Heatcraft Refrigeration Products H-IM-CU warranty Preventive Maintenance, Unit Coolers

Page 19

Preventive Maintenance

Unit Coolers

At every six month interval, or sooner if local conditions cause clogging or fouling of air passages through the finned surface, the following items should be checked.

1)Visually inspect unit

Look for signs of corrosion on fins, cabinet, copper tubing and solder joints.

Look for excessive or unusual vibration for fan blades or sheet metal panels when in operation. Identify fan cell(s) causing vibration and check motor and blade carefully.

Look for oil stains on headers, return bends, and coil fins. Check any suspect areas with an electronic leak detector.

Check drain pan to insure that drain is clear of debris, obstructions or ice buildup and is free draining.

2)Clean evaporator coil and blades

Periodic cleaning can be accomplished by using a brush, pressurized water or a commercially available evaporator coil cleaner or mild detergent. Never use an acid based cleaner. Follow label directions for appropriate use. Be sure the product you use is approved for use in your particular application.

Flush and rinse coil until no residue remains.

Pay close attention to drain pan, drain line and trap.

3)Check the operation of all fans and ensure airflow is unobstructed

Check that each fan rotates freely and quietly. Replace any fan motor that does not rotate smoothly or makes an unusual noise.

Check all fan set screws and tighten if needed.

Check all fan blades for signs of stress or wear. Replace any blades that are worn, cracked or bent.

Verify that all fan motors are securely fastened to the motor rail.

Lubricate motors if applicable.

4)Inspect electrical wiring and components

Visually inspect all wiring for wear, kinks, bare areas and discoloration. Replace any wiring found to be damaged.

Verify that all electrical and ground connections are secure, tighten if necessary.

Check operation/calibration of all fan cycle and defrost controls when used.

Look for abnormal accumulation of ice patterns and adjust defrost cycles accordingly

Compare actual defrost heater amp draw against unit data plate.

Visually inspect heaters to ensure even surface contact with the coil. If heaters have crept, decrease defrost termination temperature and be sure you have even coil frost patterns. Re-align heaters as needed.

Check drain line heat tape for proper operation (supplied and installed by others).

5)Refrigeration Cycle

Check unit cooler superheat and compare reading for your specific application

Visually inspect coil for even distribution

Air-Cooled Condensing Units

Quarterly

1)Visually inspect unit

Look for signs of oil stains on interconnection piping and condenser coil. Pay close attention to areas around solder joints, building penetrations and pipe clamps. Check any suspect areas with an electronic leak detector. Repair any leaks found and add refrigerant as needed.

Check condition of moisture indicator/sightglass in the sight glass if so equipped. Replace liquid line drier if there is indication of slight presence of moisture. Replace refrigerant, oil and drier if moisture concentration is indicated to be high.

Check moisture indicator/sightglass for flash gas. If found check entire system for refrigerant leaks and add refrigerant as needed after repairing any leaks.

Check compressor sightglass (if equipped) for proper oil level.

Check condition of condenser. Look for accumulation of dirt and debris (clean as required).

Check for unusual noise or vibration. Take corrective action as required.

Inspect wiring for signs of wear or discoloration and repair if needed.

Check and tighten all flare connections.

Semi-Annually

2)Repeat all quarterly inspection items.

3)Clean condenser coil and blades

Periodic cleaning can be accomplished by using a brush, pressurized water and a commercially available foam coil cleaner. If foam cleaner is used, it should not be an acid based cleaner. Follow label directions for appropriate use.

Rinse until no residue remains.

4)Check operation of condenser fans

Check that each fan rotates freely and quietly. Replace any fan motor that does not rotate smoothly or makes excessive noise.

Check all fan blade set screws and tighten as required.

Check all fan blades for signs of cracks, wear or stress. Pay close attention to the hub and spider. Replace blades as required.

Verify that all motors are mounted securely.

Lubricate motors if applicable. Do not lubricate permanently sealed, ball bearing motors.

5)Inspect electrical wiring and components

Verify that all electrical and ground connections are secure, tighten as required.

Check condition of compressor and heater contactors. Look for discoloration and pitting. Replace as required.

Check operation and calibration of all timers, relays pressure controls and safety controls.

Clean electrical cabinet. Look for signs of moisture, dirt, debris, insects and wildlife. Take corrective action as required.

Verify operation of crankcase heater by measuring amp draw.

6)Check refrigeration cycle

Check suction, discharge and net oil pressure readings. If abnormal take appropriate action.

Check operation of demand cooling, liquid injection or unloaders if so equipped.

Check pressure drop across all filters and driers. Replace as required.

Verify that superheat at the compressor conforms to specification. (30°F to 45°F)

Check pressure and safety control settings and verify proper operation.

Annually

7)In addition to quarterly and semiannual maintenance checks, submit an oil sample for analysis

Look for high concentrations of acid or moisture. Change oil and driers until test results read normal.

Investigate source of high metal concentrations, which normally are due to abnormal bearing wear. Look for liquid refrigerant in the crankcase, low oil pressure or low superheat as a possible source.

8)Inspect suction accumulator (if equipped)

If the accumulator is insulated remove insulation and inspect for leaks and corrosion.

Pay close attention to all copper to steel brazed connections

Wire brush all corroded areas and peeling paint.

Apply an anticorrosion primer and paint as required. Re-insulate if applicable.

19

Image 19
Contents Units Warranty Statement General Safety InformationSome units are pressurized with dry air or inert gas Decorative Fences Requirements for Remote and Water Cooled Condensing Units Diagram City & Tower Water ConnectionsCondensing Unit Rigging and Mounting Head Pressure Control Ambient Fan Cycle Thermostat SettingsMineral Oils Refrigeration OilsOil Types Polyol Ester LubricantsSuction Lines Phase Loss MonitorRecommended Refrigerant Piping Practices Refrigerant Pipe SupportHot Gas Defrost Systems Liquid LinesHot gas line sizes for R-22, R404A and R507 Line Sizing Unit Cooler PipingRecommended Remote Condenser Line Sizes Equivalent Feet of Pipe Due to Valve and Fitting FrictionCopper Tube, O.D., Type L Globe Valve Open 000 Recommended Line Sizes for R-22Recommended Line Sizes for R-404A and R507 Evacuation and Leak Detection Field WiringRefrigerant Charging Instructions Check Out and Start Up System Balancing Compressor Superheat Operational Check OutExample General Sequence of Operation Electric Defrost TroubleshootingOperation of Paragon Timer Operation of Grasslin TimerClean strainers System Troubleshooting ChartCheck liquid line solenoid valve operation Unit Coolers Preventive MaintenanceAir-Cooled Condensing Units Page Page Page Page Replacement Parts by

H-IM-CU specifications

Heatcraft Refrigeration Products has long been recognized as a leader in the refrigeration industry, and their H-IM-CU model is a prime example of innovative design and cutting-edge technology. The H-IM-CU is engineered to deliver exceptional performance and efficiency, catering to various commercial refrigeration needs.

One of the standout features of the H-IM-CU is its robust construction. The unit is designed with high-quality materials that ensure durability and long-lasting performance in demanding environments. This construction not only protects against wear and tear but also supports the reliable operation essential for business continuity.

The H-IM-CU incorporates advanced cooling technologies that enhance its efficiency. Equipped with a high-efficiency compressor, this model optimizes energy consumption, reducing operational costs while still maintaining optimal refrigerant temperatures. This energy-efficient design is particularly beneficial for businesses looking to minimize their carbon footprint and achieve sustainability goals.

An important characteristic of the H-IM-CU is its user-friendly control system. The intuitive interface allows operators to easily adjust and monitor temperature settings, ensuring that products are stored in favorable conditions. This user-centric design simplifies the management of refrigeration units, making it easier for staff to perform routine tasks.

Additionally, the H-IM-CU features a whisper-quiet operation, which is an advantage for businesses that prioritize a pleasant customer experience. This is achieved through effective sound-dampening technologies and smart engineering that minimize noise without compromising cooling performance.

Another significant highlight is the versatility of the H-IM-CU. It is suitable for a wide range of applications, from convenience stores to restaurants and supermarkets. This adaptability makes it a preferred choice for businesses seeking a reliable refrigeration solution that can cater to their specific needs.

Furthermore, the model boasts enhanced airflow technology that ensures even temperature distribution throughout the unit. This promotes efficient cooling and eliminates hotspots, keeping products at the desired temperature consistently.

Overall, the Heatcraft Refrigeration Products H-IM-CU stands out as a leading choice in commercial refrigeration. With its combination of durability, energy efficiency, user-friendly controls, quiet operation, and versatility, it meets the high standards of modern businesses looking for reliable cooling solutions. Investing in the H-IM-CU not only enhances product longevity but also aids in operational efficiency, making it a wise choice for any commercial refrigeration setup.