TROUBLESHOOTING (Tables 6-8, and Fig. 19)

WARNING

Be sure to check for broken wires or loose cable lugs before troubleshooting system.

Table 6 — Service Indicators

LAMP STATUS

INDICATION

CORRECTION ACTION

 

 

Check the TH1 thermistor for correct resistance.

1 Flash

Faulty TH1 Sensor

Check for proper connection.

 

 

Replace thermistor if necessary.

 

 

Check the TH2 thermistor for correct resistance.

2 Flashes

Faulty TH2 Sensor

Check for proper connection.

 

 

Replace thermistor if necessary.

 

 

Check system pressures.

3 Flashes

Low Pressure

Check refrigerant charge.

 

 

Check thermistors (TH1 and TH2) for correct resistance.

 

 

Check system pressures.

4 Flashes

High Pressure

Check refrigerant charge.

 

 

Check thermistors (TH1 and TH2) for correct resistance.

5 Flashes

Low Voltage

Check operating voltage.

 

 

 

Check electrical connections.

6 Flashes

High Voltage

Check operating voltage.

 

 

 

Check electrical connections.

 

 

 

OPERATION LED.

INDICATES ERROR

POWER LED.

OFF WHEN SYSTEM IS OPERATING AND FLASHES WHEN SYSTEM IS IN ERROR.

(DOES NOT INDICATE ERROR CODE)

CLEAN FILTER INDICATOR

FLASHED AFTER 250 HOURS

OF OPERATION

Fig. 19— Indicator Lights

12

Image 12
Contents Contents Safety ConsiderationsGeneral Parts List High Wall Units QTY DiagramPhysical Data Cooling Only Physical Data Heat PumpInstallation Indoor Unit InstallationInstall the Mounting Bracket Wire the Indoor Unit Reassemble Make Drainage ConnectionsDischarge opening Mount the indoor unit on the mounting bracketAttach the Remote Controller Mounting Bracket OptionalIndoor unit LED’s and Wiring Electrical Data, Indoor Units 30VDC Electrical Data, Outdoor Units 115MCA Condensing Unit Indoor UNSchematic DFF2AH09J1A, DFF2AH12J1A FAN Coil with D O O R U N I TCare and Maintenance ServiceSTART-UP Indoor UnitTroubleshooting Tables 6-8, and Fig Service IndicatorsLamp Status Indication Correction Action Tempeature Temperature Minimum Mean 100.4 General System Troubleshooting Guide