Installation

 

 

 

 

Condition

Specifications

 

Input Filter

Without Display: Analog with time constant of 3 seconds and digital with time

 

 

constant of 1 second.

 

 

 

With Display: Analog with time constant of 3 seconds and digital adjustable 0

 

 

seconds to 120 seconds.

 

 

 

 

 

Case

Molded, foamed-Noryl with gasketed door to meet NEMA 3 enclosure

 

 

requirements.

 

 

 

 

 

Pen

Disposable fiber-tip ink cartridge, line length per cartridge more than 305 m

 

 

[1000 ft]

 

 

 

One Pen: Purple

 

 

 

Two Pen: Purple (pen 1) and red (pen 2)

 

 

 

NOTE: Only pen 1 (purple) is referenced to the chart time line.

 

 

 

 

Chart

262 mm [10.32-inch] diameter chart with standard preprinted markings and a

 

 

calibrated width of 100 mm [4 inches].

 

 

 

 

 

 

Wiring Connections

Screw terminals (2 piece)

 

 

 

 

 

 

Color

Case: Black

 

 

 

Door: Standard—Gray; Optional—Carribean blue or black

 

 

 

 

 

Weight

5.4 kg [12 lbs]

 

 

 

 

 

 

Mounting

Panel-, pipe- or surface-mounted

 

 

 

 

 

Installation Category

Category II: Energy-consuming Equipment Supplied from the Fixed Installation,

 

(Overvoltage Category)

Local Level Appliances, and Industrial Control Equipment (EN61010-1).

 

 

 

 

Pollution Degree

Pollution Degree 2: Normally Non-conductive Pollution with Occasional

 

 

Conductivity Caused by Condensation (Ref. IEC 664-1).

 

 

 

 

EMC Classification

Group 1, Class A: ISM Equipment (EN55011, emissions), Industrial Equipment

 

 

(EN50082-2, Immunity).

 

 

 

 

 

 

Dielectric Insulation

AC Main to Inputs/Outputs

250 Vac

 

 

Input to Input

250 Vac

 

 

Input to Output

250 Vac

 

 

(except Digital Input to Current Output)

 

 

 

AC Main to Transmitter Power

250 Vac

 

 

 

 

 

Options

 

 

 

Current Output (Isolated)

Range can be set anywhere between 4 mA and 21 mA, and as direct or reverse

 

 

action.

 

 

 

Resolution: 11 bits for 4 mA to 21 mA

 

 

 

Accuracy: 0.5 % full scale

 

 

 

Temperature Stability: 0.1 % F.S./°C

 

 

 

Load Resistance: 0 ohms to 600 ohms

 

 

 

 

 

 

Electromechanical Relay

SPDT contacts. Internally socketed.

 

 

Output

Resistive Load: 5 A @ 120 Vac or 2.5 A @ 240 Vac or 30 Vdc.

 

 

Inductive Load: 50 VA @ 120 Vac or 240 Vac.

 

 

 

Motor: 1/6 H.P.

 

 

 

 

 

12/03

DR4300 Circular Chart Recorder Product Manual

13

Page 25
Image 25
Honeywell DR4300 Requirements, ft One Pen Purple Two Pen Purple pen 1 and red pen, Calibrated width of 100 mm 4 inches