ICP DAS USA DFS2A318J2A, DFS2H324J2A Indoor Unit Installation, Install the Mounting Bracket

Page 4

 

6" (0.15m) min.

8"

8"

(0.2m)

(0.2m)

min.

min.

6'-8'3" (1.8-2.5m)

Fig. 2 — Indoor Unit Clearances

INSTALLATION

Plan the installation carefully to avoid component failures and make installation easier.

Indoor Unit Installation

REFRIGERANT LINE ROUTING — The refrigerant lines may be routed in any of the four directions shown in Fig. 3.

INSTALL THE MOUNTING BRACKET

1.Carefully remove the mounting bracket, which is connected to the back of the indoor unit's base with screws.

2.Position the mounting bracket on the wall and level it using a spirit level (see Fig. 2 for minimum required clearance distances).

3.Mark the four drilling holes on the wall, as they appear in Fig. 4.

4.Drill the holes, insert the wall plugs and use four long screws to attach the mounting bracket to the wall.

5.Check that the bracket is leveled and securely fastened to the wall.

DRILL A HOLE IN THE WALL FOR DRAINAGE AND INTER-UNIT CONNECTIONS-

To make the connections between the indoor and outdoor units, drill a 2.5-in. hole through the wall for the refrigerant lines, drain- age hose and control cable passage as shown in Fig. 5.

1.Mark the center of the hole to be drilled according to the refrigerant line routing used and dimensions shown in Fig. 4.

2.Make sure to drill outwards and downwards, so that the opening in the outside wall is at least 1/2" lower than the opening on the inside.

3.Make sure the drainage hose is at the bottom side of the hole.

4 . If refrigerant line route no. 1,2 or 4 are used, use a small saw blade to carefully remove the corresponding plastic covering on the side panel.

5.Run the outdoor sensor cable, electrical cable, refrigerant lines, and drainage tube through the hole.

6.Fill the remaining wall hole gap with an appropriate sealant material.

2

3

 

 

1

4

Fig. 3 — Refrigerant Lines

Fig. 4 — Mounting Bracket DFF2A/DFF2H 09, 12

2.5-IN.

Fig. 5 — Drill Holes

4

Image 4
Contents Safety Considerations ContentsGeneral Parts List High Wall Units QTY DiagramPhysical Data Cooling Only Physical Data Heat PumpIndoor Unit Installation InstallationInstall the Mounting Bracket Wire the Indoor Unit Reassemble Make Drainage ConnectionsDischarge opening Mount the indoor unit on the mounting bracketAttach the Remote Controller Mounting Bracket OptionalIndoor unit LED’s and Wiring Electrical Data, Outdoor Units 115 Electrical Data, Indoor Units 30VDCMCA Condensing Unit Indoor UNSchematic DFF2AH09J1A, DFF2AH12J1A FAN Coil with D O O R U N I TCare and Maintenance ServiceSTART-UP Indoor UnitService Indicators Troubleshooting Tables 6-8, and FigLamp Status Indication Correction Action Tempeature Temperature Minimum Mean 100.4 General System Troubleshooting Guide