GSW PART NO.70999 REV.G (03-12) Installation Check List, Pressure BUILD-UP in a Water System

Page 7

Pressure rating of the valve must not exceed the working pressure shown on the rating plate of the water heater. The discharge capacity must be equal to or greater than the input to the water heater. Temperature and Pressure Relief valve piping must terminate 6 inches, no more than 12” (reference the applicable code) above a floor drain or external to the building. Do not thread, cap, or plug the end of this discharge line. Be certain that no contact is made with any live electrical part. Do not connect discharge line directly to drain. See Figure 2. To prevent bodily injury, hazard to life or damage to property, the relief valve must be allowed to discharge water in the event of excessive temperature or pressure developing in the water heater. The function of the temperature and pressure relief valve is to discharge water in quantities should circumstances demand. If the discharge pipe is not directed to drain as shown in Figure 2 or other suitable means, the water flow may cause property damage.

The discharge line:

1)must not be smaller than the outlet pipe size of the relief valve,

2)must not be plugged or blocked,

3)must be material capable of withstanding 210°F without distortion,

4)must be installed so as to allow complete drainage of both temperature and pressure relief valve,

5)must terminate at an adequate drain, and

6)must not have any valve between the relief valve and the water heater.

WARNING

Do not attempt to operate this water heater with the cold water inlet valve closed. Manually operate the Temperature and Pressure Relief valve at least once a year. Standing clear of the outlet (discharge water may be hot), lift and release the lever handle on the Temperature and Pressure Relief valve to make the valve operate freely.

NEVER OPERATE THE HEATER IF IT IS NOT COMPLETELY FILLED WITH WATER. TO MAKE SURE THE HEATER IS FILLED, OPEN A HOT WATER TAP UNTIL A FULL FLOW OF WATER IS VISIBLE WITH NO AIR ESCAPING.

PRESSURE BUILD-UP IN A WATER SYSTEM

During the heating cycle of the water heater the water expands, creating a pressure build-up in the water system. The water supply meter may contain a check valve or back flow preventer. This will create a closed water system. A temperature and pressure relief valve must be installed on the water heater (150 PSI maximum pressure setting. See temperature and pressure relief valve).

If a water heater is installed in a closed water supply system, the relief valve will discharge water as the volume of water expands with rising water temperatures. This is normal and indicates a normal functioning of the relief valve. Do not plug the relief valve. Only if the discharge from the relief valve is continuous or for an extended period of time would this indicate a malfunction. Have the operation of the heater checked by a qualified serviceman.

INSTALLATION CHECK LIST

Check Here

1. Have the vent location limitations and minimum height for vent termination and maximum vent length been checked?

2. Are the terminal and vent pipes installed and sealed properly?

3. Has the gas piping been leak tested?

4. Is there at least a 1” clearance between the water heater and combustible materials, 20” at the top and 1” around the vent pipe?

5. Have you taken steps to prevent water damage in case of leaks?

6. Is the diptube installed in the cold water inlet connection?

7. Is the water heater completely filled with water?

8.Does the gas piping conform with the recommendations of your Local Gas Utility Company?

9. Is the vent terminal opening unobstructed?

10.Is a temperature and pressure relief valve installed?

11.Is the drain pipe from the T & P valve unobstructed?

12.Has all plastic and cardboard packaging material been removed from the heater and venting?

IF the answer to all of the above questions is “YES” proceed with lighting the heater.

– 6 –

Image 7
Contents Direct Vent GAS Fired Water Heater For Your SafetyLocation InstallationOption Vent Location Limitations Condition GAS Connections Temperature & Pressure Relief ValvePressure BUILD-UP in a Water System Installation Check ListFor Your Safety Read Before Lighting VI Lighting After InstallationLighting Instructions for Heater with SIT GAS Controls Robertshaw R110 GAS Control Exposure to Water Water Temperature RegulationHigher Setting Increases Risk of Scald Injury Burner MaintenanceCathodic Protection Maintenance Instructions General HousekeepingTank Venting System InspectionDo not Tamper with the GAS Control Control~ Certificate of Warranty ~

PART NO.70999 REV.G (03-12) specifications

The GSW PART NO. 70999 REV.G (03-12) is an exemplary product designed for high-performance application in various industrial settings. This part stands out not only for its robust construction but also for its advanced technological features, which cater to the evolving demands of modern industry.

One of the main characteristics of the GSW 70999 REV.G is its durable design, engineered to withstand challenging operational conditions. The materials used in its construction are specifically chosen for their strength and resistance to wear and corrosion, ensuring longevity and reliability in performance. This makes the component an ideal choice for applications that require consistent and dependable operation over extended periods.

In terms of technology, the GSW 70999 REV.G incorporates cutting-edge manufacturing processes that enhance its precision and functionality. The advanced machining techniques employed ensure tight tolerances and superior fit, which contribute to improved efficiency in machinery operation. This precision is particularly critical in high-speed applications, where even minor discrepancies can lead to significant performance issues.

Another key feature of the GSW 70999 REV.G is its adaptability. The part is designed with versatility in mind, allowing it to be integrated seamlessly into a variety of systems and equipment. This adaptability minimizes downtime during installation and maintenance, as users can easily incorporate the part into their existing configurations without extensive modifications.

The GSW 70999 REV.G also benefits from innovative design aspects such as ergonomic considerations, which aim to simplify handling and improve user experience. The thoughtful layout and accessibility of the component facilitate easier maintenance procedures, ultimately reducing operational costs and maximizing productivity for users.

Furthermore, GSW emphasizes sustainability in its product design and manufacturing processes. The materials are selected not only for their performance characteristics but also for their environmental impact, aligning with the industry's growing focus on sustainability and responsible sourcing.

In summary, the GSW PART NO. 70999 REV.G (03-12) is a crucial component characterized by its durability, precision, adaptability, and commitment to sustainability. It serves as an integral part in various industrial applications, promoting efficiency and reliability while catering to the increasing demands of modern technological advancement. Whether in high-speed settings or more moderate environments, this part exemplifies quality and innovation in industrial design.