DR4300 Circular Chart Recorder

Condition

 

Specifications

 

Solid State Relay Output

 

SPST solid state contacts consisting of a triac NO output.

 

 

 

Internally socketed.

 

 

 

Resistive Load: 1.0 A @ 25 °C for 120 Vac or 240 Vac.

 

 

 

0.5 A @ 55 °C for 120 Vac or 240 Vac.

 

 

 

Inductive Load: 50 VA @ 120 Vac or 240 Vac.

 

 

 

 

 

Open Collector Output

 

Maximum Sink Current: 20 mA

 

 

 

Internally powered @ 30 Vdc

 

 

 

Opto-isolated from all other circuits except current output, but not from each other.

 

 

 

Socketed jumper assembly replaces relay.

 

 

 

 

 

Modbus Communication

 

Baud Rate: 19,200 maximum, configurable for models with display;

 

 

 

fixed at 9,600 for models without display

 

 

 

Protocol: Modbus

 

 

 

Length of Link: 1,219 m [4,000 ft] maximum

 

 

 

Link Characteristics: Two-wire, multidrop

 

 

 

 

 

Digital Inputs

 

+24 Vdc source for external dry contacts or isolated solid state contacts for either

 

(Supply common with

 

of the two inputs.

 

current output)

 

On contact closure the recorder will respond according to how each digital input is

 

 

 

 

 

 

configured. Opening contact causes return to previous state.

 

 

 

 

 

Transmitter Power

 

24 Vdc with adjustment of ± 6 % (22.6 to 25.4)

 

 

 

100 mA maximum output

 

 

 

 

 

14

DR4300 Circular Chart Recorder Product Manual

12/03

Page 26