ICP DAS USA DFS2H324J2A, DFS2A318J2A specifications Contents, Safety Considerations, General

Page 1

Cooling Model

Heat Pump

 

51302618919-A0606

DFS2A318J2A

DFS2H318J2A

R-22

DFS2A/H 2 X 09, 2 X 12

DFS2A324J2A

DFS2H324J2A

Duct Free Systems

 

 

Installation, Start-Up and Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

1

GENERAL

1-4

INSTALLATION

4-11

Indoor Unit Installation

4

Outdoor Unit Installation

6

Power Supply

7

Leak Test

7

Wiring Diagrams

9-10

START-UP

11

System Checks

11

CARE AND MAINTENANCE

11

Outdoor Units

11

Indoor Units

11

To Clean the Indoor Unit Front Panel

11

To Clean Indoor Coil

11

Air Filters for Indoor Units

11

SERVICE

11

TROUBLESHOOTING

12-15

SAFETY CONSIDERATIONS

Installing, starting up, and servicing air-conditioning equip- ment can be hazardous due to system pressures, electrical compo- nents, and equipment location (roofs, elevated structures, etc.).

Only trained, qualified installers and service mechanics should install, start-up, and service this equipment.

Untrained personnel can perform basic maintenance func- tions such as cleaning coils. All other operations should be per- formed by trained service personnel.

When working on the equipment, observe precautions in the literature and on tags, stickers, and labels attached to the equip- ment.

Follow all safety codes. Wear safety glasses and work gloves. Keep quenching cloth and fire extinguisher nearby when brazing. Use care in handling, rigging, and setting bulky equipment.

WARNING

Before installing or servicing system, always turn off main power to system and install lockout tag on disconnect. There may be more than one disconnect switch. Electrical shock can cause personal injury.

GENERAL

These instructions cover the installation, start-up and servic- ing of DFC2A/DFC2H outdoor and DFF2A/DFF2H indoor units cool- ing only and heat pump duct free systems. See Table 1 for parts included. See Tables 2 and 3 for Physical Data.

System Requirements

IMPORTANT: The Indoor units & the inter units cable voltage is 30 VDC.

IMPORTANT: Each refrigerant line must be insulated Separately. See line sizing requirements in tabel 2.

Consult local building codes and National Electrical Code

 

(NEC, U.S.A.) for special installation requirements.

 

Max. cable length. Total voltage drop should not exceed 1V.

 

Therefore max. length:

 

 

 

 

 

 

 

For #18 AWG

24.3 Feet (7.4 m)

 

 

 

 

 

 

 

 

For #16 AWG

37.7 Feet (11.5 m)

 

 

 

 

 

 

 

 

For #14 AWG

50.0 Feet (18 m)

 

 

 

 

 

 

Use only type "G" or "C" fuses. Use single length power

 

cable without extension. Allow sufficient space for airflow

 

clearance on condensing units for wiring, refrigerant piping,

 

and servicing unit. See Fig. 1 and 2 for minimum required

 

distances between unit and walls or ceilings.

Indoor and outdoor units should be installed at a

 

Minimum length of 10 ft. apart.

 

Maximum line length of 50 ft. and

 

vertical separation of 30 ft.

Do not install indoor units near a direct source of heat such as

 

direct sunlight, steam or flame.

CAUTION

Do not bury more than 36 in. of refrigerant pipe in the ground. If any section of pipe is buried, there must be a 6 in. vertical rise to the valve connections on the outdoor units. If more than the rec- ommended length is buried, refrigerant may migrate to the cooler buried section during extended periods of system shutdown. This causes refriger-ant slugging and could possibly damage the com- pressor at start-up.

TOP (min.) 2" (0.6m)

LEFT (min.) 6" (0.15m)

FRONT (min.) 2" (0.6m)

REAR (min.) 6" (0.15m)

RIGHT(min.)

2" (0.6m)

Fig. 1 — 38BCC/BCQ 018, 024 Outdoor Unit Clearances

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without inc.

Printed in Israel

Pg 1

Image 1
Contents Safety Considerations ContentsGeneral QTY Diagram Parts List High Wall UnitsPhysical Data Heat Pump Physical Data Cooling OnlyIndoor Unit Installation InstallationInstall the Mounting Bracket Make Drainage Connections Wire the Indoor Unit ReassembleDischarge opening Mount the indoor unit on the mounting bracketOptional Attach the Remote Controller Mounting BracketIndoor unit LED’s and Wiring Electrical Data, Outdoor Units 115 Electrical Data, Indoor Units 30VDCMCA Indoor UN Condensing UnitD O O R U N I T Schematic DFF2AH09J1A, DFF2AH12J1A FAN Coil withService Care and MaintenanceSTART-UP Indoor UnitService Indicators Troubleshooting Tables 6-8, and FigLamp Status Indication Correction Action Tempeature Temperature Minimum Mean 100.4 General System Troubleshooting Guide