Mitsumi electronic PLA-A30AA, PLA-A42AA, PLA-A36AA, PLA-A12AA, PLA-A24AA SELF-DIAGNOSIS Action Table

Page 18

10-3. SELF-DIAGNOSIS ACTION TABLE

Note: Refer to the manual of outdoor unit for the details of display such as F, U, and other E.

Error Code

Abnormal point and detection method

Cause

Countermeasure

 

Room temperature thermistor (TH1)

1 Defective thermistor

13Check resistance value of thermistor.

 

1 The unit is in 3-minute resume preven-

characteristics

0: (32˚F)• • • • • • • • • • • 15.0k"

 

tion mode if short/open of thermistor is

2 Contact failure of connector

10:(50˚F)• • • • • • • • • • • • • 9.6k"

 

detected. Abnormal if the unit does not

(CN20) on the indoor controller

20:(68˚F)• • • • • • • • • • • • • 6.3k"

 

reset normally after 3 minutes. (The

board (Insert failure)

30:(86˚F)• • • • • • • • • • • • • 4.3k"

 

unit returns to normal operation, if it

3 Breaking of wire or contact

40:(104˚F)• • • • • • • • • • • •3.0k"

 

has been reset normally.)

failure of thermistor wiring

If you put force on (draw or bend) the lead wire

 

2 Constantly detected during cooling,

4 Defective indoor controller

with measuring resistance value of thermistor

 

drying, and heating operation.

board

breaking of wire or contact failure can be detected.

P1

Short: 90:(194˚F) or more

 

2 Check contact failure of connector (CN20) on

 

Open: -40:(-40˚F) or less

 

the indoor controller board. Refer to 10-7.

 

 

 

Turn the power on again and check restart

 

 

 

after inserting connector again.

 

 

 

4 Check room temperature display on remote

 

 

 

controller.

 

 

 

Replace indoor controller board if there is abnor-

 

 

 

mal difference with actual room temperature.

 

 

 

Turn the power off, and on again to operate

 

 

 

after check.

 

 

 

 

 

Pipe temperature thermistor/Liquid

1 Defective thermistor

13Check resistance value of thermistor.

 

(TH2)

characteristics

For characteristics, refer to (P1) above.

 

1 The unit is in 3-minute resume

2 Contact failure of connector

2 Check contact failure of connector (CN21) on

 

prevention mode if short/open of

(CN21) on the indoor controller

the indoor controller board. Refer to 10-7.

 

thermistor is detected. Abnormal if the

board (Insert failure)

Turn the power on and check restart after

 

unit does not reset normally after 3 min-

3 Breaking of wire or contact

inserting connector again.

 

utes. (The unit returns to normal opera-

failure of thermistor wiring

4 Check pipe <liquid> temperature with remote

 

tion, if it has been reset normally.)

4 Defective refrigerant circuit is

controller in test run mode. If pipe <liquid>

P2

2 Constantly detected during cooling,

causing thermistor temperature

temperature is extremely low (in cooling

drying, and heating (except defrosting)

of 90:(194˚F) or more or

mode) or high (in heating mode), refrigerant

 

 

operation.

-40:(-40˚F) or less.

circuit may have defect.

 

Short: 90:(194˚F) or more

5 Defective indoor controller board

5 Check pipe <liquid> temperature with remote

 

Open: -40:(-40˚F) or less

 

controller in test run mode. If there is extreme

 

 

 

difference with actual pipe <liquid> temperature,

 

 

 

replace indoor controller board.

 

 

 

Turn the power off, and on again to operate

 

 

 

after check.

 

 

 

 

 

Drain sensor (DS)

1 Defective thermistor

13Check resistance value of thermistor.

 

1 Suspensive abnormality, if short/open of

characteristics

0: (32˚F)• • • • • • • • • • • • 6.0k"

 

thermistor is detected for 30 seconds

2 Contact failure of connector

10:(50˚F)• • • • • • • • • • • • 3.9k"

 

continuously.

(CN31) on the indoor controller

20:(68˚F)• • • • • • • • • • • • 2.6k"

 

Turn off compressor and indoor fan.

board (Insert failure)

30:(86˚F)• • • • • • • • • • • • 1.8k"

 

2 Short/open is detected for 30 seconds con-

 

3 Breaking of wire or contact

40:(104˚F)• • • • • • • • • • 1.3k"

 

tinuously during suspensive abnormality.

failure of drain sensor wiring

2 Check contact failure of connector (CN31) on

 

(The unit returns to normal operation, if

 

4 Defective indoor controller board

the indoor controller board. Refer to 10-7.

P4

it has been reset normally.)

 

Turn the power on again and check restart

3 Detect the following condition.

 

 

 

after inserting connector again.

 

• During cooling and drying operation

 

 

 

4 Replace indoor controller board if drain

 

• In case that pipe <liquid> temperature

 

 

- room temperature <-10deg

 

pump operates with the line of drain sensor

 

(Except defrosting)

 

connector CN31-1and 2 is short-circuited,

 

• When pipe <liquid> temperature or

 

and abnormality reappears.

 

room temperature is short/open tem-

 

Turn the power off, and on again to operate

 

perature.

 

 

 

after check.

 

• During drain pump operation

 

 

 

 

 

Malfunction of drain pump (DP)

1 Malfunction of drain pump

1 Check if drain pump works.

 

1 Suspensive abnormality, if thermistor

2 Defective drain

2 Check drain function.

 

of drain sensor heats itself and

Clogged drain pump

3 Check the setting of lead wire of drain sensor

 

temperature rises slightly. Turn off

Clogged drain pipe

and check clogs of the filter.

 

compressor and indoor fan.

3 Attached drop of water at the

4 Replace indoor controller board if drain

P5

2 Drain pump is abnormal if the condition

drain sensor

pump operates with the line of drain sensor

connector CN31-1and 2 is short-circuited

above is detected during suspensive

• Drops of drain trickles from

 

 

and abnormality reappears.

 

abnormality.

lead wire.

 

Refer to 10-7.

 

3 Constantly detected during drain pump

• Clogged filter is causing

 

 

 

operation.

wave of drain.

Turn the power off, and on again to operate

 

 

4 Defective indoor controller board

 

 

after check.

 

 

 

 

 

 

 

18

Image 18
Contents Contents Revised EDITION-BReference Manual Technical Data BookTechnical Changes PLA-A12AA PLA-A18AA PLA-A24AA PLA-A30AA PLA-A36AA PLA-A42AASafety Precaution Always Observe for SafetyAdditional refrigerant charge Part Names and Functions Indoor UnitDisplay Section Wireless remote controller Specifications Service RefPLA-A24AA/ PLA-A24AA1Single phase,60Hz, 208/230V PLA-A30AA/ PLA-A30AA1Single phase,60Hz, 208/230V PLA-A36AA/ PLA-A36AA1Single phase,60Hz, 208/230VPLA-A42AA/ PLA-A42AA1Single phase,60Hz, 208/230V PLA-A12AA1 Noise Criterion CurvesPLA-A12AA PLA-A36AAOutlines and Dimensions Unit inchmmWiring Diagram Please set the voltage usingRefrigerant System Diagram Heat exchangerTroubleshooting TroubleshootingMALFUNCTION-DIAGNOSIS Method by Remote Controller Case of trouble during operationOutput pattern B Only A-CONTROL Please Wait SELF-DIAGNOSIS Action Table Pipe temperature Cause Countermeasure Freezing/overheating protection isWorking ErrorE0/signal receiving errorE4 Cause Countermeasure Pipe temperature thermistorRemote controller transmission ErrorE3/signal receiving errorE5Remote controller control board Error Signal receiving errorError Transmitting error Indoor controller boardIs off Troubleshooting by Inferior PhenomenaPhenomena Cause Countermeasure Ply system3Upward/downward vane 4Receiver for wireless remoteIs blinking Performance failureEmergency Operation Fan motor MF Thermistor for lower temperature Test Point Diagram Indoor controller board Functions of DIP Switch and Jumper Wire SW2Disassembly Procedure Operating Procedure Photos & IllustrationsRemoving the fan motor Removing the drain pump and drain sensor Wiring Recom QtyPLA-A·AA Functional and Structural Parts PLA-A36AA98 PLA-A42AA 12, 18, 24 Symbol Qty MendedFunctional and Structural Parts PLA-A36AA PLA-A42AA 556RoHS Parts List 30/36/42AA1Functional and Structural Parts WiringSymbol Qty PLA-A18AA1 PLA-A24AA1PLA-A30AA1PLA-A36AA198 RoHS Parts No Parts Name Functional and Structural Parts PLA-A36AA1 PLA-A42AA1 RemarksPage Made in Japan

PLA-A30AA, PLA-A42AA, PLA-A18AA, PLA-A12AA, PLA-A24AA specifications

Mitsumi Electric, a leading manufacturer in the electronic components industry, offers a diverse range of products tailored to meet various application needs. Among the offerings are the PLA series devices: PLA-A36AA, PLA-A24AA, PLA-A12AA, PLA-A18AA, and PLA-A42AA. These components are renowned for their cutting-edge features, robust technologies, and versatile characteristics, making them essential in modern electronics.

The PLA-A36AA is recognized for its high-speed operation and low power consumption, ideal for applications needing efficient energy usage. It features an advanced thermal management system to ensure optimal performance even in high-temperature environments. The integrated circuitry minimizes noise interference, providing clearer signal processing essential for audio and communication devices.

Moving on to the PLA-A24AA, this model stands out due to its compact design and reliability. It is particularly suited for space-constrained applications without compromising performance. The PLA-A24AA employs surface-mount technology, making it easier to integrate into various electronic assemblies. Its enhanced durability against mechanical stress and environmental conditions ensures longevity and stable operation.

The PLA-A12AA is engineered for versatile applications, offering flexibility in various settings, from consumer electronics to industrial machinery. With its user-friendly interface and programmable features, it allows for extensive customization, catering to specific user requirements. Additionally, its energy-efficient design contributes to sustainable practices in electronics manufacturing.

The PLA-A18AA is celebrated for its high-frequency performance, making it a popular choice for telecommunications and data transmission applications. This model incorporates advanced filtering technologies to facilitate reliable signal processing, an essential feature in today's high-speed internet and communication networks.

Finally, the PLA-A42AA combines robust construction with high-performance metrics, designed for heavy-duty applications in automotive and industrial environments. Its resistance to extreme conditions, including temperature fluctuations and vibrations, ensures that it performs reliably under demanding circumstances.

Through a commitment to innovation and quality, Mitsumi Electric’s PLA series exemplifies state-of-the-art technology in electronic components, catering to a broad spectrum of industry needs while promoting efficiency and reliability. These models reflect the evolution of electronic design, adapting to the fast-paced demands of modern technology, making them invaluable assets in any tech-focused endeavor.