Configuration, Startup, and Operation

 

 

 

 

 

 

of Recorder with Display

 

 

 

 

 

 

 

 

 

Lower Display

Upper Display

 

 

Parameter

 

 

Prompt

Range of Setting

 

 

Definition

 

 

 

or Selection

 

 

 

 

 

 

 

 

 

 

MINRPM

RPM

MINUTES PER REPEAT or REPEATS PER MINUTE

 

 

 

MIN [factory setting]

Use this parameter to choose whether you want to specify

 

 

 

the integral term (reset) in the PIDA algorithm in terms of

 

 

 

 

length (minutes per repeat) or frequency (repeats per

 

 

 

 

minute). Your choice here affects which tuning prompt, “I

 

 

 

 

MIN” or “I RPM”, is displayed.

 

 

 

 

The relationship between the two ways of thinking about

 

 

 

 

reset is demonstrated by this example:

 

 

 

 

20 repeats per minute = 0.05 minutes per repeat.

 

 

 

 

This parameter is displayed only if the “CTRALG” (control

 

 

 

 

algorithm) is set to “PIDA”.

 

 

 

 

 

 

 

 

 

 

 

 

ATTENTION

If the setting of MINRPM is changed,

 

 

 

 

 

 

 

 

 

 

you must change the value of the associated tuning

 

 

 

 

parameter (“I MIN” or “I RPM”) if you want to maintain the

 

 

 

 

same control action. For example, suppose MINRPM = I

 

 

 

 

RPM and the value of tuning parameter “I RPM” = 2. If

 

 

 

 

you change MINRPM to I MIN, the value of “I MIN” will

 

 

 

 

now be 2 (the value formerly assigned to “I RPM”). If you

 

 

 

 

want the same control action you had before, you must

 

 

 

 

change the value of “I MIN” to 0.5.

 

 

 

 

 

 

 

 

12/03