Nortec RESDELUX manual Figure #9 Blower Pack Cabinet Assembly

Page 7

4.Put the power leads from the blower pack through this opening as you position the blower pack on top of the RESDELUX humidifier

5.Push the blower pack forward until the locating tabs on the bottom of the blower pack with slots in the top of the RESDELUX push forward to engage.

6.Use two Phillips screws with star washers in the Blower Pack screw support tabs to secure to the RESDELUX unit.

7.Remove the front door and service cover from the RESDELUX humidifier.

8.Connect the power leads for the blower pack to terminal P7 on the RESDELUX control board located next to the capacity adjustment potentiometer.

9.Use the short piece of steam hose and hose clamps supplied with the basic hardware kit to connect the steam cylinder to the blower pack steam distributor.

Installation of the blower pack is now complete. For instructions on mounting the RESDELUX humidifier please see the location and mounting section.

Figure #9

Blower Pack Cabinet Assembly

Remote Mounting of the Blower Pack

1.The remote mounted blower pack should be located at least 7’ off the floor to prevent the discharged steam from coming in contact with pedestrian traffic or any obstruction.

2.When installing the remote blower pack, ensure the primary voltage to the RESDELUX has been

switched off at the electrical panel, or that it is unplugged (RESDELUX/C).

3.Find a suitable location for mounting the remote blower pack. The surface should be flat with adequate clearances for the top, side, and front:

Table #1

Clearances of Remote Mounted Blower Pack

Minimum Ceiling

Minimum Side

Minimum frontal

Clearance

Clearance

Clearance

inches (cm)

inches (cm)

inches (cm)

18” (45)

18” (45)

60” (150)

 

 

 

 

 

 

4.Minimum slope of steam hose is 20°. Steam lines longer than 5 ft require condensate trap installation (see Figure #6).

5.RESDELUX blower pack has two teardrop (or keyhole) openings on the back of the cabinet for mounting purposes. They are located 8 ¼” apart, and 1” from the top of the blower pack cabinet.

6.Measure the screw locations and use two #8 screws, 2” long. The screws should be anchored in a standard 2” x 4” wood stud or equivalent to ensure adequate support of the blower pack and connecting steam hose.

7.Remove the 7/8” knockout on the top of the RESDELUX humidifier and insert the closed finger grommet into the opening.

8.Put the power leads from the blower pack through this opening. If the wire leads are not long enough field splice the additional requirement, or get a wire extension kit (P/N 1502326) available from

NORTEC.

Figure #10

Steam Absorption Distances

Steam absorption space size in inches for ambient humidity 30% RH, room temperature and selected steam outputs of RESDELUX humidifier.

H

W

F

0”

Steam Output

F

W

H

4 lbs/hr

36"

12"

12"

6 lbs/hr

42"

16"

18"

8 lbs/hr

48"

18"

18"

- 4 -

Image 7
Contents Installation, Operation Maintenance Troubleshooting Guide Table Of Contents Page Receiving & Unpacking Equipment InstallationPRE-INSTALLATION Checkpoint Humidifier ConfigurationFigure #3 Wall Mounting Detail Blower Pack Connection Steam Hose InstallationFigure #9 Blower Pack Cabinet Assembly Water Supply Line PlumbingDrain Line Page Introduction OperationResdelux Operation Steam Cylinder MaintenanceManual Capacity Adjustment When to Replace the Steam CylinderHOW to Install the Replacement Cylinder HOW to Remove the Steam CylinderExtended Shutdown Mandatory Cleaning of the Drain ValveDiagnostic Procedures Troubleshooting TroubleshootingProcedures and Terms Used Diagnosing Page Page Item Number Part Number Description Spare Parts List and Exploded View Resdelux21a 21b 21c 13a 13d 13e 13b 13c 11b 11a 12 12a 14a Inspect, Check, Clean, and Adjust all items listed Periodic Maintenance ChecklistLimited Warranty MTH/DAY/YR