Heatcraft Refrigeration Products H-IM-CU warranty Phase Loss Monitor, Refrigerant Pipe Support

Page 8

Phase Loss Monitor

The combination phase sequence and loss monitor relay protects the system against phase loss (single phasing), phase reversal (improper sequence) and low voltage (brownout). When phase sequence is correct and full line voltage is present on all three phases, the relay is energized as the normal condition indicator light glows.

Note: If compressor fails to operate and the normal condition indicator light on the phase monitor does not glow, then the supplied electrical current

is not in phase with the monitor. This problem is easily corrected by the following steps:

1.Turn power off at disconnect switch.

2.Swap any two of the three power input wires.

3.Turn power on. Indicator light should glow and compressor should start.

4.Observe motors for correct rotation.

Recommended Refrigerant Piping Practices

The system as supplied by Heatcraft Refrigeration Products, was thoroughly cleaned and dehydrated at the factory. Foreign matter may enter the system by way of the evaporator to condensing unit piping. Therefore, care must be used during installation of the piping to prevent entrance of foreign matter.

Install all refrigeration system components in accordance with applicable local and national codes and in conformance with good practice required for the proper operation of the system.

The refrigerant pipe size should be selected from the Line Sizing Tables. The interconnecting pipe size is not necessarily the same size as the stub-out on the condensing unit or the evaporator.

The following procedures should be followed:

a)Do not leave dehydrated compressors or filter-driers on condensing units open to the atmosphere any longer than is absolutely necessary.

b)Use only refrigeration grade copper tubing, properly sealed against contamination.

c)Suction lines should slope 1/4" per 10 feet towards the compressor.

d)Suitable P-type oil traps should be located at the base of each suction riser to enhance oil return to the compressor.

e)For desired method of superheat measurement, a pressure tap should be installed in each evaporator suction line in

the proximity of the expansion valve bulb.

f)When brazing refrigerant lines, an inert gas should be passed through the line at low pressure to prevent scaling and oxidation inside the tubing. Dry nitrogen is preferred.

g)Use only a suitable silver solder alloy on suction and liquid lines.

h)Limit the soldering paste or flux to the minimum required to prevent contamination of the solder joint internally. Flux only the male portion of the connection, never the female. After brazing, remove excess flux.

i)See Table 6 for discharge and liquid drain line sizes for remote condenser connections.

j)If isolation valves are installed at the evaporator, full port ball valves should be used.

Refrigerant Pipe Support

1.Normally, any straight run of tubing must be supported in at least two locations near each end of the run. Long runs require additional supports. The refrigerant lines should be supported and fastened properly. As a guide, 3/8 to 7/8 should be supported every 5 feet; 1-1/8 and 1-3/8 every 7 feet; and 1-5/8 and 2-1/8 every 9 to 10 feet.

2.When changing directions in a run of tubing, no corner should be left unsupported. Supports should be placed a maximum of 2 feet in each direction from the corner.

3.Piping attached to a vibrating object (such as a compressor or compressor base) must be supported in such a manner that will not restrict the movement of the vibrating object. Rigid mounting will fatigue the copper tubing.

4.Do not use short radius ells. Short radius elbows have points of excessive stress concentration and are subject to breakage at these points.

5.Thoroughly inspect all piping after the equipment is in operation and add supports wherever line vibration is significantly greater than most of the other piping. Extra supports are relatively inexpensive as compared to refrigerant loss.

Figure 9. Example of Pipe Support

Figure 10. Condensing Unit / Compressor to Wall Support

Suction Lines

Horizontal suction lines should slope away from the evaporator toward the compressor at the rate of 1/4 inch per 10 feet for good oil return. When multiple evaporators are connected in series using a common suction line, the branch suction lines must enter the top of the common suction line.

For dual or multiple evaporator systems, the branch lines to each evaporator should be sized for the evaporator capacity. The main common line should be sized for the total system capacity.

Suction lines that are outside of refrigerated space must be insulated. See the Line Insulation section on page 14 for more information.

Figure 11. Suction P-Traps

Slope 1/4" per 10 ft. toward compressor

Suction Line Risers

Prefabricated wrought copper traps are available, or a trap can be made by using two street ells and one regular ell. The suction trap must be the same size as the suction line. For long vertical risers, additional traps may be necessary. Generally, one trap is recommended for each length of pipe (approximately 20 feet) to insure proper oil movement. See Figure 11 for methods of constructing proper suction line P-traps.

Figure 12. Double Suction Riser Construction

Sized for

Minimum

Sized forLoad

Minimum

Load

Sized

Sized

for Full

for Full

Load

Load

NOTE:

A suction line trap must be installed at the point where piping changes the direction of refrigerant flow from any horizontal run to an upward vertical run.

Image 8
Contents Units Some units are pressurized with dry air or inert gas General Safety InformationWarranty Statement Decorative Fences Diagram City & Tower Water Connections Requirements for Remote and Water Cooled Condensing UnitsCondensing Unit Rigging and Mounting Ambient Fan Cycle Thermostat Settings Head Pressure ControlRefrigeration Oils Oil TypesPolyol Ester Lubricants Mineral OilsPhase Loss Monitor Recommended Refrigerant Piping PracticesRefrigerant Pipe Support Suction LinesHot gas line sizes for R-22, R404A and R507 Liquid LinesHot Gas Defrost Systems Unit Cooler Piping Line SizingCopper Tube, O.D., Type L Globe Valve Open Equivalent Feet of Pipe Due to Valve and Fitting FrictionRecommended Remote Condenser Line Sizes Recommended Line Sizes for R-22 000Recommended Line Sizes for R-404A and R507 Refrigerant Charging Instructions Field WiringEvacuation and Leak Detection Check Out and Start Up Example Operational Check OutSystem Balancing Compressor Superheat Electric Defrost Troubleshooting Operation of Paragon TimerOperation of Grasslin Timer General Sequence of OperationCheck liquid line solenoid valve operation System Troubleshooting ChartClean strainers Air-Cooled Condensing Units Preventive MaintenanceUnit Coolers Page Page Page Page Replacement Parts by

H-IM-CU specifications

Heatcraft Refrigeration Products has long been recognized as a leader in the refrigeration industry, and their H-IM-CU model is a prime example of innovative design and cutting-edge technology. The H-IM-CU is engineered to deliver exceptional performance and efficiency, catering to various commercial refrigeration needs.

One of the standout features of the H-IM-CU is its robust construction. The unit is designed with high-quality materials that ensure durability and long-lasting performance in demanding environments. This construction not only protects against wear and tear but also supports the reliable operation essential for business continuity.

The H-IM-CU incorporates advanced cooling technologies that enhance its efficiency. Equipped with a high-efficiency compressor, this model optimizes energy consumption, reducing operational costs while still maintaining optimal refrigerant temperatures. This energy-efficient design is particularly beneficial for businesses looking to minimize their carbon footprint and achieve sustainability goals.

An important characteristic of the H-IM-CU is its user-friendly control system. The intuitive interface allows operators to easily adjust and monitor temperature settings, ensuring that products are stored in favorable conditions. This user-centric design simplifies the management of refrigeration units, making it easier for staff to perform routine tasks.

Additionally, the H-IM-CU features a whisper-quiet operation, which is an advantage for businesses that prioritize a pleasant customer experience. This is achieved through effective sound-dampening technologies and smart engineering that minimize noise without compromising cooling performance.

Another significant highlight is the versatility of the H-IM-CU. It is suitable for a wide range of applications, from convenience stores to restaurants and supermarkets. This adaptability makes it a preferred choice for businesses seeking a reliable refrigeration solution that can cater to their specific needs.

Furthermore, the model boasts enhanced airflow technology that ensures even temperature distribution throughout the unit. This promotes efficient cooling and eliminates hotspots, keeping products at the desired temperature consistently.

Overall, the Heatcraft Refrigeration Products H-IM-CU stands out as a leading choice in commercial refrigeration. With its combination of durability, energy efficiency, user-friendly controls, quiet operation, and versatility, it meets the high standards of modern businesses looking for reliable cooling solutions. Investing in the H-IM-CU not only enhances product longevity but also aids in operational efficiency, making it a wise choice for any commercial refrigeration setup.