Installation of outdoor unit

Step four: connect indoor and outdoor pipes

1.Remove the screw on the right han- dle of outdoor unit and then remove the handle.

screw

handle

2.Remove the screw cap of valve and aim the pipe joint at the bellmouth of pipe.

 

liquid pipe

liquid

gas pipe

valve

 

 

gas valve

3.Pretightening the union nut with hand.

pipe joint

union nut

4.Tighten the union nut with torque wrench by referring to the sheet below.

Hex nut diameter

Tightening torque

 

(N.m)

ĭ

15~20

ĭ

30~40

ĭ

40~55

ĭ

60~65

ĭ

70~75

6WHS¿YHFRQQHFWRXWGRRUHOHFWULFZLUH

1.Remove the wire clip; connect the power connection wire and signal control wire (only for Heat pump type) to the wiring terminal according to the color; fix them with screws.

1824K Heat pump type:

N(1) 2 3 L N

yellow- green

blue black brown

brown yellow- (black) blue green

L N

Indoor unit connection POWER

26

Image 29
Contents Split Air Conditioner Page Content Working temperature range PrecautionsIndoor Unit Parts nameIntroduction for icons on display screen Buttons on remote controllerTimer ON/TIMER OFF Button to adjust fan blowing angle Introduction for buttons on remote controllerEXWWRQ Auto&ORFNWLPHDGRSWVKRXUPRGH Timer on / Timer OFF button 7,0521EXWWRQUse remote controller to cancel it WRGLVSOD\VHWWHPSHUDWXUHDIWHUWKUHHRU¿YHVHFRQGV $1EXWWRQ2QO\IRUWKHPRGHOVZKRVHLQGRRUXQLWKDVGXDOGLVSOD\ Child lock function Temperature display switchover functionFunction introduction for combination buttons Operation guide Replacement of batteries in remote controllerClean surface of indoor unit Clean and maintenanceEmergency operation Panel Aux. buttonKHQWKH¿OWHULVYHU\GLUW\XVH Open panel&OHDQ¿OWHUDQGLQGRRUXQLW¶VSDQHO Disconnect power supply&KHFNZKHWKHU¿OWHULVFOHDQ General phenomenon analysis Malfunction analysis5HPRYHREVWDFOHV OLPLQDWHREVWDFOHV,VSOXJORRVH 5HLQVHUWWKHSOXJ 3RZHUIDLOXUHLULQJKDVPDOIXQFWLRQ 5HVHWWKHIXQFWLRQUnit, which is a normal phenomenon OLPLQDWHWKHRGRXUVRXUFH &OHDQWKH¿OWHU7KHQRLVHLVWKHVRXQGRI UHIULJHUDQWÀRZLQJLQVLGH FRQWDFWTXDOL¿HGSURIHVVLRQDOVIRUVHUYLFH Error CodeH1 0HDQVGHIURVWLQJVWDWXV,W¶VWKHQRUPDOSKHQRPHQRQ Installation dimension diagram Selection of installation location Tools for installationRequirements for electric connection Safety precautionGrounding requirement DQG&&E\DXWKRULHGSHUVRQQHORQO\Step one choosing installation location Installation of indoor unitStep two install wall-mounting frame Step three open piping holeRSHQLQJWKHKROH Step four outlet pipeORFDOO\ Pretightening the union nut with handStep seven connect wire of indoor unit Step six install drain hoseInstallation With wire clipStep nine hang the indoor unit Step eight bind up pipeUpper hook Lower hook of wall-mounting frameSelect it according to the actual installation situation Installation of outdoor unitJoint RUWKHXQLWZLWKFRROLQJFDSDFLW\RIPipe joint Union nut Step four connect indoor and outdoor pipesPipe hole of indoor unit Step six neaten the pipesUse vacuum pump Vacuum pumpingLeakage detection Test operation Check after installationLiquid pipe RQ¿JXUDWLRQRIFRQQHFWLRQSLSHRQ¿JXUDWLRQRIFRQQHFWLRQSLSH &KHFNWKHTXDOLW\RIHSDQGLQJSRUW Pipe expanding methodSDQGWKHSRUWZLWKHSDQGHU 66129914641