D.2 Starting and Stopping Tuning with Accutune II

Procedure

After “TUNE” has been enabled in the tuning set up group as described in Section 4, use the procedure in Table D-1to start tuning.

To abort tuning in progress, press the MAN/AUTO/RESET key to take the recorder out of Auto mode. The message “AbRT” (abort) will be displayed as the value of tuning set up group parameter “AT ERR”. The tuning parameters will retain the values they had at the start of the Accutune operation.

Table D-1 Procedure for Starting Accutune II

Step

 

Press

 

 

 

Action/Result

 

 

 

 

 

 

 

 

1

 

 

 

 

Lower Display

 

If “TuneOF” (tune off) does not appear, then

 

 

 

 

 

 

DISP

 

 

TuneOF

 

Accutune is not enabled.

 

 

 

 

 

 

 

 

 

until you see

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

to toggle to

 

 

 

 

or

 

Lower Display

 

 

 

 

 

TuneON

Tuning will begin and the lower display will flash

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

“TUNING”. When tuning has been completed the

 

 

 

 

 

 

lower display will again show “TuneOF”.

 

 

 

 

 

 

 

 

226

DR4300 Circular Chart Recorder Product Manual

12/03

Page 238
Image 238