Input and Output Calibration for Recorder with Display

5.5 Input Calibration Procedure

Introduction

Before performing this procedure, be sure the recorder is wired for calibration as described in Subsection 5.4. Apply power and allow the recorder to warm up for 30 minutes before you calibrate.

Make sure “LOCK” is set to “NONE” (see Section 4 - Configuration, Startup and Operation of Recorder with Display).

ATTENTION

For Milliamp inputs, be sure the current source is at zero before switching on the calibrator.

Do not switch the calibrator on/off while it is connected to the recorder’s input. Failure to observe this precaution could result in damage to input circuits.

Calibration procedure sequence

The calibration procedure sequence for all inputs is listed in Table 5-9.The calibration procedure for inputs 1 and 2 is identical. The displays indicate the input number.

Press the

FUNC

key to change display as required (INP1 or INP2).

Table 5-9 Input Calibration Procedure Sequence

Step

Description

Press

Action/Result

1

Enter Calibration Mode

SET

 

Upper Display

 

 

 

CAL

 

 

UP

 

 

 

 

Lower Display

 

 

 

 

 

 

 

until you see

 

 

INPUT

 

 

 

 

 

 

 

 

If “CAL” doesn’t appear or prompt access is declined,

 

 

 

check “LOCK” configuration.

 

 

 

 

 

 

 

You will see:

 

FUNC

 

 

 

Upper Display

 

 

 

DIS

 

 

 

 

 

 

 

 

 

Lower Display

 

 

 

CAL IN

 

 

 

 

 

 

 

 

The calibration sequence is enabled and you will see:

 

 

 

 

 

 

Upper Display

 

 

 

BEGIN

 

 

 

 

 

 

 

 

 

Lower Display

 

 

 

 

CAL IN

 