Patterson-Kelley DVSCM-02 owner manual Minimum Clearance for Boiler Connections

Page 10

 

 

 

 

Thermific® Gas-Fired Boiler

Installation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the air inlet and/or exhaust vent terminal are through the sidewall, clearances from other exhaust/inlet, windows, doors, building openings, snow line, etc must be as shown in the figure above.

There must be either 5' vertical separation or 10' horizontal separation between the flue gas outlet and the combustion air inlet.

The bottom of the flue gas outlet must be located at least 12 inches above finish grade or snow line, but must be at least 7 feet above finish grade when located adjacent to a public walkway. It must also have a minimum clearance of 4 feet horizontally from, and in no case above or below, (unless a 4 foot horizontal distance is maintained,) electric meters, gas meters, regulators and relief equipment.

3.4.2Rooftop Installations 10' min.

Combustion

 

Flue Gas

Air Inlet

4' min.

Outlet

4' min. above snow line

Clearances which must be maintained when both inlet and exhaust are through the roof are shown in the figures above.

3.4.3Minimum Clearance for Boiler Connections

There are special considerations needed when installing the air inlet and exhaust duct systems because of the orientation of these connections on the boilers.

3.4.3.1 Series 700, 1000, 1200

Air Inlet

Round

Damper

90o Elbow

26" Min.*

 

10' min.

 

Vent

Combustion

4' min.

Air Inlet

 

4' min.

 

above

 

snow line

Flue Gas Outlet

*Dimension shown above is based on 12" round ductwork.

A minimum clearance of 26 inches is required on the left side of the boiler to permit the connection of the air inlet duct to the boiler.

Page 8

Image 10
Contents Direct Vent What to do if you smell gas Direct Vent/Sealed Combustion System IntroductionFresh Air System Safety Roof Exhaust Vent Sidewall Air InletInlet Duct InstallationSystem Design Pressure Drop Air Inlet TerminationInlet Duct Assembly at the Boiler Unrestricted Rain capSystem Design Materials, Length, Size, and Construction Inlet Damper and Auxiliary Control Panel optionalFlue Gas Outlet Duct Exhaust Vent Connection at the Boiler Flue Gas TerminationSidewall Installations Equivalent Length of FittingsMinimum Clearance for Boiler Connections Combustion Min Air Inlet Above Snow line Flue Gas OutletOperation Round Vent Damper 90o ElbowMaintenance Combustion Air Requirement, ScfmWiring Diagrams ON-OFFSERIES 700, 1000Logic Diagram 1A ON-OFFIRI Series 700, 1000 1A ON-OFFIRI Series 700, 1000 1B LO-HILO 1B LO-HILO 1C LO-HI-LOIRI 1C LO-HI-LOIRI 1D ON-OFFSERIES 1500, 1700 1D ON-OFFSERIES 1500, 1700 1E ON-OFFIRI Series 1500, 1700 1E ON-OFFIRI Series 1500, 1700 On-Off Auxiliary Control Panel