Mermaid Air Conditioner manual Compressor Runs Fan Does Not, No Water Out

Page 32

j)After you have removed all 115 (220) vac electrical power, the electrical box cover may be removed by removing the three retaining screws on each side of the box. Once the screws are removed the cover will slide off the box.

k)Closely check the box for loose or disconnected wires. If all wiring is tight and in

place, replace the transformer. A new transformer may be purchased from your nearest Mermaid dealer, refrigeration supply store or direct from the Mermaid factory.

2. Standard 24v Thermostat In COOL Position - Fan Runs - Compressor Does Not:

a)Place thermostat in the OFF position. Locate the HIGH PRESSURE switch mounted on the top of the air conditioner unit. Check if the red button is active or extended. If the pin is extended, push it in. This switch shuts power off to the compressor when cooling water is insufficient to make the required heat exchange as described in Theory Of Operation above. Check water pump for prime and motor operation, check raw water strainer for clogging and hoses for kinks. Fix water problem and turn thermostat back on.

b)If water pump is operational and HIGH PRESSURE switch has not activated, perform thermostat jumper test described in paragraph 1h) above. If unit operates, replace thermostat batteries and/or thermostat.

3. Compressor Runs - Fan Does Not:

a)Place thermostat in the OFF position. Use a shorting wire as described in paragraph

1h above, except this time short the "RED" wire to the "GREEN" wire. If fan comes on, thermostat is faulty.

b)If fan does not come on when jumper is applied, it is most likely a faulty fan relay inside the electrical box or an external fan capacitor. Replace the fan relay or capacitor with the recommended from the factory. Before opening the electrical box, all 115 (220) power must be removed from the boat. See the above Note and WARNING under paragraph 1i) regarding opening the electrical box.

4. No Water Out:

a)Put thermostat in OFF position.

b)Check that sea cock is open. If closed, open and prime pump.

c)Check raw water strainer. If dirty, clean and prime pump.

d)Check that pump is running. If pump is faulty, replace and prime.

Image 32
Contents Mermaid Marine AIR Conditioning Table of Contents Installation and Operation OverviewAIR Conditioner Installation Installing the Air Conditioner Unit AIR Conditioner Dimensions Unit BTU Width Length HeightCooling water in and out WaterPage Page Water Strainer Pump Water Out Electrical Power Air Ducting and Splitting Model BTU SQ. Inches of Return Return AirReturn AIR Requirements High Pressure Switch Access Condensation RemovalPage See Warning below Putting it all togetherMaking contact with the hull Wire Connections Priming The Pump PowerSystem Operation Checking Out The System Setting the Current DAY and Time IntroductionPage Temperature Override and Temperature Hold Temporary Temperature OverrideNormal Operation Programming the ThermostatVacation Temperature Hold InstallationPage Air System MaintenanceWater System Air Conditioning Unit and Water Pump Electrical SystemWinterization Theory of Operation General Theory of Operation and Trouble ShootingClean AIR ACT Amendments of 1990 Title VI C-1 Heating Options ElectricalStandard 24v Thermostat In Cool Position No Operation Trouble ShootingCooling Water Page Compressor Runs Fan Does Not No Water OutEvaporator Freezing Condensation Pan OverflowsHigh Pressure Switch Activates In Cooling Mode High Pressure Switch Activates In Heating ModeNo Heat Electric Heat Unit Fan Runs No Heat Reverse Cycle Unit Compressor And Fan RunOUR Normal Procedure for a Warranty Issue is AS Follows