Configuration, Startup, and Operation of Recorder with Display

4.3.10 Totalizer Parameters Set Up Group

Introduction

If the recorder hardware supports totalizer functions, the functions in this group are used to calculate and display the total flow volume as measured by the input. The displayed value is six digits with a configurable scale factor.

The totalized value can be in engineering units different from the input, by setting INP EU (engineering units of input) and TOT EU (engineering units of totalized value).

The total can be displayed with one or two decimal places to provide more resolution for selections that produce smal values (e.g., Acre-Feet). A Scaler configuration other than one will override the decimal display.

Control group prompts

Table 4-8lists all the function prompts in the totalizer function group.

For a 2-pen recorder, the desired input channel is displayed on the left side of the operator interface. Press

FUNC to select channel.

Press SETUP key until “TOTAL” appears in the lower display.

Press FUNC key to select the parameters.

Table 4-8 Totalizer Function Definitions

Lower Display

Upper Display

 

 

Parameter

Prompt

Range of Setting

 

 

Definition

 

or Selection

 

 

 

 

 

 

 

 

(actual current

(current scale factor)

VIEW CURRENT TOTALIZED VALUE—This selection lets

totalized value)

Example: E1

you view the current totalized value.

 

In the example shown, E1 represents the exponential value

 

 

 

 

that applies to the total (total times 101).

 

 

See “SCALER” function prompt in this group for choices.

 

 

 

RESET

YES

RESET TOTALIZER TO ZERO—This parameter is used to

 

NO [factory setting]

reset the totalizer to zero.

 

Selecting YES will reset the totalizer to zero. When the reset

 

 

 

 

action has been performed, the parameter will be set to NO

 

 

automatically.

 

 

 

 

 

 

 

 

ATTENTION

In order for this prompt to appear, the

 

 

 

 

 

 

“RSTABL” function (described later in this table) must be set

 

 

to “KEY”.

 

 

 

TOTAL

ENAB

TOTALIZATION FOR INPUT—This parameter is used to

 

DIS [factory setting]

enable or disable the totalizer function. This prompt appears

 

first if “DIS” is the current choice.

 

 

ENABLE allows configuration of the rest of the prompts

 

 

associated with totalization.

 

 

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual