DR4300 Circular Chart Recorder

4.3.9 Chart Parameters Set Up Group

Introduction

The functions in this group are used to specify proper chart function. For a 2-pen recorder the desired input channel is displayed on the left side of the operator interface.

Press FUNC key to select channel.

Chart group prompts

Table 4-7lists all the function prompts in the chart parameters set up group.

Press SET UP key until “CHART” appears in the lower display.

Press FUNC key to display parameters.

Table 4-7 Chart Parameter Definitions

Lower Display

Upper Display

 

 

Parameter

Prompt

Range of Setting

 

 

Definition

 

or Selection

 

 

 

 

 

 

CHTSPD

 

CHART SPEED—This is the time it will take to drive the

 

 

chart one complete revolution.

 

 

 

 

 

 

 

 

ATTENTION

This prompt only appears for pen 1

 

 

 

 

 

 

configuration of a two-pen recorder.

 

8HR

8 hour revolution

 

12HR

12 hour revolution

 

24HR [factory setting]

24 hour revolution

 

7DAYS

7 day revolution

 

– HR

– hour revolution—specify Hours per Revolution selection

 

 

at prompt “HR/REV”.

 

 

 

HR/REV

1 to 744 Hours

HOURS PER REVOLUTION—Set the desired chart

 

 

speed. Appears only if – HR was selected at prompt

 

 

“CHTSPD”.

 

 

 

CHTTYP

 

CHART TYPE—Selection is based on the type of chart.

 

LIN [factory setting]

Linear (even) or

 

NLIN

Non-Linear (i.e., J T/C or RTD)

 

 

 

 

 

 

 

 

ATTENTION

LIN chart type is automatically selected

 

 

 

 

 

 

when input type is linear (as defined by value of input set

 

 

up parameter “INTYP”).

 

 

 

 

 

90

DR4300 Circular Chart Recorder Product Manual

12/03

Page 102
Image 102
Honeywell DR4300 manual Chart Parameters Set Up Group, Chart group prompts, Chart Parameter Definitions, Chtspd, Chttyp