGa. Constructed from high-quality materials, these boilers are engineered to withstand the rigors of daily operation. The cast iron heat exchanger provides superior heat retention and longevity, ensuring that the system remains operational for years with proper maintenance.

Installation of the CGa boiler is straightforward due to its compact design and versatile venting options, which can accommodate various installation configurations. This ease of installation combined with a user-friendly interface allows homeowners and technicians alike to manage the system with minimal hassle.

In summary, the Weil-McLain CGa boiler epitomizes efficiency, durability, and versatility. Its advanced technologies and robust construction make it a top choice for those seeking a reliable heating solution for their homes or commercial spaces. With Weil-McLain's commitment to quality and innovation, the CGa series delivers performance that meets the diverse needs of today's heating applications.