Cooling Model | Heat Pump |
| ||
DFS2A318J2A | DFS2H318J2A | DFS2A/H 2 X 09, 2 X 12 | ||
DFS2A324J2A | DFS2H324J2A | |||
Duct Free Systems | ||||
|
|
Installation, Start-Up and Service Instructions
CONTENTS | Page |
SAFETY CONSIDERATIONS | 1 |
GENERAL | |
INSTALLATION | |
Indoor Unit Installation | 4 |
Outdoor Unit Installation | 6 |
Power Supply | 7 |
Leak Test | 7 |
Wiring Diagrams | |
11 | |
System Checks | 11 |
CARE AND MAINTENANCE | 11 |
Outdoor Units | 11 |
Indoor Units | 11 |
To Clean the Indoor Unit Front Panel | 11 |
To Clean Indoor Coil | 11 |
Air Filters for Indoor Units | 11 |
SERVICE | 11 |
TROUBLESHOOTING |
SAFETY CONSIDERATIONS
Installing, starting up, and servicing
Only trained, qualified installers and service mechanics should install,
Untrained personnel can perform basic maintenance func- tions such as cleaning coils. All other operations should be per- formed by trained service personnel.
When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equip- ment.
Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.
WARNING
Before installing or servicing system, always turn off main power to system and install lockout tag on disconnect. There may be more than one disconnect switch. Electrical shock can cause personal injury.
GENERAL
These instructions cover the installation,
System Requirements
IMPORTANT: The Indoor units & the inter units cable voltage is 30 VDC.
IMPORTANT: Each refrigerant line must be insulated Separately. See line sizing requirements in tabel 2.
• | Consult local building codes and National Electrical Code | |||
| (NEC, U.S.A.) for special installation requirements. | |||
| Max. cable length. Total voltage drop should not exceed 1V. | |||
| Therefore max. length: | |||
|
|
|
|
|
|
| For #18 AWG | 24.3 Feet (7.4 m) |
|
|
|
|
|
|
|
| For #16 AWG | 37.7 Feet (11.5 m) |
|
|
|
|
|
|
|
| For #14 AWG | 50.0 Feet (18 m) |
|
|
|
|
|
|
• | Use only type "G" or "C" fuses. Use single length power | |||
| cable without extension. Allow sufficient space for airflow | |||
| clearance on condensing units for wiring, refrigerant piping, | |||
| and servicing unit. See Fig. 1 and 2 for minimum required | |||
| distances between unit and walls or ceilings. | |||
• | Indoor and outdoor units should be installed at a | |||
| Minimum length of 10 ft. apart. | |||
| Maximum line length of 50 ft. and | |||
| vertical separation of 30 ft. | |||
• | Do not install indoor units near a direct source of heat such as | |||
| direct sunlight, steam or flame. |
CAUTION
Do not bury more than 36 in. of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. vertical rise to the valve connections on the outdoor units. If more than the rec- ommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes
TOP (min.) 2" (0.6m)
LEFT (min.) 6" (0.15m)
FRONT (min.) 2" (0.6m)
REAR (min.) 6" (0.15m)
RIGHT(min.)
2" (0.6m)
Fig. 1 — 38BCC/BCQ 018, 024 Outdoor Unit Clearances
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without inc. | Printed in Israel |