Configuration, Startup, and Operation

 

 

 

 

 

 

of Recorder with Display

 

 

 

 

 

 

 

 

 

Lower Display

Upper Display

 

 

Parameter

 

 

Prompt

Range of Setting

 

 

Definition

 

 

 

or Selection

 

 

 

 

 

 

 

 

 

 

LD CAL

 

LOAD CALIBRATION VALUES—This parameter is used to specify

 

 

 

 

which set of calibration values you want to use.

 

 

 

FAC [factory setting]

Factory—Uses built-in calibration values (stored in read-only

 

 

 

 

memory).

 

 

 

FLD

Field—Uses calibration values stored as a result of the field

 

 

 

 

calibration procedure described in Section 5.

 

 

 

 

 

 

 

 

 

 

 

 

ATTENTION

Until field calibration has been done,

 

 

 

 

 

 

 

 

 

 

FLD uses the same calibration values as FAC. When field

 

 

 

 

calibration is performed, the value of LD CAL is automatically set to

 

 

 

 

FLD at the completion of the field calibration operation.

 

 

 

 

 

 

 

INP HI

–999 to 9999

INPUT HIGH RANGE VALUE in engineering units is displayed but

 

 

 

[factory setting = 900]

can only be configured for linear input type.

 

 

 

Otherwise, this is a read-only display of the higher range value for

 

 

 

 

 

 

 

 

the selected T/C or RTD input type.

 

 

 

 

• Scale the input signal to the display value you want for 100 %.

 

 

 

 

EXAMPLE:

 

 

 

 

 

Actuation (Input) = 4 to 20 mA

 

 

 

 

 

Process Variable = Flow

 

 

 

 

 

Range of Flow = 0 to 250 Gal/Min

 

 

 

 

 

High Range display value = 250

 

 

 

 

 

Then 20 mA = 250 Gal/Min

 

 

 

 

 

 

 

INP LO

–999 to 9999

INPUT LOW RANGE VALUE in engineering units is displayed but

 

 

 

in Engineering Units

can only be configured for linear input type.

 

 

 

[factory setting =

• Otherwise, this is a read-only display of the low range value for

 

 

 

 

the selected T/C or RTD input type.

 

 

 

300]

 

 

 

 

• Scale the input signal to the display value you want for 0 %. See

 

 

 

 

 

 

 

 

 

example in “INPHI”.

 

 

 

 

 

 

 

BIAS

–99.9 to 999.9

INPUT BIAS—Used to compensate the input for drift of an input

 

 

 

[factory setting = 0]

value due to deterioration of a sensor, or some other cause; select

 

 

 

the value you want on the input.

 

 

 

 

 

 

 

FILTER

0 to 120 seconds

FILTER FOR INPUT—A software digital filter is provided for the

 

 

 

No filter = 0

input to smooth the input signal. You can configure the first order

 

 

 

[factory setting = 0]

lag time constant from 1 to 120 seconds. If you do not want filtering,

 

 

 

enter 0.

 

 

 

 

 

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual

87

Page 99