4.Put the power leads from the blower pack through this opening as you position the blower pack on top of the RESDELUX humidifier
5.Push the blower pack forward until the locating tabs on the bottom of the blower pack with slots in the top of the RESDELUX push forward to engage.
6.Use two Phillips screws with star washers in the Blower Pack screw support tabs to secure to the RESDELUX unit.
7.Remove the front door and service cover from the RESDELUX humidifier.
8.Connect the power leads for the blower pack to terminal P7 on the RESDELUX control board located next to the capacity adjustment potentiometer.
9.Use the short piece of steam hose and hose clamps supplied with the basic hardware kit to connect the steam cylinder to the blower pack steam distributor.
Installation of the blower pack is now complete. For instructions on mounting the RESDELUX humidifier please see the location and mounting section.
Figure #9
Blower Pack Cabinet Assembly
Remote Mounting of the Blower Pack
1.The remote mounted blower pack should be located at least 7’ off the floor to prevent the discharged steam from coming in contact with pedestrian traffic or any obstruction.
2.When installing the remote blower pack, ensure the primary voltage to the RESDELUX has been
switched off at the electrical panel, or that it is unplugged (RESDELUX/C).
3.Find a suitable location for mounting the remote blower pack. The surface should be flat with adequate clearances for the top, side, and front:
Table #1
Clearances of Remote Mounted Blower Pack
Minimum Ceiling | Minimum Side | Minimum frontal |
Clearance | Clearance | Clearance |
inches (cm) | inches (cm) | inches (cm) |
18” (45) | 18” (45) | 60” (150) |
|
|
|
|
|
|
4.Minimum slope of steam hose is 20°. Steam lines longer than 5 ft require condensate trap installation (see Figure #6).
5.RESDELUX blower pack has two teardrop (or keyhole) openings on the back of the cabinet for mounting purposes. They are located 8 ¼” apart, and 1” from the top of the blower pack cabinet.
6.Measure the screw locations and use two #8 screws, 2” long. The screws should be anchored in a standard 2” x 4” wood stud or equivalent to ensure adequate support of the blower pack and connecting steam hose.
7.Remove the 7/8” knockout on the top of the RESDELUX humidifier and insert the closed finger grommet into the opening.
8.Put the power leads from the blower pack through this opening. If the wire leads are not long enough field splice the additional requirement, or get a wire extension kit (P/N 1502326) available from
NORTEC.
Figure #10
Steam Absorption Distances
Steam absorption space size in inches for ambient humidity 30% RH, room temperature and selected steam outputs of RESDELUX humidifier.
H
W
F
0”
Steam Output | F | W | H |
4 lbs/hr | 36" | 12" | 12" |
6 lbs/hr | 42" | 16" | 18" |
8 lbs/hr | 48" | 18" | 18" |
- 4 -