DR4300 Circular Chart Recorder

Lower Display

Upper Display

 

 

Parameter

Prompt

Range of Setting

 

 

Definition

 

or Selection

 

 

 

 

 

 

 

 

FAILSF

0 % to 100 %

FAILSAFE OUTPUT VALUE—Select the value you want

 

[factory setting = 0]

the output to be when power is restored after a power

 

down. The value used here will also be used as the

 

 

output level if the input fails when input group “BRNOUT”

 

 

parameter is set to “NONE”.

FSMODE

 

FAILSAFE MODE

 

AUTO

Failsafe Latching Disabled – When the recorder goes

 

 

into “Failsafe”, the control mode does not change. The

 

 

output assumes the failsafe value if the recorder is in auto

 

 

mode. When the cause of failsafe is removed, normal

 

 

automatic control action resumes.

 

MAN

Failsafe Latching Enabled – When the recorder goes

 

 

into “Failsafe”, the control mode changes to Manual. If the

 

 

recorder was in Auto mode, the output assumes the

 

 

failsafe value. When the cause of failsafe is removed, the

 

 

recorder remains in manual mode.

PBorGN

 

PROPORTIONAL BAND or GAIN—Use this parameter

 

 

to choose whether you want to specify the proportional

 

 

term in the PIDA or PDMR algorithms in terms of percent

 

 

proportional band or of gain. Your choice here affects

 

 

which tuning prompt, “PB” or “GAIN”, is displayed.

 

 

This parameter is displayed only if the “CTRALG” (control

 

 

algorithm) is set to “PIDA” or “PDMR”.

 

PB

Percent proportional band is the percent of the range of

 

 

the measured variable for which a proportional-only

 

 

controller will produce a 100 % change in its output.

 

GAIN [factory setting]

Gain is the ratio of output change (%) over the measured

 

 

variable change (%) that caused it.

 

 

The relationship between %PB and gain can be

 

 

expressed as: GAIN = 100

 

 

 

 

%PB

 

 

For example, setting PB = 20 % will have the same effect

 

 

on control as setting GAIN = 5. Therefore, if the change in

 

 

the PV input were 3 % of the whole range of possible

 

 

input values, then the resulting change in the output due

 

 

to proportional only control would be 15 % of the output’s

 

 

range, regardless of whether PBorGN = PB and PB = 20,

 

 

or PBorGN = GN and GAIN = 5.

 

 

Another example: Setting PB = 50 % will have the same

 

 

effect as setting GAIN = 2. In this case, if the change in

 

 

input were again 3 % of range, then the resulting output

 

 

change would be 6 %.

 

 

 

 

 

 

 

ATTENTION

If the setting of PBorGN is changed,

 

 

 

 

 

 

you must change the value of the associated tuning

 

 

parameter (“PB” or “GAIN”) if you want to maintain the

 

 

same control action. For example, suppose PBorGN = PB

 

 

and the value of tuning parameter “PB” = 20. If you

 

 

change PBorGN to GAIN, the value of tuning parameter

 

 

“GAIN” will now be 20 (the value formerly assigned to

 

 

“PB”). If you want the same control action you had before,

 

 

you must change the value of “GAIN” to 5.

 

 

 

 

 