Honeywell DR4300 Procedure for selecting manual or automatic mode

Models: DR4300

1 262
Download 262 pages 56.21 Kb
Page 145
Image 145

Configuration, Startup, and Operation of Recorder with Display

4.5.2.2 Changing Control Mode and Adjusting Output Manually

Available modes

The recorder can operate in one of two modes.

Manual: When switched to manual mode, the recorder holds its output at the last value used during automatic operation and stops adjusting the output for changes in process variable. In manual, the operator uses the keypad to adjust the output by changing the value shown in the upper display.

If the switch to manual is the result of an input failure sending the channel to failsafe operation, the output value displayed when the controller first switches to manual will be the value of the “FAILSF” parameter in the control set up group. This “FAILSF” value is expressed as a percentage. The output can be any value between 0 % and 100 %.

Automatic with Local Setpoint: In automatic local mode, the recorder uses the local setpoint and automatically adjusts the output to maintain the setpoint at the desired value. In this mode you can adjust the setpoint as described in Subsection 4.5.2.3.

Procedure for selecting manual or automatic mode

Table 4-29includes procedures for selecting automatic or manual mode, and for changing the output while in manual.

Table 4-29 Procedure for Selecting Automatic or Manual Mode

Step

Operation

Press

Action/Result

1

Selecting automatic

MAN

Until “A” indicator is ON.

 

mode

The recorder regulates its output to maintain the PV at

 

AUTO

 

 

RESET

the desired setpoint.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Selecting manual

 

Until “M” indicator is ON.

MAN

 

mode

The recorder holds its output at the last value used

 

AUTO

 

 

RESET

during automatic operation and stops adjusting the

 

 

 

output for changes in setpoint or process variable.

 

 

 

 

 

 

If you get a “KEYERR” prompt, be sure control has

 

 

 

 

been enabled through configuration as described

 

 

 

 

earlier in this section.

 

 

 

 

3

Adjust the output in

 

Adjust the output value while in manual mode.

 

manual mode

or

 

Upper Display

 

 

 

 

 

 

 

shows the input value.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lower Display

 

 

 

 

 

 

 

 

 

shows OT and the output value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in % for the selected channel.

 

 

 

 

4

Return to automatic

 

“A” indicator appears indicating automatic mode.

MAN

 

mode

AUTO

 

 

 

 

 

 

 

 

 

RESET

 

 

 

 

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual

133

Page 145
Image 145
Honeywell DR4300 Procedure for selecting manual or automatic mode, Procedure for Selecting Automatic or Manual Mode