Introduction

The recorder is almost ready for operation when you have:

mounted and wired the recorder as described in Section 2

set up the recorder as described in Subsection 3.2

prepared the recorder as described in Subsection 3.3.2

The only remaining tasks are aligning the chart time and applying power.

Procedure

To set the chart time and apply power, follow the procedure in Table 3-5.(See also Figure 3-5.)

Table 3-5 Startup Procedure

Step

Action

1Open the door.

2Pull up the pen lifter to raise the pen(s) from the chart plate. Open the hub locking clip.

3Turn the chart until the desired time line on the chart is aligned with the time index on the chart plate and pen 1 before closing the locking clip on the hub. Push down on the lifter to return the pen(s) to the chart.

CAUTION: Do not try to rotate the hub.

4Close the door and apply power.

5The pen(s) will move into position and the recorder will start to track the input value.

Time index

Pen lifter

Large chart hub

24212

Figure 3-5 Setting Chart Time to Time Index

12/03

DR4300 Circular Chart Recorder Product Manual

69