Troubleshooting and Pen Alignment of Recorder without Display

7.4 Alignment of Pen at Zero and 100 %

Procedure

You can align the pens to the zero and 100 % positions on the chart using the procedure in Table 7-6.If humidity causes the chart to change size, repeat the procedure as needed.

WARNING

SHOCK HAZARD

When the unit is powered a potentially lethal shock hazard exists at the AC line connections at TB1 on each printed circuit assembly (behing the chart plate). Make sure the unit power is disconnected before starting the procedure. More than one switch may be required to de-energize the recorder.

Failure to observe this precaution can result in exposure to a potentially lethal shock hazard.

Table 7-6 Procedure for Pen Alignment

Step

Action

Graphic

 

 

 

1

Place run switch SW5 to the setup position (toward the top of

 

 

the board) on the pen’s PCA.

 

 

 

See Figure 3-1 for location of SW5 (to

 

 

the right of TB1).

 

 

 

2

Press SW3 and SW4 simultaneously and release them.

See Figure 3-1 for location of SW3 and

 

The pen will move downscale toward the hub and be

SW4.

 

 

 

positioned at the previously set 0 % point on the chart within

 

 

approximately 10 seconds.

 

 

 

 

If the pen tip is greatly out of position, follow Steps 3 through 7. (Unless a pen arm has been replaced, this probably will not be necessary.) If pen position requires only minor adjustment, go to Step 8.

3

Turn off the power to the recorder before the pen begins to

 

 

move upscale (approximately 10 seconds).

 

 

 

 

4

To place the pen tips in approximately the correct position,

 

 

loosen the screw holding the pen 1 arm to the servo shaft

 

 

and move the pen arm to access the locking screw for the

 

 

pen 2 arm (if applicable).

 

 

 

 

5

Align the tip of pen 2 with the zero line on the chart and

 

 

tighten the locking screw.

 

 

 

 

6

Align the tip of pen 1 with the zero line on the chart and

 

 

tighten the locking screw.

 

 

 

 

7

Turn on the power and repeat Step 2.

 

 

 

 

8

To fine-tune the alignment of a pen, press the raise switch

See Figure 3-1 for the location of SW3

 

SW4 or lower switch SW3 on its PCA until the pen tip is

and SW4.

 

aligned with the zero line on the chart.

 

 

Approximately 10 seconds after the last press of the raise or

 

 

lower switch the pen will move to the previously set 100 %

 

 

point.

 

 

 

 

12/03