Configuration, Startup, and Operation of Recorder with Display

4.3.7 Input Parameters Set Up Group

Introduction

These are the parameters required to configure the temperature units, decimal location, actuation, high and low range values in engineering units, bias, filter, and burnout. For a 2-pen recorder, the desired input channel is displayed on the left side of the operator interface.

Press FUNC key to select channel.

Input group prompts

Table 4-5lists all the function prompts in the input set up group.

Press SETUP key until “INPUT” appears in the lower display.

Press FUNC key to display the parameters.

Table 4-5 Input Parameter Definitions

Lower Display

 

Upper Display

Parameter

Prompt

 

Range of Setting

Definition

 

 

or Selection

 

 

 

 

 

DECMAL

 

 

DECIMAL POINT LOCATION—This selection determines where

 

 

 

the decimal point appears in the display.

 

XXXX [factory setting]

None

 

XXX.X

One Place

 

XX.XX

Two Places

 

 

 

NOTE: Be sure the selection agrees with the value to be displayed.

 

 

 

If PV requires 4 whole digits, the decimal will not show. Value of “IN

 

 

 

TYP” parameter must be for a linear input type for two decimal

 

 

 

places to be displayed.

 

 

 

 

UNITS

 

 

TEMPERATURE UNITS—This selection will be indicated on the PV

 

 

 

display.

 

NONE

No units

 

F

[factory setting]

Degrees Fahrenheit

 

C

 

Degrees Celsius

 

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual

85

Page 97
Image 97