Troubleshooting and Pen Alignment of Recorder with Display

8.5.2 Recorder Failure Troubleshooting

Procedure

Table 8-6explains how to troubleshoot recorder failure symptoms.

Table 8-6 Troubleshooting Recorder Failure Symptoms

Step

What to do

How to do it or

 

 

where to find the instructions

 

 

 

1

Check the supply voltage.

Measure the line voltage across the line and

 

 

neutral connections at TB1 on the printed circuit

 

 

assembly (PCA) on the right (for pen 1).

 

 

 

2

Check the connections to TB1 on the pen

Refer to ac wiring procedures in Section 2 –

 

1 PCA.

Installation.

 

 

 

3

Check the system for brown-outs, heavy

Refer to Section 2 – Installation.

 

load switching, etc.; and conformance to

 

 

installation instructions.

 

 

 

 

4

Replace the PCA for pen 1.

Refer to the replacement procedures in Section 9

 

 

– Replacing Hardware Assemblies.

 

 

 