Configuration, Startup, and Operation

 

 

 

 

of Recorder with Display

 

 

 

 

 

 

 

Lower Display

Upper Display

Parameter

 

 

Prompt

Range of Setting

Definition

 

 

 

or Selection

 

 

 

 

 

 

 

 

OUTALG

Tcur

TIME/CURRENT DUPLEX (Relay = Cool)—Similar to

 

 

(continued)

 

CurT, except that current is active for 50 % to 100 %

 

 

 

 

(tuning set 1) and relay is active for 0 % to 50 % (tuning

 

 

 

 

set 2).

 

 

 

 

Control group functions “CURRNG” and "DBAND" are

 

 

 

 

affected.

 

 

 

 

 

 

 

CURRNG

 

CURRENT RANGE—This parameter appears if

 

 

 

 

“OUTALG” is set to “CurT” or “Tcur”.

 

 

 

FULL [factory setting]

FULL—Current output is calculated over the full range

 

 

 

 

0 % to 100 %. For example, a control output of 50 %

 

 

 

HALF

would result in a 12 mA current output.

 

 

 

HALF—Current output is calculated over half the range

 

 

 

 

(50 % to 100 %). For example, a control output of 50 %

 

 

 

 

would result in a 4 mA current output.

 

 

 

 

 

 

 

CTRALG

 

CONTROL ALGORITHM—Use this to specify the type of

 

 

 

 

control appropriate for your application.

 

 

 

ON/OFF [factory setting]

ON/OFF is the simplest type of control. The output can be

 

 

 

 

either ON (100 %) or OFF (0 %). The process variable

 

 

 

 

(PV) is compared with the setpoint (SP) to determine the

 

 

 

 

sign of the error (ERROR = PV–SP). The ON/OFF

 

 

 

 

algorithm operates on the sign of the error.

 

 

 

 

In direct-acting control (set with parameter “ACTION”

 

 

 

 

described below), when the error is positive, the output is

 

 

 

 

100 %. When the error is negative, the output is 0 %. If

 

 

 

 

the control action is reverse, the opposite is true. An

 

 

 

 

adjustable overlap is provided between the ON and OFF

 

 

 

 

states. (See “HYST” below.)

 

 

 

 

DUPLEX ON/OFF is an extension of this algorithm that

 

 

 

 

applies when the “OUTLAG” is set for “RLYD” (relay

 

 

 

 

duplex). It allows for the operation of a second ON/OFF

 

 

 

 

output. There is a configurable deadband (see “DBAND”

 

 

 

 

below) between the operating ranges of the two inputs,

 

 

 

 

and a separately configurable overlap (“HYST”) of the ON

 

 

 

 

and OFF states of each output. With no relay action the

 

 

 

 

controller output will read 50 %.

 

 

 

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual

95

Page 107
Image 107
Honeywell DR4300 manual TIME/CURRENT Duplex Relay = Cool-Similar to, Full factory setting, ON/OFF factory setting