Honeywell DR4300 manual TIME/CURRENT Duplex Relay = Cool-Similar to, Full factory setting

Models: DR4300

1 262
Download 262 pages 56.21 Kb
Page 107
Image 107

 

 

 

Configuration, Startup, and Operation

 

 

 

 

of Recorder with Display

 

 

 

 

 

 

 

Lower Display

Upper Display

Parameter

 

 

Prompt

Range of Setting

Definition

 

 

 

or Selection

 

 

 

 

 

 

 

 

OUTALG

Tcur

TIME/CURRENT DUPLEX (Relay = Cool)—Similar to

 

 

(continued)

 

CurT, except that current is active for 50 % to 100 %

 

 

 

 

(tuning set 1) and relay is active for 0 % to 50 % (tuning

 

 

 

 

set 2).

 

 

 

 

Control group functions “CURRNG” and "DBAND" are

 

 

 

 

affected.

 

 

 

 

 

 

 

CURRNG

 

CURRENT RANGE—This parameter appears if

 

 

 

 

“OUTALG” is set to “CurT” or “Tcur”.

 

 

 

FULL [factory setting]

FULL—Current output is calculated over the full range

 

 

 

 

0 % to 100 %. For example, a control output of 50 %

 

 

 

HALF

would result in a 12 mA current output.

 

 

 

HALF—Current output is calculated over half the range

 

 

 

 

(50 % to 100 %). For example, a control output of 50 %

 

 

 

 

would result in a 4 mA current output.

 

 

 

 

 

 

 

CTRALG

 

CONTROL ALGORITHM—Use this to specify the type of

 

 

 

 

control appropriate for your application.

 

 

 

ON/OFF [factory setting]

ON/OFF is the simplest type of control. The output can be

 

 

 

 

either ON (100 %) or OFF (0 %). The process variable

 

 

 

 

(PV) is compared with the setpoint (SP) to determine the

 

 

 

 

sign of the error (ERROR = PV–SP). The ON/OFF

 

 

 

 

algorithm operates on the sign of the error.

 

 

 

 

In direct-acting control (set with parameter “ACTION”

 

 

 

 

described below), when the error is positive, the output is

 

 

 

 

100 %. When the error is negative, the output is 0 %. If

 

 

 

 

the control action is reverse, the opposite is true. An

 

 

 

 

adjustable overlap is provided between the ON and OFF

 

 

 

 

states. (See “HYST” below.)

 

 

 

 

DUPLEX ON/OFF is an extension of this algorithm that

 

 

 

 

applies when the “OUTLAG” is set for “RLYD” (relay

 

 

 

 

duplex). It allows for the operation of a second ON/OFF

 

 

 

 

output. There is a configurable deadband (see “DBAND”

 

 

 

 

below) between the operating ranges of the two inputs,

 

 

 

 

and a separately configurable overlap (“HYST”) of the ON

 

 

 

 

and OFF states of each output. With no relay action the

 

 

 

 

controller output will read 50 %.

 

 

 

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual

95

Page 107
Image 107
Honeywell DR4300 manual TIME/CURRENT Duplex Relay = Cool-Similar to, Full factory setting, ON/OFF factory setting