DR4300 Circular Chart Recorder

7.3.3 Pen Trace Troubleshooting

Procedure

Table 7-3explains how to troubleshoot a pen trace problem.

Table 7-3 Troubleshooting Pen Trace Failure Symptoms

Step

What to do

How to do it or

 

 

where to find the instructions

 

 

 

1

Check the ink cartridge for proper

Reposition or replace the ink cartridge as

 

installation.

described in Section 6 – Routine Maintenance.

 

 

If the pen arm is severely warped, replace the

 

 

pen arm as described in Section 9 – Replacing

 

 

Hardware Assemblies.

 

 

 

2

Check that the chart agrees with the

Replace wrong chart with correct chart. Refer to

 

actuation type and chart set up.

Section 3 – Configuration, Startup, and Operation

 

 

of Recorder without Display for instructions for

 

 

viewing the configuration.

 

 

See Section 6 – Routine Maintenance for

 

 

instructions for replacing the chart.

 

 

 

3

Check the pen alignment.

Follow the procedure in Subsection 7.4.

 

 

 

4

Look at printed circuit assembly (PCA) for

Press the reset switch SW2. The PCA will be

 

the pen to see if the red* LED is lit. This

initialized. If the problem was a software error,

 

LED is lit when the PCA failed a self-

the error may be cleared by the reset.

 

diagnostic, or an out-of-range input has

 

 

been detected. (Flashing green LED is

 

 

OK, it indicates that the processor is

*For Recorders with a display, the red LED is

 

active.)

 

used by an internal control signal and is not a

 

 

 

 

fault indicator.

 

 

 

5

Check the sensor for the proper type and

Verify the input configuration data and operation

 

its ability to function.

of the sensor.

 

 

Measure input signal at TB2 or apply calibration

 

 

source to verify input signal.

 

 

 

6

Replace the servo plate assembly.

Refer to the replacement procedure in Section 9

 

 

– Replacing Hardware Assemblies.

 

 

 

7

Replace the printed circuit assembly for

Refer to the replacement procedure in Section 9

 

the pen with the problem.

– Replacing Hardware Assemblies.

 

 

 

166

DR4300 Circular Chart Recorder Product Manual

12/03

Page 178
Image 178